6ES7 135-0HF01-0XB0

Siemens product menu:
Siemens Automation  ›  SIMATIC S7 PLC  ›  Siemens ET 200  ›  ET 200 Manuals and PDF Archive

6ES7 135-0HF01-0XB0 – Siemens SIMATIC ET 200B-4AO Analog Output Block

6ES7 135-0HF01-0XB0 is a four-channel analog output electronics block for the Siemens SIMATIC DP ET 200B system. It converts digital values received from a PLC or PROFIBUS DP master into voltage or current signals for drives, proportional valves, positioners, indicators and process controllers.

This product belongs to the older ET 200B block-I/O architecture within the Siemens ET 200 distributed I/O family. It is not mechanically equivalent to a slim ET 200S, ET 200M or ET 200SP electronic module. See the Siemens ET 200 system overview for the differences between these system families.

Function Within the ET 200B System

The ET 200B design combines the field-signal electronics and PROFIBUS DP communication in a block arrangement. The 6ES7135-0HF01-0XB0 must therefore not be treated as a conventional ET 200S electronic module installed behind a separate interface module.

The four analog outputs occupy a total of 8 output bytes, with one word assigned to each channel. The PROFIBUS module definition, output start address, analog-value format and physical channel settings must correspond.

Principal Technical Data

Product type: ET 200B-4AO analog electronics block
Article number: 6ES7 135-0HF01-0XB0
Number of analog outputs: 4
Voltage-output ranges: 0–10 V and ±10 V
Current-output ranges: 0–20 mA, 4–20 mA and ±20 mA in the manual parameter tables
Resolution: 11 bits including sign, two’s-complement format
Conversion time: 1 ms per channel
Output address space: 8 bytes
PROFIBUS DP transmission rate: Maximum 12 Mbit/s
Required terminal block: TB8 – 6ES7193-0CD40-0XA0

Rated supply voltage: 24 V DC
Permissible supply range: 18.5–30.2 V DC
Current consumption: Maximum 200 mA
Typical power loss: 2.4 W
Maximum current-output load: 300 Ω
Maximum inductive load: 1 mH
Maximum capacitive voltage-output load: 1 µF
Current-output open-circuit voltage: Maximum 18 V
Shielded signal-cable length: Maximum 100 m
Degree of protection: IP20

Voltage-output short-circuit protection: Electronic; maximum short-circuit current 25 mA
Voltage-output connection: Two-wire or four-wire
Current-output connection: Two-wire
RUN indication: Yes
Bus fault indication: Red BF LED
Diagnostic alarm: Parameterisable
Galvanic isolation between analog channels: No

Approximate dimensions: 160 × 130 × 60 mm
Approximate weight: 550 g
The stated dimensions and weight refer to the completed electronics-block and TB8 assembly.

Selecting Voltage or Current Output

The principal advantage of the 6ES7135-0HF01-0XB0 is the availability of voltage and current signal ranges across its four channels. Typical examples include ±10 V for bidirectional drive references, 0–10 V for one-direction commands and 4–20 mA for process equipment. See the analog input and output guide for a comparison of the signal types.

The signal range is not determined solely by the numeric value written by the PLC. TB8 channel coding and the PROFIBUS master parameters must match the selected range. Incorrect settings can produce a zero signal, incorrect scaling or unexpected operation of the connected device.

For related measurement and output hardware, see ET 200 analog input modules, ET 200 special output modules and ET 200 digital output modules.

SIMATIC S7 Analog-Value Scaling

The principal SIMATIC S7 two’s-complement scaling points are:

±10 V: −27648 represents approximately −10 V, 0 represents 0 V and +27648 represents +10 V
0–10 V: 0 represents 0 V and 27648 represents approximately 10 V
±20 mA: −27648 represents approximately −20 mA, 0 represents 0 mA and +27648 represents +20 mA
0–20 mA: 0 represents 0 mA and 27648 represents approximately 20 mA
4–20 mA: 0 represents 4 mA, 13824 approximately 12 mA and 27648 approximately 20 mA

Because the module has 11-bit resolution, every consecutive raw integer does not create a different physical output step. Engineering-unit conversion must consider the configured channel range, limits and overrange behaviour. These S7 examples must not be applied without verification when the station is controlled by a SIMATIC S5 or another PROFIBUS master.

