Toshiba P7 Fault codes 3
UP1 (Undervoltage - main circuit):
+ Input voltage (main circuit) becomes insufficient in operation.
+ Momentary power failure occurs because undervoltage continues longer than undervoltage detection time (#528).
Countermeasures:
+ Check input voltage.
+ If undervoltage is detected, set regenerative power ride-through control (#301 and #302) and undervoltage detection time (#528) as countermeasures against future momentary power failure.
UP2 (Undervoltage - control circuit):
+ Input voltage (control circuit) becomes insufficient in operation.
+ Momentary power failure occurs because undervoltage continues longer than undervoltage detection time (#528).
Countermeasures:
+ Check input voltage.
+ If undervoltage is detected, set regenerative power ride-through control (#301 and #302) and undervoltage detection time (#528) as countermeasures against future momentary power failure.
OT (Over-torque):
+ Load torque reaches over-torque detection level in operation.
Countermeasures:
+ Check the system if there is something abnormal in it or not.
EF1/Ef2 (Ground-fault):
+ Output cable or motor falls into ground-fault.
Countermeasures:
+ Check units and connections if there is ground-fault or not.
Et n (Auto-tuning error):
+ Check settings of motor parameters (#400 to #414).
+ Motor whose capacity is smaller by two or more ranks than that of inverter is used.
+ Extremely think cable is used as inverter output cable.
+ Motor is running.
+ Motor other than three-phase inductive type is used.
+ If Et n error occurs as power is turned on, set motor type parameter as others (#413 - #414).
Countermeasures:
+ Check motor settings (#400 - #414).
+ Check motor capacity and compatibility with inverter.
+ Check motor cable.
+ Ensure motor is stopped before auto-tuning.
E tYP (Inverter type error):
+ Is control board (or drive board of main circuit) replaced?
Countermeasures:
+ When board has been replaced, input code for the new board.
E-10 (Sink/source switching error):
+ Sink/source switch of input/output terminal is set wrong (reversely switched on/off).
Countermeasures:
+ Check connections and set proper logic.
E-11 (Sequence error):
+ The signal from a system is not inputted into input terminals.
+ The input terminal function (#30 or #31) is not set up.
+ For not using the system-supporting sequence (#530) function, it is set up except 0.0 at (#530).
Countermeasures:
+ Please check if the sequence is normal or not.
+ Please set (#30 or #31) as the input terminal to use.
+ Please set up 0.0 when you do not use system-supporting sequence.
E-12 (Encoder error):
+ Disconnection of encoder circuit.
Countermeasures:
+ Check connection of encoder.
+ Connect encoder correctly.
E-13 (Speed error - Over speed):
+ Something abnormal in encoder.
Countermeasures:
+ Check connection of encoder.
+ Connect encoder correctly.
E-14 (Too much potential deviation):
+ Potential deviation exceeded the (#531) set value during position control.
Countermeasures:
+ Check connection of encoder.
+ Increase the setting value of (#531).
+ Adjust the parameters on position control.
E-17 (Key error):
+ RUN or STOP key is depressed for 5 seconds or more.
+ Key is faulty.
Countermeasures:
+ Check operation panel.
E-18 (VI/II input error):
+ Breaking down of a wire for VI/II input signal.
Countermeasures:
+ Check VI/II input signal.
nrON (Low-current operation):
+ Output current declined to the low-current detection level during operation.
Countermeasures:
+ Check to see if low-current detection level is set properly to the system or not (#5 and #1).
OFF (ST-CC opened):
+ ST terminal is in open-circuit.
Countermeasures:
+ Close ST-CC circuit.
P.OFF (Control circuit undervoltage):
+ Undervoltage between RO and SO of control power supply (when option is used for 22 kW or lower type).
Countermeasures:
+ Measure supply voltage of control power. If voltage is normal, it needs repair service.
nOFF (Main circuit undervoltage):
+ Undervoltage between R, S and T of main circuit power supply.
+ Trouble of pre-charge circuit or DC circuit fuse.
Countermeasures:
+ Measure supply voltage of main circuit power. If voltage is normal, it needs repair service.
rt rY (Retry indication):
+ In retry operation.
+ Momentary power failure is occurred.
Countermeasures:
+ If inverter automatically restarts dozens of seconds later, it is normal. Be careful of inverter in retry status, because there is a fear that it may suddenly restart.
P-ER (Frequency point setting error alarm):
+ Points 1 and 2 of frequency setting signal are set too close to each other.
Countermeasures:
+ Set points 1 and 2 of frequency setting signal apart from each other.
CLr (Clear enabling indication):
+ If STOP key is pressed after trip indication, this indication appears.
Countermeasures:
+ Press STOP key once more for resetting.
EOFF (Emergency stop enabling indication):
+ Stop operation is performed by panel during automatic or remote operation.
Countermeasures:
+ If STOP key is pressed, emergency stop is executed. To cancel emergency stop, press any other key.
HI/LO (Alarm for setup value error):
+ Setup value error is detected in reading out or writing data.
Countermeasures:
+ Check setup value for input error.
d.b (DC braking indication):
+ Under DC braking.
Countermeasures:
+ If message disappears dozens of seconds later, it is normal.
E1/E2 (Panel indication overflow):
+ Number to be shown on panel such as frequency and so on overflows figures of display. (Number of overflowing digits is indicated.)
Countermeasures:
+ For indication of frequency, set multiplying rate (#2) lower. (Parameter setting that results in overflow is of course valid.)
t (Communication error):
+ Various transmission errors occur when computer is linked up with inverter system.
+ Various transmission errors occur in inverter to inverter communication (slave side).
+ Time-out or trip in master side.
Countermeasures:
+ For countermeasures against various transmission errors, refer to the "Manual for communication".
+ Check the master inverter.
Init (Parameter is under initialization):
+ Parameters are initialized to be standard default values.
Countermeasures:
+ If message disappears dozens of seconds later, it is normal.
Atn (In auto-tuning):
+ Under auto-tuning.
Countermeasures:
+ If message disappears several seconds later, it is normal.
Messages and Their Meanings: No Trip Developed
Indication: OFF
Contents: ST-CCC opened
- Terminal is open-circuit.
- ST terminal is in open-circuit and one of control power supply voltages is too low for 22 kW model or lower.
Countermeasures:
- Close ST-CCC circuit.
- Measure supply voltage of main circuit.
Indication: PGOFF
Contents: Control circuit undervoltage
- Measure supply voltage of control power supply. If voltage is normal, it resets later.
+ Toshiba VFD P7 User Manual >
+ Toshiba VFD P7 >
+ Toshiba P7 Fault codes 2 >
+ Toshiba P7 Fault codes 3 >
+ Toshiba P7 Fault codes 4 >+ VFD Main page -
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 28.06.2013Your shopping cart is empty!