What Is the IP00 Protection Rating?


IP00 is one of the most basic enclosure protection ratings used within the IEC IP classification system. It is not a separate standard by itself; it is a protection code defined within IEC 60529. The first digit describes protection against access to hazardous parts and solid foreign objects, while the second digit describes protection against water.

In simple terms… IP00 means that the enclosure provides no defined IP protection against access to hazardous parts or solid foreign objects and no defined IP protection against water. This does not automatically mean that the equipment is poor quality or unsafe when correctly installed. Many IP00 industrial products are designed to operate inside a separate control cabinet, machine enclosure or other protective housing.

What does the first 0 in IP00 mean?

The first digit, 0, means that the IP classification provides no protection against access to hazardous parts and no protection against solid foreign objects.

You therefore cannot assume from an IP00 marking that the enclosure prevents fingers, tools, wires or other objects from reaching hazardous electrical or mechanical parts. A particular product may still use internal barriers or other safety measures, but the IP00 code itself makes no such enclosure-protection claim.

For comparison, IP20 provides protection associated with finger access and solid foreign objects 12.5 mm and larger. IP00 provides no equivalent IP access or solid-object protection.

What does the second 0 in IP00 mean?

The second digit, 0, means that no protection against water is provided by the IP classification.

An IP00 product therefore has no IP claim for dripping water, rain, splashing, water jets, wash-down or immersion. If water exposure is possible, an enclosure with an appropriate second IP digit must be selected for the real application.

IP00 = no defined solid-object/access protection + no defined water protection.

Is IP00 the same as “protection not specified”?

No. The distinction between 0 and X in an IP code is important. A zero states that no protection is provided for that characteristic. An X means that the protection degree for that characteristic is not specified in that particular code.

For example, IP0X states that the solid-object/access protection level is 0, while the water characteristic is not specified. IPX0 states that the water-protection level is 0 while the solid-object characteristic is not specified. IP00 explicitly uses 0 for both characteristics.

Does IP00 mean open-type equipment?

IP00 equipment is often associated in practice with open or chassis-type industrial products that require an additional protective enclosure. However, “IP00” and terms such as “open type” should not automatically be treated as exact equivalents because they may originate from different standards or manufacturer classification systems.

Some industrial AC drives and VFDs, particularly at higher power levels, can be supplied in IP00 configurations intended for integration into a properly designed electrical cabinet.

An IP00 drive is therefore not necessarily incomplete or low quality. Its design may simply assume that the final machine builder or panel manufacturer will provide the required environmental and access protection.

What is the difference between IP00 and IP20?

The main difference between IP00 and IP20 is protection against access to hazardous parts and solid foreign objects. Both ratings end in 0, so neither provides a water-protection claim.

IP00 provides no IP protection against access or solid foreign objects. IP20 provides protection associated with finger access and solid objects in the 12.5 mm class.

IP00 = no access/solid-object protection + no water protection.
IP20 = finger/12.5 mm-class protection + no water protection.

This distinction is important during installation and maintenance because accessible IP00 equipment cannot be treated in the same way as equipment that provides finger-access protection.

What is the difference between IP00 and IP21?

IP21 differs from IP00 in both characteristics.

Its first digit is 2, providing protection associated with finger access and solid foreign objects 12.5 mm and larger. Its second digit is 1, providing protection against vertically falling water drops.

IP00 provides neither of those defined enclosure protections.

What is the difference between IP00, IP30 and IP40?

IP30 provides protection against solid foreign objects in approximately the 2.5 mm class and against access with a tool. IP40 extends that protection to approximately the 1 mm class and wire-type access.

IP00 provides no such solid-object or access protection. What IP00, IP30 and IP40 have in common is the second digit 0: none of them provides a standardized water-protection claim.

What is the difference between IP00 and IP50?

IP50 begins with first digit 5 and is therefore dust-protected. Limited dust ingress may be permitted, but not in a quantity or location that interferes with satisfactory operation or safety.

IP00 provides no defined protection against dust or other solid foreign objects. Both ratings end in 0, so neither has a water-protection claim.

IP00 = no solid-object protection + no water protection.
IP50 = dust-protected + no water protection.

Is IP00 waterproof?

No. The second digit is 0, so IP00 provides no standardized protection against water.

Terms such as waterproof, moisture-resistant, rain-resistant or splash-resistant cannot be derived from an IP00 marking. If a manufacturer states some other environmental characteristic separately, that claim must be evaluated on its own; it is not provided by IP00.

Is IP00 dust-protected?

No. The first digit is 0, so the IP code provides no protection against solid foreign objects or dust.

For this reason, IP00 equipment generally should not be directly exposed to heavy stone dust, cement dust, woodworking dust, metal particles or similar industrial contamination unless a separate protective enclosure is provided in accordance with the manufacturer's requirements.

Can IP00 equipment be used outdoors?

An IP00 marking does not establish suitability for exposed outdoor installation. It provides no IP protection against solid foreign objects and no protection against water.

Outdoor installations can also involve ultraviolet radiation, temperature changes, condensation, freezing, corrosion, salt atmosphere and chemicals. IP00 says nothing about resistance to these conditions.

Where IP00 equipment has to be used as part of an outdoor system, it will normally require a separate enclosure designed for the actual environmental conditions.

Why is IP00 equipment used in industrial automation?

At first glance, manufacturing equipment without its own ingress-protection enclosure may seem unusual. In industrial automation, however, many products are intended from the beginning to be integrated into an electrical cabinet or machine enclosure.

This can provide advantages in cooling, service access, installation flexibility, physical size and cost, particularly for high-power electronics.

The final environmental and personnel protection is then provided by the electrical cabinet and its panel components.

What does IP00 mean on a variable frequency drive?

