Siemens 6ES7 193-0CB30-0XA0 ET 200B TB4/DC Terminal Block
Siemens 6ES7 193-0CB30-0XA0 is the TB4/DC terminal block for the ET 200B series within the SIMATIC ET 200 family. It accommodates digital electronics blocks and has three-tier spring terminals in a 235 mm-wide format. When replacing a base in an existing station, check the full order number together with the electronics-block identification and field wiring.
What the TB4/DC does
The terminal block holds the field wiring, while the electronics block fitted above it provides the input and output functions. Field cables can remain on the base when the electronics block is replaced. Identifying the correct assembly therefore starts with reading both labels, rather than selecting a terminal block by appearance alone.
Separating the roles of the PLC, digital input module and digital output module helps narrow down a replacement enquiry. For example, an output's load capacity cannot be established from the base's order number.
Three-tier terminals and protective earth
The three terminal tiers arrange signal, supply and M reference connections. Three tiers do not mean three channels. Individual terminal assignments and supply groups must be checked against the installed electronics block.
The TB4/DC does not have the additional fourth PE terminal row found on the TB4-4/DC. The base still has its own PE connection. Keep the functions of the M reference and protective earth clear in the wiring documentation. When transferring wiring from another base, identify each connection from the diagram rather than matching terminal positions visually.
Compatible ET 200B electronics blocks
Supported electronics blocks include ET 200B-32DI, ET 200B-32DI 0.2 ms, ET 200B-16DO/2A, ET 200B-32DO, ET 200B-16DI/16DO, ET 200B-24DI/8DO and ET 200B-24DI/8DO 0.2 ms.
Describing this product simply as a “32-input terminal” leaves out other supported configurations. Include the complete electronics-block number when identifying a replacement. If a different electronics block is being considered, compare its I/O allocation, supply grouping and PLC hardware configuration before proceeding.
Electrical ratings and cabinet layout
The specified nominal supply is 24 V DC, with a permissible range of 18.5–30 V DC including ripple and an IP20 protection rating. The Siemens data sheet's 100–200 mA internal logic consumption is separate from field-load consumption and output-channel current ratings.
ET 200B catalogue conditions allow 0 to +60 °C for horizontal mounting on a vertical surface and 0 to +40 °C for other orientations. Cabinet planning should also allow access to the bus connector, cable routes and parts that will need servicing.
Explore the power supply modules and power distribution modules categories when reviewing related equipment. Match any proposed component to the actual station design and wiring requirements.
PROFIBUS, station addressing and STOP/RUN
The base carries the PROFIBUS-DP connection, station address selector, STOP/RUN switch and fuse. A new address takes effect following a STOP-to-RUN transition. The base requires a suitable electronics block to form an operational remote I/O station.
Review the PROFIBUS network arrangement alongside the installed connection components. If an upgrade to PROFINET is planned, assess the controller, network and field wiring together as part of the migration.
STOP does not establish that every load connection is de-energized. Isolate the relevant energy sources and verify absence of voltage before wiring work or component replacement. Recording the station address and photographing the connections before removal gives the commissioning technician a useful reference.
Checking sensors and field wiring
If a sensor signal is missing, examine the sensor supply, output type, cable and input channel before deciding to replace the base. The explanations of sink and source wiring and two-wire sensors provide background for these checks.
For metal detection applications, review how inductive sensors work before comparing inductive sensor models. Check electrical compatibility alongside sensing distance, mounting arrangement and housing dimensions.
Distinguishing similar terminal blocks
6ES7 193-0CB30-0XA0 identifies the three-tier spring-terminal TB4/DC. 6ES7 193-0CB40-0XA0 identifies the four-tier spring-terminal TB4-4/DC, while 6ES7 193-0CB10-0XA0 identifies the three-tier screw-terminal TB2/DC. Similar width does not remove the need to compare the wiring arrangements.
When assessing a used component, inspect the terminal housing, spring connections, electronics-block contacts and retaining features. A readable label photograph and a close view of the wiring area are particularly useful when distinguishing bases with similar housings.
PDF manuals and wiring diagrams
Visit the Siemens ET 200 manuals page for documentation. Section 7.2.6 of the ET 200B Distributed I/O Station manual covers the TB4/DC base. For terminal assignments, also consult the section for the installed electronics block. The Siemens ET 200 overview introduces the wider family.
Related topics
Explore Siemens S7 PLCs and SIMATIC S7-300 when researching the controller and communications hardware. Keeping the base, electronics-block and controller numbers in the same maintenance record makes future identification easier.
Editor's note: The terminal tiers are an easy detail to overlook when comparing similar ET 200B bases. Read the base and electronics-block labels together, and compare the existing PE and field-wiring arrangement carefully when choosing between 0CB30 and 0CB40.
Explore more: Siemens products | SIMATIC S7 | SIMATIC ET 200