6ES7 134-4JB00-0AB0

Siemens 6ES7134-4JB00-0AB0 ET200S 2AI TC ST Thermocouple Input Module

Siemens 6ES7134-4JB00-0AB0 is a two-channel 2AI TC Standard analog input module for SIMATIC ET200S stations. It converts thermocouple temperature measurements and low-level voltage signals into values that a PLC can process. The order number may also appear as 6ES7 134-4JB00-0AB0 on equipment labels and in project records.

Measurement types and sensor selection

The module supports thermocouple types B, E, J, K, L, N, R, S and T, with linearization for the selected sensor characteristic. Its voltage measuring range is ±80 mV, resolution is 15 bits plus sign, and input resistance is at least 1 MΩ. Each channel must be configured for the sensor actually connected to it.

When planning an application, consider how a thermocouple works, the cable type and the reference junction together. For analog signal selection, this module measures voltage at millivolt level. A transmitter with a 0–10 V or 4–20 mA output requires a module with the corresponding input type.

Cold junction compensation

The 6ES7134-4JB00-0AB0 has no internal cold junction compensation. Compensation can use an external compensating box for each channel or a reference temperature obtained from a suitable RTD module in the same ET200S station. With the second method, the Pt100 sensor measuring the reference junction connects to the separate RTD module. The reference channel settings in the TC module and interface module must correspond. If RTD compensation is enabled for both TC channels, they use the same reference RTD channel.

For RTD-based compensation, configure the reference input for Pt100 Climate and follow the manufacturer's wiring arrangement. Thermal contact between the Pt100 and reference junction, suitable compensation cable and correct polarity all affect the result. The sensor and compensation arrangement must also be included when evaluating the total measurement error.

Power supply and terminal connections

The electronic module is 15 mm wide. It receives its nominal 24 V DC supply through the ET200S power module and draws a maximum of 30 mA from L+. When assessing the panel power supply, include the consumption of the other station modules.

For channel 0, terminal 1 is M0+ and terminal 2 is M0−. For channel 1, terminal 5 is M1+ and terminal 6 is M1−. Terminals 3 and 7 provide the MANA reference. Suitable terminal bases include the screw-terminal TM-E15S24-01 and spring-terminal TM-E15C24-01. The inputs are galvanically isolated from the backplane bus and L+ supply; there is no galvanic isolation between channels.

Conversion time and diagnostics

The basic conversion time per channel is 65 ms with 50 Hz interference suppression and 55 ms with 60 Hz interference suppression. Enabling the wire-break check adds 20 ms to the conversion time of the applicable channel. The module cycle depends on the conversion times of the active channels, while the smoothing setting also affects the response to a changing measurement.

The red SF LED indicates a group fault. Wire-break diagnostics are available for thermocouples and must remain disabled in the ±80 mV voltage range. Unused channels must be deactivated in the parameters and fitted with the terminal jumpers specified in the manual.

Maintenance and order number checks

Siemens identifies the 6ES7134-4JB01-0AB0 version as compatible with the 4JB00 in its manual. Before a replacement, check the installed module's complete order number, terminal base, interface module and hardware configuration together. Additional functions documented for the 4JB01 must not be assumed to be features of the 4JB00.

Editor's note

Check the thermocouple type and existing compensation method alongside the order number when selecting a module. This model measures TC/mV signals; direct Pt100 measurement requires a suitable RTD input module. Use the relevant manufacturer document in the Siemens ET200 manuals section for wiring, reference channel and parameter details. Availability, product condition and the scope of supply should be confirmed with the quotation.