Some industrial VFDs and motor drives, especially higher-power chassis, are available in IP00 versions. In these products, the final protection against access to power electronics, busbars or other hazardous parts is provided by the installation and cabinet specified by the manufacturer.

Installing an IP00 drive openly on the factory floor is therefore very different from installing the same drive inside a properly designed and restricted-access electrical cabinet.

The manufacturer's installation, clearance, cooling and electrical-safety requirements must be followed.

Should IP00 equipment be installed inside a cabinet?

For many industrial IP00 products, yes. The exact enclosure requirements, however, depend on the product manufacturer and the hazards present in the application.

Cabinet design must consider more than ingress protection. Access to hazardous voltage, ventilation, heat dissipation, short-circuit conditions, cable routing, maintenance access and fire considerations may also be important.

For example, installing a high-power IP00 VFD inside a very small, tightly sealed high-IP enclosure without a thermal calculation can create a serious overheating problem.

IP00 and control-panel cooling

IP00 equipment, particularly power electronic equipment, can generate substantial heat. The enclosure must therefore provide both the required safety/environmental protection and adequate heat removal.

When a VFD or power module is installed inside a panel, its power losses, ambient temperature, permitted internal cabinet temperature, airflow and required mounting clearances must be considered.

If fans, filters or air-conditioning systems are added, their effect on the completed cabinet's IP rating must also be taken into account.

Is it safe to touch IP00 equipment?

An IP00 marking provides no protection against access to hazardous parts. The first digit is 0, so no IEC 60529 enclosure-access protection is claimed.

This is particularly important with energized power electronics. IP00 drives, rectifiers and similar equipment should not be approached or serviced without the required electrical-safety procedures.

Removing supply power does not necessarily make power-electronic equipment immediately safe. DC-link capacitors in VFDs and other converters can retain hazardous voltage for a period after isolation.

The manufacturer's specified discharge time, voltage checks and maintenance procedures must be followed before work begins.

Does IP00 mean the product is electrically unsafe?

Not necessarily. IP00 means that the enclosure itself provides no defined IP protection against access to hazardous parts. It does not describe the entire electrical-safety design of the product or completed system.

Insulation, protective earthing, internal barriers, cabinet doors, interlocks, installation methods and other safety measures may be used to achieve the required protection in the final application.

The correct interpretation is not “IP00 means electrically unsafe,” but “IP00 provides no enclosure access protection under the IP classification.”

IP00 and PLC systems

Conventional modular PLCs and modules more commonly use enclosure designs that provide basic finger-access protection, but open electronic boards, special control modules or machine-integrated electronics can use different enclosure concepts.

In such systems, the machine or electrical cabinet becomes the primary barrier separating personnel from hazardous or sensitive internal components.

IP00 and industrial power supplies

Some open-frame industrial power supplies are designed for integration into a final product, machine or electrical cabinet rather than for direct exposed installation.

When selecting such equipment, voltage and power ratings are only part of the design. Access to hazardous parts, clearances, cooling and the protection provided by the final enclosure must also be considered.

Does IP00 protect against condensation?

No. IP00 provides no water-protection rating and does not make any claim about condensation resistance.

Condensation can form inside a cabinet as temperature and relative humidity change. When IP00 electronics are installed inside an enclosure, the manufacturer's permitted humidity conditions and any requirement for non-condensing operation must be checked separately.

Does IP00 mean lower product quality?

No. An IP rating is not a general quality score. The same manufacturer may offer a high-power professional drive in IP00 form, a smaller cabinet drive in IP20 form and a field-mounted version in IP54 or higher.

The difference is primarily about where and how the product is intended to be installed. An IP00 product can be completely appropriate inside a properly engineered electrical cabinet and completely inappropriate if left exposed on the factory floor.

Is a higher IP rating always better?

No. The correct IP rating depends on the installation method and actual environment.

One advantage of IP00 equipment can be greater flexibility for panel cooling, layout and maintenance. The trade-off is that access protection and environmental protection must be provided by the final system design.

The right engineering question is not “What is the highest IP rating?” but “Where will this equipment be installed, and what protection must the final enclosure provide?”

What does IP00 not guarantee?

IP00 provides no IP protection against solid foreign objects, access to hazardous parts or water. It also says nothing about operating temperature, humidity, condensation, ultraviolet resistance, corrosion resistance, chemical resistance, mechanical impact or electromagnetic compatibility.

An IP00 marking also does not by itself establish whether equipment satisfies every electrical-safety requirement, is suitable for explosive atmospheres or carries a particular certification. These subjects are addressed separately through the relevant industrial standards and product requirements.

What should be checked before using IP00 equipment?

First determine whether the equipment will be accessible to personnel or installed inside a locked or otherwise protective cabinet. The final system must prevent unsafe access to hazardous parts.

Second, assess the environment for dust, metal particles, moisture, liquids and condensation. Any required environmental protection must be provided by the surrounding enclosure.

Finally, follow the manufacturer's requirements for mounting clearances, cooling, ambient temperature, discharge times and electrical safety. IP00 equipment places greater importance on correct final cabinet and system engineering.

IP00 in one sentence

IP00 means no defined IP protection against access to hazardous parts or solid foreign objects, and no defined protection against water. It does not mean that the product is poor quality; many industrial IP00 products are intentionally designed for installation inside a suitable machine enclosure or electrical cabinet, particularly in high-power drive and power-electronics applications.

Related IP protection guides

IP Protection Ratings and IEC 60529 Guide | IP20 | IP21 | IP30 | IP40 | IP50

Related standards: Industrial Standards | IEC Standards

Related automation equipment: AC Drives and VFDs | Panel Components | PLCs and Modules | Power Supplies