TB8 Terminal Block and Wiring

The electronics block requires a TB8 – 6ES7193-0CD40-0XA0 ET 200 terminal block. The TB8 combines field terminals, the 24 V DC supply, PROFIBUS connection, station-address setting and the mechanical mounting point for the electronics block.

Voltage outputs can use two-wire or four-wire connections. With four-wire voltage connection, the S+ and S− sense conductors help compensate for voltage drop along the signal cable. Current outputs use a two-wire connection. TB8 coding elements must be set according to the selected range and wiring diagram in the Siemens manual.

The installation should also be reviewed together with the relevant ET 200 connection modules, ET 200 power supply modules and ET 200 power-distribution components.

Isolation and Grounding

The electronics block is electrically isolated from the PROFIBUS DP side, but the four analog output channels are not galvanically isolated from each other. Common analog reference, shield connection and equipotential bonding must be considered when signals are sent to equipment in different panels or at different grounding potentials.

Shielded analog cables should be routed separately from motor, contactor and drive-output cables. If grounding the cable shield at both ends produces equalisation current, the grounding arrangement must be adapted to the plant’s EMC and bonding design.

PROFIBUS DP Configuration

The electronics block supports PROFIBUS DP rates up to 12 Mbit/s. During commissioning, verify the station address, baud rate, master configuration, module identity, output start address and channel parameters. When an older type file, COM ET 200 or STEP 7 hardware catalogue entry is used, the selected record must match the complete article number and hardware version.

Network cabling and termination information is available under ET 200 PROFIBUS and PROFINET. Other communication products can be compared through ET 200 other network interfaces.

RUN and BF Indicators

The RUN LED indicates the operating state of the block, while the red BF LED indicates a PROFIBUS communication fault. A BF indication does not automatically prove that the electronics block has failed. Check the station address, master configuration, PROFIBUS cable, connector, shielding, termination and master status together.

The parameterisable diagnostic alarm permits more detailed fault evaluation by the master. LEDs cannot, however, confirm the accuracy of an analog channel. Actual voltage and current values must be measured using a suitable instrument and test load.

Safety-Related Distinction

The 6ES7135-0HF01-0XB0 is a standard analog output block, not a fail-safe analog output or F-module. Emergency stopping and safe torque removal must not depend solely on its analog command. Where required by the risk assessment, use suitable ET 200 safety modules, PROFIsafe components and functional safety solutions.

Used-Product Inspection

1. Confirm the complete 6ES7135-0HF01-0XB0 article number.
2. Check whether the TB8 – 6ES7193-0CD40-0XA0 terminal block is included.
3. Test all four channels separately in voltage and current modes.
4. Compare zero, midpoint and full-scale values with a calibrated instrument.
5. Test the RUN and BF LEDs, PROFIBUS communication and diagnostic alarm.
6. Inspect TB8 contacts for oxidation, heat damage and broken coding components.
7. Check the station-address selector, bus connector and shield connection.

Other installed-system components can be found under ET 200 additional modules. For a product-code comparison, provide both electronics-block and terminal-block numbers through the Siemens automation contact page.

Editor’s note: The critical point is that this product must not be treated as an ET 200S analog module. The 6ES7135-0HF01-0XB0 is an older ET 200B electronics block with PROFIBUS communication and must be evaluated together with its TB8 terminal block. An illuminated RUN LED is not a complete used product test. All four channels should be measured under a real load in the configured voltage and current ranges. The absence of galvanic isolation between the analog channels must also be considered.

Manuals and PDF Documents

Additional manufacturer documentation is available through the Siemens ET 200 manuals and PDF archive.

Siemens ET 200B Distributed I/O Station manual
English manufacturer manual. Section 8.6 covers the 6ES7135-0HF01-0XB0, channel settings, analog-value representation and TB8 wiring.

Siemens 6ES7135-0HF01-0XB0 technical data sheet
Product-specific Siemens data sheet covering electrical ratings, output ranges, PROFIBUS, environmental conditions and dimensions.

Reminder: This information is intended to assist identification and selection. Before installation, replacement or purchase, verify the electronics block, TB8 terminal block, PROFIBUS configuration, channel signal ranges and manufacturer manual together. For used products, also review the stated operating and test condition.