Toshiba P7 Fault codes 4
Indication: NOFF
Contents: Main circuit undervoltage
- Undervoltage between R, S, and T.
- If a momentary power supply failure occurs, no trip is developed.
- Measure supply voltage of main circuit. If voltage is normal, it resets later.
- If momentary power failure occurs, retry operation activates automatically.
Indication: rdy
Contents: Retry indication
Expected Causes:
- Panel indication of retry operation for momentary power failure is occurred.
- Measure supply voltage of main circuit. If voltage is normal, it resets later.
- If momentary power failure occurs, retry operation activates automatically.
Indication: P-E
Contents: Frequency point setting error
Expected Causes:
- Points 1 and 2 of frequency setting signal are set too close to each other.
Countermeasures:
- Set points 1 and 2 of frequency setting signal apart from each other.
Indication: C1-C
Contents: Clear enabling indication
Expected Causes:
- STOP key is pressed after trip indication.
Countermeasures:
- Press STOP key once more for resetting.
Indication: EOFF
Contents: Emergency stop enabling indication
Expected Causes:
- Clear operation is performed by panel during automatic or remote operation.
Countermeasures:
- If STOP key is pressed, emergency stop is released. To cancel emergency stop, press any other key.
Indication: H1 - H0
Contents: Parameter in memory being edited alternately displayed twice
Expected Causes:
- Under DC braking
- Under motor shaft fixing control
- Input error
Countermeasures:
- Check setup value for input error.
Indication: db
Contents: DC braking indication
Expected Causes:
- Under DC braking
- Under motor shaft fixing control
Countermeasures:
- If message disappears dozens of seconds later, it is normal. (Note that this is not a fault indication.)
Indication: E2
Contents: Panel Indication overflow
Expected Causes:
- Number to be shown on panel exceeds six figures which can be shown by inverter. Last number of overflowing digits is indicated alternately with a decimal point.
Countermeasures:
- If message disappears dozens of seconds later, it is normal. (Note that this is not a fault indication.)
Indication: E-C
Contents: Communication error
Expected Causes:
- When control unit is linked with inverter via communication, communication error is indicated if reading data and writing data are interrupted.
Countermeasures:
- For continuous transmission errors, refer to various communication errors.
Indication: L
Contents: Parameter is initialized, setting value is reset to standard default values
Expected Causes:
- Parameter initialization is executed.
Countermeasures:
- If message disappears several seconds later, it is normal.
Indication: In
Contents: In auto-tuning
Expected Causes:
- Auto-tuning is executed.
Countermeasures:
- If message disappears several seconds later, it is normal.
Pre-alarm display
Indication Contents Expected Causes and Countermeasures
O Overcurrent alarm Same as OC
P Overvoltage alarm Same as OP
F Overload alarm Same as OL
r Overheating alarm Same as OH
Note: When two or more alarms occur at the same time, such the message as shown in the following blinks. Blinking indications appear in the order of OC, OP, OL, OH from the leftmost place to right.
+ Toshiba VFD P7 User Manual >
+ Toshiba VFD P7 >
+ Toshiba P7 Fault codes 2 >
+ Toshiba P7 Fault codes 3 >
+ Toshiba P7 Fault codes 4 >+ VFD Main page -
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 28.06.2013Your shopping cart is empty!