Yaskawa V1000 Fault codes 2
Yaskawa V1000 error codes and their descriptions:
bUS - Option Communication Error
- Connection was lost after initial communication was established.
- Detected only when the run command frequency reference is assigned to an option card.
- Possible Causes and Solutions:
+ No signal from PLC.
+ Check cable connections.
+ Correct cable connections.
+ Check for loose cable connections and shorts, and repair as necessary.
+ Communication cable is faulty or shorted.
+ Communication data error due to noise.
+ Check various options to minimize the effects of noise.
+ Prevent noise in control circuit, main circuit, and grounding wiring.
+ Use cables recommended by Yaskawa or another type of shielded cable. Ground the shield on the controller side or on the drive input power side.
+ Separate all wiring for communication devices from drive input power lines. Install an EMC noise filter on the input side of the drive input power.
+ Option card is damaged.
+ Option card is not properly connected to the drive.
CE - MEMOBUS/Modbus Communication Error
- Control data was not received for the duration of the CE detection time set to H5-09.
- Possible Causes and Solutions:
+ Error or short circuit in communication wiring.
+ Communication data error due to noise.
CF - Control Error
- A torque limit was continuously reached for three seconds or longer during the stop ramp in Open Loop Vector Control.
- Possible Causes and Solutions:
+ Motor parameters are not properly set.
+ Torque limit is too low.
+ Load inertia is too large.
CoF - Current Offset Error
- There is a problem with the current sensing circuit, or the drive is trying to run a PM motor that is in motion.
- Possible Causes and Solutions:
+ While the drive is automatically setting the current offset, the calculated value exceeded the allowable setting range. This problem can occur when trying to restart a PM motor that is in motion.
CPF02 - A/D Conversion Error
- An A/D conversion error has occurred.
- Possible Causes and Solutions:
+ Control circuit is damaged.
+ Control circuit terminals shorted (+V, AC).
CPF03 - PWM Data Error
- There is a problem with the PWM data.
- Possible Cause and Solution:
+ Drive hardware is damaged. Replace the drive.
CPF06 - EEPROM Data Error
- There is an error in the data stored in the EEPROM.
- Possible Causes and Solutions:
+ Control circuit is damaged. Cycle power to the drive. If the problem persists, replace the drive.
+ Power supply was turned off while parameters were being written (e.g., using a communication option card). Restart the drive (A1-03).
CPF07 - Terminal Card Communication Error
- A communication error has occurred in the terminal card.
- Possible Cause and Solution:
+ There is a connection error between the terminal card and the control card. Turn off power and reconnect the control circuit terminals.
CPF08 - EEPROM Serial Communication Error
- Communications with the EEPROM are not functioning properly.
- Possible Cause and Solution:
+ Terminal card or control card is not properly connected. Turn off power and check control terminal connections.
CPF11 - RAM Error
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF12 - FLASH Memory Error
- There is a problem with the ROM (FLASH memory).
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF13 - Watchdog Circuit Exception
- Self-diagnosis problem.
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF14 - Control Circuit Error
- CPU error (CPU is malfunctioning due to noise, etc.).
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF16 - Clock Error
- Standard clock error.
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF17 - Timing Error
- A timing error occurred during an internal process.
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF18 - Control Circuit Error
- CPU error. Non-Maskable Interrupt (an unusual interrupt triggered by noise, etc.).
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF19 - Control Circuit Error
- CPU error (manual reset due to noise, etc.).
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF20 or CPF21
- One of the following errors occurred: RAM error, FLASH memory error, watchdog circuit exception, clock error
+ RAM error.
+ FLASH memory error (ROM error).
+ Watchdog circuit exception (self-diagnosis error).
+ Clock error.
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF22 - A/D Conversion Error
- An A/D conversion error.
- Possible Cause and Solution:
+ Control circuit is damaged.
+ Cycle power to the drive. Refer to the Troubleshooting and Reset section on page 266.
+ If the problem persists, replace the drive.
CPF23 - PWM Feedback Error
- PWM feedback error.
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
CPF24 - Drive Capacity Signal Error
- A non-existent capacity was entered. (Checked when the drive is energized.)
- Possible Cause and Solution:
+ Hardware is damaged. Replace the drive.
dEv - Speed Deviation (for Simple V/f with PG)
- According to the pulse input (RP), the speed deviation continues for a longer period than set in F1-11 with respect to the setting in F1-10.
- Possible Causes and Solutions:
+ Load is too heavy. Reduce the load.
+ Acceleration and deceleration times are set too short. Increase acceleration and deceleration times (C1-01 - C1-08).
+ Load is locked. Check the machine.
+ Parameters are not properly set. Check the settings of parameters F1-10 and F1-11.
+ Motor brake is engaged. Ensure that the motor brake is properly released.
dWFL - DriveWorksEZ Error
- dWAL - DriveWorksEZ Program Error Output
- Possible Cause and Solution:
+ An error output was made by DriveWorksEZ. Correct the cause of the error.
EF0 - Option Card External Error
- An external error condition exists.
- Possible Causes and Solutions:
+ An external error was received from the PLC, except for F6-03 = 3 "alarm only" (drive continued to operate after the external error).
+ Eliminate the cause of the external error.
+ Remove the external error input from the PLC.
+ There is a problem in the PLC program. Check the PLC program and correct any issues.
-----
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 19.03.2014Your shopping cart is empty!