6ES7 194-3AA00-0BA0
Siemens 6ES7 194-3AA00-0BA0 ET 200eco M12 / 7/8″ Connection Block
6ES7 194-3AA00-0BA0 is the M12 / 7/8″ terminal block that carries PROFIBUS DP communication and 24 V DC supplies to a classic PROFIBUS-based SIMATIC ET 200eco I/O module. It has two M12 PROFIBUS ports, two 7/8″ power ports and two rotary coding switches for the station address. It is not an input or output module by itself; it operates only when fitted to a compatible ET 200eco I/O body.
Short definition and correct classification
Siemens identifies the unit as an “M12, 7/8″ terminal block.” DP1 accepts the incoming PROFIBUS DP line and DP2 loops the bus to the following node; X01 accepts the 24 V supplies and X02 loops them onward. The incoming and loop-through sockets are internally interconnected as a T function. The product therefore belongs with ET 200 connection modules and ET 200 terminal blocks, not with signal modules.
Technical data
Manufacturer / family: Siemens SIMATIC DP, ET 200eco
Order number: 6ES7 194-3AA00-0BA0
Product type: M12 / 7/8″ connection and terminal block
PROFIBUS DP ports: DP1 incoming and DP2 loop-through; two M12 ports
24 V DC supply ports: X01 incoming and X02 loop-through; two 7/8″ ports
Address setting: PROFIBUS address 1–99 by two rotary selectors
Dimensions: 79 × 60 × 29 mm
Approximate weight in the manual: 392 g
Typical power loss: 2 W; dependent on the current looped through the block
Maximum loop-through current: 6 A at 1L+ and 8 A at 2L+
System degree of protection: IP65 / IP66 / IP67 in the ET 200eco assembly when correctly fitted, sealed and capped
M12 and 7/8″ pin assignments
DP1 / DP2 M12 PROFIBUS:
Pin 1: P5V2 supply +
Pin 2: Data channel A, RxD/TxD-N
Pin 3: M5V2 data reference potential
Pin 4: Data channel B, RxD/TxD-P
Pin 5 and thread: Shield
X01 / X02 7/8″ supply:
Pin 1: 2M load-voltage ground
Pin 2: 1M electronics / sensor-supply ground
Pin 3: PE protective conductor
Pin 4: 1L+ electronics / sensor supply
Pin 5: 2L+ load-voltage supply
Check pin numbers against the Siemens drawing viewed from the front of the terminal block, not from an assumed cable-side view. PROFIBUS shielding and PE continuity deserve particular attention when field-assembled cables or metal connector shells are used. See the ET 200 PROFIBUS and PROFINET components section for related network hardware.
Compatibility and selection checks
6ES7 194-3AA00-0BA0 is the M12 / 7/8″ connection block intended for the PROFIBUS DP ET 200eco I/O modules covered by the Siemens ET 200eco manual. The alternative 6ES7 194-3AA00-0AA0 performs the connection function with ECOFAST connectors and is not a cable-for-cable substitute. Before purchase, confirm that the installed field cabling uses M12 and 7/8″ connectors, that the I/O body is the classic ET 200eco type, and that the complete order number is legible on the label. This product is not a universal adapter for ET 200eco PN, ET 200pro or ET 200S.
For system-level selection, also review technical information about Siemens ET 200, ET 200 power-supply modules, ET 200 power-distribution modules and other ET 200 network interfaces.
Installation and commissioning guidance
De-energize first: Installation, removal and connector work must be performed on a de-energized system by qualified personnel. Siemens specifically states that the 7/8″ connector must not be removed during operation; switch off the 2L+ load voltage before removal.
Secure the block: Seat the connection block squarely on the I/O body and tighten its screws diagonally to 1–1.3 Nm. IP65 / IP66 / IP67 protection depends on firm attachment, intact seals and approved caps on unused sockets.
Set the address: The lower selector sets the units digit and the upper selector sets the tens digit. Select a unique address from 1 to 99 that matches the engineering project. Refit the sealing caps at 0.5–0.8 Nm. A changed address is accepted only after the next POWER ON.
Terminate the bus: DP1 is the incoming port and DP2 the loop-through port. The last PROFIBUS node requires the appropriate M12 terminating resistor. Verify the continuation cable, shield and equipotential bonding according to the installation rules. Do not exceed 6 A on 1L+ or 8 A on 2L+; size the cable and calculate voltage drop for the actual run.
Checks for a used unit
Start by reading the complete 6ES7 194-3AA00-0BA0 label and hardware revision. Inspect the M12 and 7/8″ threads for impact damage, pins for bending or corrosion, the housing for cracks, the sealing face for cuts, and all four fastening points for damage. Confirm that both rotary address switches move without binding, their sealing caps are present, and the internal contacts show no heat discoloration. Before energizing, test DP1–DP2 and X01–X02 continuity, PE and shielding. Perform insulation and functional tests only with a suitable approved procedure.
Official Siemens documents
+ Siemens ET 200eco Operating Instructions – English, 08/2014, 114-page PDF
+ Siemens ET 200eco / ET 200pro cable and connector selection document – English PDF
+ Siemens 6ES7 194-3AA00-0BA0 dynamic product data sheet
+ Otomasyon AVM Siemens ET 200 PDF manual archive
Related topics
ET 200 analog input modules • ET 200 digital output modules • ET 200 special output modules • ET 200 additional modules • ET 200 functional modules • ET 200 safety modules • Siemens ET 200 PROFIsafe • Analog input and output guide • Second-hand automation products
Reminder: Siemens 6ES7 194-3AA00-0BA0 and other SIMATIC parts are offered by Otomasyon AVM subject to stock. Some items may be used; evaluate the label, revision, physical condition and system compatibility before purchase. The same hardware revision may not be restocked after it is sold. This page supports product selection and maintenance but does not replace binding technical approval.
Note: Commissioning, measurement and energization must be performed by qualified personnel in accordance with current Siemens documentation and site safety rules. You can share field observations through the Siemens automation contact page.