Hello everyone,
A coast stop (freewheel stop) tells the drive to stop supplying the output that produces motor torque. The motor and the attached machine do not physically halt at that instant: the shaft keeps moving as its stored inertia and the load's opposing forces allow. Separating drive output from actual shaft motion is the key to understanding this setting.

What actually happens when you press Stop?
First check the drive's assigned stop mode. Removing a Run request does not always mean coast: drive model, input mapping, and control profile determine whether Stop calls up a deceleration ramp, a freewheel stop, or another function. Verify both the parameter setting and the machine's actual response.
With coast selected, the inverter ceases to generate the output used for controlled deceleration. The drive's displayed output frequency may become zero while the rotor is still spinning. Think of a fan initially driven at 50 Hz: its output command disappears at Stop, while air drag and bearing friction gradually slow the blades. Output frequency alone is not a tachometer reading.
The DEC parameter does not determine coast-down time. Inertia, initial speed, friction, fan load, and any external force driving the mechanism all matter. In an overhauling application, such as a suspended weight, the load can keep moving or even accelerate after drive torque is removed. A coast command guarantees no stopping distance.
Coast stop versus controlled ramp stop
On an acceleration/deceleration ramp, the drive continues energizing the motor as its output-frequency command falls through the programmed DEC interval. When the motor creates braking torque, a rotating load can return energy to the DC link. Coasting removes that active braking path; plotting a growing DC bus from routine regenerative braking after the output is already disabled would teach the wrong mechanism. Special systems with other backfeed paths need their own analysis.
| What changes? | Coast stop | Ramp stop |
|---|---|---|
| Drive output | Torque producing output is removed at Stop. | Motor remains under drive control during DEC. |
| Shaft motion | Decays according to load and drag; time varies. | Follows the target ramp within available torque and protection limits. |
| Braking energy | No active braking through the drive in the usual case. | Regenerative energy can raise the DC link. |
| Quick stop | Usually unsuitable. | Possible with suitable hardware and validation; DEC alone is no guarantee. |
Remember: “Output frequency is zero” is not the same observation as “the rotor is stationary.” That is why the first plot contains two separate lines.
Try both stop modes on the same load
1. The solid brown line is the drive output command; the dashed blue line is approximate shaft motion. 2. Both columns use the same time scale. 3. Try a short DEC, high inertia, and no resistor; if the right plot reaches the OV limit, the model disables the ramp and lets the load coast.
Model limits: These numbers are not measured motor current, actual DC-link voltage, or a resistor-sizing calculation. The bus plot is an illustrative rise toward an example OV limit, not an absolute voltage for a specific drive. Inertia and friction are relative, and “stopped” means less than 1% of starting speed. The model excludes overhauling loads, slip, changing mains, drive-specific ramp adaptation, and resistor thermal duty. Validate stopping distance and safety on the real machine using manufacturer data and measurements.
Try this: Select “Compare both.” Increase J and reduce friction; the shaft on the left takes longer to slow. Then shorten DEC and disable BR; the example bus trend on the right may reach the illustrative OV limit. Turn the appropriately sized resistor on again and observe that only the ramp-stop bus trend changes. This gives the braking resistor its actual role.
Which stop should a machine use?
Fans and some pumps: Coasting can make sense if the process accepts the rundown time. Check valve response, system pressure, reverse rotation, and the next start. Coasting does not automatically save energy or extend equipment life in every fan or pump. If a new command arrives while the fan is spinning, flying start may be needed to take control smoothly.
Conveyors and sensitive lines: If product position, web tension, or synchronization with another axis matters, a freewheel stop may create scrap. Set controlled deceleration against the load's allowable torque and stopping distance; an excessively aggressive ramp can also increase regenerative energy.
High-inertia flywheels: Coast is one possible choice, not a requirement. Depending on the required stop time, consider a longer DEC, an appropriately matched brake chopper and resistor, or another braking topology. Some drives automatically adapt the ramp when the DC link approaches its limit, making actual stop time longer than the set time. Regenerative energy belongs in the braking design.
Hoists, lifts, and suspended loads: If drive torque is holding the load, removing it need not bring the load to rest. It may even accelerate. The machine needs a correctly sequenced mechanical holding brake and a suitable safety design. A braking resistor is not a holding brake.
A practical commissioning check
- Confirm the stop source: Which mode does a terminal, keypad, PLC, or communication command actually call? Do not assume that a fault stop behaves like a routine stop.
- Observe the machine: Measure coast-down with no load and at the expected working load; check direction, access to moving parts, and what happens on restart. Mechanical motion may continue after the output reaches zero.
- Measure the ramp: If controlled stopping is needed, compare actual stop time, motor current, DC-link behavior, and drive fault records. For OV, review the DC bus and the manufacturer's ramp adaptation settings. Do not size a resistor solely from motor kW.
- Design safety separately: Safe Torque Off (STO) is a safety function intended to prevent torque generation through the drive. An ordinary coast command is not STO. STO on its own does not guarantee rapid stopping, load holding, or electrical isolation.
Frequently asked questions
Is coast stop a braking method?
The drive does not actively brake in a normal coast stop. The rotating system slows through the load, friction, or external mechanical effects. Releasing torque and actively braking are different actions.
Why doesn't the coast plot show a DC-bus rise?
In the typical freewheel scenario, the inverter stops applying braking torque and no longer brings energy back through that controlled path. Regenerative DC-link rise is a concern during driven deceleration. Other energy paths or overhauling arrangements require separate evaluation.
Will enabling a resistor make a coasting load stop faster?
No. In a compatible drive, a brake chopper and resistor dissipate the energy returned during active braking. A resistor does not press on a released shaft like a mechanical brake.
Is coast sufficient for an emergency stop?
That depends on the stopping distance and the machine risk assessment. A normal coast command is not itself a safety function; STO and related safety functions must be assessed as part of the complete machine safety system.
Technical references: Schneider Electric — freewheel/ramp stops; Schneider Electric — braking, DC bus, ramp adaptation. Drive-specific thresholds and wiring must come from the applicable manufacturer's manual.