Description and system role

6ES7 134-4MB00-0AB0 is a 2AI I 2/4WIRE High Feature analog input module for ET 200S stations. It reads current signals from two-wire or four-wire measuring transmitters. Applications include monitoring pressure, level, flow and similar process values through a PLC. For the measurement fundamentals, see what is an analog signal?

When selecting a spare, check the full order number, transmitter wiring type, measurement range, terminal base and required update time together. Save the existing channel settings before replacement to make comparison easier.

Current ranges and resolution

There are two analog inputs. Resolution is 15 bits plus sign for ±20 mA and 15 bits for 4–20 mA. Input resistance is 50 Ω in both ranges.

For a 4–20 mA measurement loop, match the transmitter output and PLC scaling to the selected range. Record the sensor's physical measurement span as well: the same current can represent different pressure or level values with different transmitters.

Two-wire and four-wire connections

A four-wire transmitter's current output connects to M+ and M−. For a two-wire transmitter, connect its positive terminal to L+ and negative terminal to M+, with M− bridged to L−. Check the wiring against the transmitter type being used.

Siemens lists screw-terminal TM-E15S24-01 / TM-E15S26-A1 and spring-terminal TM-E15C24-01 / TM-E15C26-A1 bases as compatible options. Inspect the installed base's full order number, terminal numbering and supply distribution. Clarify whether the electronic module and terminal base are both included in the offer.

Supply and isolation

The module receives 24 V DC through the ET 200S power module. Siemens specifies a maximum L+ current consumption of 53 mA and an electronic-module width of 15 mm. Include field transmitters and the other station modules in the power-supply calculation.

The channels are not galvanically isolated from each other. The inputs are isolated from the backplane bus and L+ supply. Check the supply arrangement of transmitters coming from separate panels or different grounding points.

Measurement timing and diagnostics

With 50 Hz interference suppression enabled, the manual specifies a cycle time of 90 ms with one active channel and 210 ms with two active channels. Assess filtering and the number of active channels against the application's update requirements.

The red SF LED indicates a group fault. Group, underflow/overflow and wire-break diagnostics are parameter-controlled. Wire-break diagnostics are available only in the 4–20 mA range. During troubleshooting, check the channel setting, transmitter supply and loop current together.

Comparison with 4MB02 and voltage-input models

For 6ES7 134-4MB02-0AB0, Siemens specifies a 0.5 ms module cycle time with interference suppression disabled. Assess 4MB00 timing using its own technical table. When changing a part, check timing, filtering and project compatibility alongside the measurement range.

6ES7 134-4LB02-0AB0 belongs to the voltage-input group. Confirming the field device's output type from its label or data sheet is the first step when choosing between current and voltage modules.

Editor's Note

For a used current-input module, ask for measurement tests on both channels. If a test record is available, request results at several points, such as 4, 12 and 20 mA, together with the terminal base and two-wire/four-wire arrangement used. A test that can be compared with the intended installation gives more useful evidence of condition.

PDFs and operating manuals

Visit the Siemens ET 200 PDFs and user manuals section. The 4MB00 is covered in ET 200S 12/2004, section 12.12 and 10/2005, section 4.13. Document A5E01076111-01 is used for the 4MB02 comparison; check the order number in each document's title.

Related topics

For control and monitoring, explore PLC and HMI systems, operator panels and SCADA. For system research, see Siemens S7-300, about Siemens ET 200 and ET 200 PROFIBUS and PROFINET.

Other module groups: ET 200 analog input modules · Digital input modules · Digital output modules · Connection modules · Additional modules.

Navigation: Siemens ET 200 · Siemens SIMATIC S7 · Siemens S7 PLC · OtomasyonAVM home