6ES7 157-0AC82-0XA0
6ES7 157-0AC82-0XA0 – Siemens DP/PA Coupler, 1 A / 31 V
Series: Siemens SIMATIC DP / DP/PA Coupler
Category: Non-Ex PROFIBUS PA field connection
Description and system role
6ES7 157-0AC82-0XA0 is a Siemens DP/PA coupler with a 31 V / 1000 mA PA supply, connecting PROFIBUS DP and PROFIBUS PA with electrical isolation between the two sides. Siemens identifies it as a non-Ex, Outdoor version. For an introduction to the network structure, see the PROFIBUS information page.
When selecting a spare for an existing process plant, review the PLC project, PA device list and coupler label together. Similar-looking products in this family can have different PA current ratings and hazardous-area capabilities.
Power supply and PA segment capacity
The input is 24 V DC, with a permitted range of 20.4–28.8 V DC. The PA output is 31 V DC ±1 V at 1 A. Maximum current consumption at the 24 V input is 1.8 A.
The manual specifies up to 31 PA devices. Determine the actual device count from total current demand, cable length and voltage drop. 1 A is the current budget for the whole PA segment. Use the input consumption when sizing the panel power supply.
Siemens lists 0AC80 and 0AC81 at 400 mA, and 0AC82 at 1000 mA / 31 V. If the application requires an Ex field connection, review the documentation for the relevant version, such as the 0AD82 Ex coupler, against the plant's hazardous-area requirements.
Communication speed and configuration
In standalone operation, the rates are 45.45 kbit/s on DP and 31.25 kbit/s on PA. The coupler operates transparently and requires no separate HW Config configuration. Addressing and configuration apply to the PA field devices.
A DP/PA Link can operate at up to 12 Mbit/s on the upstream DP network. This rate belongs to the Link interface. The IM157 interface is relevant when researching older systems. Before replacement, record the full order numbers of the installed IM and bus modules and check their compatibility in the applicable manual.
Connections and panel installation
DP uses a 9-pin Sub-D connector; PA uses a four-position screw terminal. The integrated PA termination has an ON/OFF switch. ON, DP and PA LEDs provide local monitoring.
The protection rating is IP20; dimensions are 80 × 125 × 130 mm. Consider enclosure protection, moisture and mounting orientation when assessing the Outdoor designation. Set termination to suit the existing PA topology. Photographing the connections before removal can help during maintenance.
Replacement with 0AC83 FDC157-0
Siemens' 07/2011 manual identifies the 6ES7 157-0AC83-0XA0 FDC157-0 as the successor to 0AC82. With the 0AC83 address set to 0, diagnostics are disabled and transparent spare-part compatibility is provided. Its additional diagnostics require addressing and configuration. PA ring or coupler redundancy requires the BM FDC/FDC (redundant) bus module. Review the installed Link arrangement and required functions together when planning the change.
Editor's Note
For a used unit, check the legible 0AC82 model label, terminal condition and termination switch. If a test record is available, ask which PA load and communication conditions were used. A result that can be compared with your plant's device currents is more useful than a photograph showing power applied.
PDFs and operating manuals
Visit the Siemens ET 200 PDFs and user manuals section. The exact model's technical table appears in A5E00209064-15, 02/2006, section 13.4. SIMATIC Field Automation, 04/2005 explains the system structure; Released Modules V7.1 SP3 distinguishes the models; A5E00193841-17, section 2.10 covers replacement with 0AC83.
Related topics
For control and monitoring, explore PLC and HMI systems, operator panels and SCADA. For broader system research, see Siemens S7-300, about Siemens ET 200 and ET 200 PROFIBUS and PROFINET.
Other module groups: ET 200 analog input modules · Digital input modules · Digital output modules · Connection modules · Additional modules.
Navigation: Siemens ET 200 · Siemens SIMATIC S7 · Siemens S7 PLC · OtomasyonAVM home