Yaskawa V1000 Fault codes 4
oH - Heatsink Overheating
The temperature of the heatsink exceeded the value set in L8-02 (90-100°C).
Possible Causes and Solutions:
+ Ambient temperature is too high. Check the temperature around the drive and ensure it is within the drive's specifications.
+ Cooling fan stopped. Replace the cooling fan.
oH1 - Overheating 1 (Heatsink Overheating)
The temperature of the heatsink exceeded the overheating detection level.
Possible Causes and Solutions:
+ Ambient temperature is too high. Check the temperature around the drive and ensure it is within the drive's specifications.
+ The load is too heavy. Measure the output current and reduce the load.
+ The internal cooling fan has reached its performance life or is malfunctioning. Check the maintenance time of the cooling fan and replace if necessary.
oH3 - Motor Overheating Alarm (PTC Input)
The motor overheating signal exceeded the overheating detection level at analog input terminal A1 or A2.
Possible Causes and Solutions:
+ The motor overheated. Check the load size, acceleration/deceleration times, and cycle times.
+ Check if the motor cooling system is operating normally and repair or replace if necessary.
oH4 - Motor Overheating Fault (PTC Input)
The motor overheating signal exceeded the overheating detection level at analog input terminal A1 or A2.
Possible Causes and Solutions:
+ The motor overheated. Check the load size, acceleration/deceleration times, and cycle times.
+ Check if the motor cooling system is operating normally and repair or replace if necessary.
oL1 - Motor Overload
The electrothermal sensor triggered overload protection.
Possible Causes and Solutions:
+ The load is too heavy. Reduce the load.
+ Acceleration and deceleration times are too short. Increase acceleration and deceleration times.
oL2 - Drive Overload
The drive's thermal sensor triggered overload protection.
Possible Causes and Solutions:
+ The load is too heavy. Reduce the load.
+ Acceleration and deceleration times are too short. Increase acceleration and deceleration times.
+ Drive capacity is too small. Replace with a larger model.
oL3 - Over Torque Detection 1
The current exceeded the value set for torque detection (L6-02) for longer than the allowed time (L6-03).
Possible Causes and Solutions:
+ Parameter settings are not suitable for the load type. Check the settings of L6-02 and L6-03 parameters.
+ There is a fault on the machine side (e.g., the machine is locked). Check the load condition and eliminate the cause of the fault.
oL4 - Over Torque Detection 2
The current exceeded the value set for Over Torque Detection 2 (L6-05) for longer than the allowed time (L6-06).
Possible Causes and Solutions:
+ Parameter settings are not suitable for the load type. Check the settings of L6-05 and L6-06 parameters.
oL5 - Mechanical Weakness Detection 1
Over torque occurred in accordance with the conditions specified in L6-08.
Possible Cause and Solution:
+ Over torque occurred and triggered the mechanical weakness level set in L6-08. Check the cause of mechanical weakness.
oL7 - High Slip Braking oL
The output frequency remained constant for longer than the time set in n3-04 during High Slip Braking.
Possible Causes and Solutions:
+ Load inertia is excessive. Reduce deceleration times using parameters C1-02, -04, -06, and -08 in applications where High Slip Braking is not used.
+ The motor is driven by the load. Something on the load side is restricting deceleration. The over torque time during High Slip Braking is too short. Increase the parameter n3-04 (High Slip Braking Over Torque Time).
oPr - External Digital Operator Connection Error
The external operator disconnected from the drive.
Possible Causes and Solutions:
+ The external operator is not properly connected to the drive. Check the connection between the operator and the drive and replace the cable if damaged.
oS - Over Speed (with Simple V/f and PG)
The pulse input (RP) indicates that the motor speed feedback exceeded the setting of F1-08.
Possible Causes and Solutions:
+ Overshoot or undershoot is occurring. Adjust the gain using pulse train input parameters (H6-02 - H6-05).
ov - Over Voltage
The voltage in the DC bus exceeded the overvoltage detection level.
Possible Causes and Solutions:
+ Deceleration time is too short, and regenerative energy is flowing back to the drive during motor braking. Increase deceleration time (C1-02, -04, -06, -08).
PF - Input Phase Loss
A phase is open in the drive's input power or there is a significant voltage imbalance between phases. Detected when L8-05 = 1 (enabled).
Possible Causes and Solutions:
+ Phase loss in the drive's input power. Check wiring errors in the main circuit of the drive's input power.
-----
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 19.03.2014