What Is a Type R Thermocouple?

A Type R thermocouple is a noble-metal thermocouple made from a platinum-13% rhodium positive thermoelement and a platinum negative thermoelement. It is used primarily for high-temperature measurement, calibration work, laboratory systems and specialized industrial processes.

In simple terms: a Type R thermocouple generates a very small thermoelectric voltage that changes with temperature. A PLC, temperature controller or precision measuring instrument converts that voltage into temperature using the standardized Type R temperature–EMF reference function.

Type R is closely related to Type S, but the two are not interchangeable. Their positive thermoelements contain different rhodium concentrations, and their temperature–EMF reference characteristics are different.

What materials are used in a Type R thermocouple?

The nominal Type R thermoelement pair is:

Positive (+): Platinum-13% Rhodium, Pt-13%Rh
Negative (-): Platinum, Pt

Because both thermoelements are based on platinum-group precious metals, Type R belongs to the noble-metal thermocouple family.

Types R, S and B are all noble-metal thermocouples, but each uses a different thermoelement combination and has its own reference function.

What is the Type R reference temperature range?

The ITS-90 reference function for Type R covers approximately -50 °C to +1768 °C.

This should not be confused with the guaranteed continuous operating range of every physical Type R sensor.

The reference-function range and the practical service range of a real thermocouple are not the same thing.

Actual service limits depend on factors such as:

thermoelement diameter · ceramic insulation · protection tube · process atmosphere · contamination · mechanical construction · continuous or intermittent exposure.

The distinction between reference data and real sensor operating limits is explained further in IEC 60584-1 Thermocouple EMF Reference Functions and Tolerances.

Why is Type R used at high temperatures?

Platinum and platinum-rhodium alloys can provide useful thermoelectric stability at elevated temperatures when they are correctly protected and used in a suitable atmosphere.

Type R can therefore be used in applications such as:

high-temperature furnaces
ceramic processes
heat-treatment systems
laboratory furnaces
calibration systems
metallurgical research

High-temperature capability alone is not enough to guarantee long sensor life. Process atmosphere and protection material compatibility can be just as important as the thermocouple type itself.

Why is Type R considered a noble-metal thermocouple?

The positive thermoelement contains platinum and rhodium, while the negative thermoelement is platinum.

These materials are much more expensive than the base-metal alloys used in Type J, K, T, E or N thermocouples.

Type R cost can therefore be strongly influenced by:

platinum and rhodium content · wire diameter · thermoelement length · ceramic protection · calibration · protection tube · terminal-head construction.

The fact that Type R contains more rhodium in its positive leg than Type S can affect material cost, but it does not create a fixed price ratio between the two types. Current metal prices and total probe construction remain important.

For the broader cost factors, see Thermocouple Prices.

How does a Type R thermocouple work?

Like other thermocouples, Type R operates through the Seebeck effect.

The Pt-13%Rh and Pt thermoelements have different thermoelectric properties. When the circuit is exposed to a temperature distribution, a small electromotive force is generated.

The measuring instrument cannot interpret that voltage directly as degrees. It must account for the reference-junction temperature and then apply the Type R temperature–EMF relationship.

How large is the Type R output signal?

Type R has lower thermoelectric sensitivity than many common base-metal thermocouples. Its signal therefore remains in the millivolt range even at high temperatures.

This makes several characteristics of the measurement system particularly important:

low input offset
low electrical noise
stable measurement electronics
accurate cold-junction compensation
correct thermocouple wiring

In calibration and metrology work, a small error of only a few microvolts can represent a meaningful temperature error.

Type R temperature–EMF reference function

The forward Type R relationship can be written conceptually as:

E = f(t90)

A measuring instrument performs the inverse conversion:

t90 = g(E)

Temperature is expressed on the ITS-90 scale. The relationship between reference functions, tables and inverse polynomials is explained in Thermocouple Reference Tables, Polynomials and ITS-90.

Does Type R require cold-junction compensation?

Yes. Noble-metal construction does not remove the need for reference-junction compensation.

Type R reference functions are defined relative to a reference junction at 0 °C.

If the PLC, transmitter or temperature controller terminals are at another temperature, the instrument must apply cold-junction compensation (CJC).

Because Type R has relatively low EMF sensitivity, CJC performance and low-level measurement quality become especially important in precision applications.

What atmosphere is suitable for Type R?

Platinum and platinum-rhodium thermocouples generally perform best in clean oxidizing or neutral atmospheres.

Strongly reducing atmospheres, metallic vapours and certain high-temperature contaminants can alter the composition and thermoelectric behaviour of platinum thermoelements.

Contamination can change the local Seebeck coefficient of the wire and cause calibration drift even while the thermocouple remains electrically continuous.

When selecting Type R, consider process atmosphere as carefully as maximum temperature.

Why is Type R commonly used with ceramic insulation?

High-temperature Type R assemblies often use high-purity ceramic insulators to electrically separate the thermoelements and reduce contamination from surrounding materials.

High-purity alumina can be useful in appropriate applications because it helps isolate the platinum wires from unsuitable metallic materials and process contaminants.

The thermocouple may then be installed inside a ceramic or other suitable protection tube selected for the process.

Protection-tube selection should consider temperature, chemical compatibility and atmosphere, not mechanical strength alone.

Why is contamination critical for Type R?

Correct thermocouple output depends on thermoelement composition and thermoelectric homogeneity along the wire.

At high temperatures, foreign elements can diffuse into platinum or platinum-rhodium and change their local thermoelectric properties.

A contaminated Type R thermocouple may still show normal continuity on a multimeter but no longer maintain its original calibration.

Electrical continuity does not prove that a high-temperature thermocouple is still accurate.

Can Type R drift over time?

Yes. Noble-metal thermocouples can provide good stability, but they are not immune to long-term thermoelectric drift.

Possible causes include:

contamination
local changes in thermoelement composition
changes involving rhodium distribution or oxidation
mechanical strain
loss of thermoelectric homogeneity
prolonged high-temperature exposure

Critical processes may therefore require scheduled calibration, comparison against another reference sensor or planned replacement.

Type R versus Type S

Types R and S are closely related platinum thermocouples:

Type R: Pt-13%Rh / Pt
Type S: Pt-10%Rh / Pt

Both use platinum as the negative thermoelement. The principal nominal difference is the rhodium content of the positive leg.

That difference gives the two thermocouples different temperature–EMF reference functions. They do not produce exactly the same EMF at the same temperature.

A Type R thermocouple should therefore not be connected to an instrument configured for Type S.

See What Is a Type S Thermocouple? for the related sensor.

Is Type R better than Type S?

There is no universal answer.

The higher rhodium content in Type R does not automatically make it more accurate, more stable or longer-lasting than Type S at every temperature.

The correct choice depends on the process atmosphere, protection system, calibration requirements, existing instrumentation and applicable standard.

Type R versus Type B

Type R: Pt-13%Rh / Pt
Type B: Pt-30%Rh / Pt-6%Rh

Both Type B thermoelements contain rhodium, and its standardized reference function extends into a higher temperature region.

However, Type B is not simply a drop-in replacement for Type R when higher temperatures are encountered. The measuring instrument must support Type B, and the protection system, furnace atmosphere and intended operating range must also be appropriate.

See What Is a Type B Thermocouple?.

Type R versus Type K

Type K is a nickel-based base-metal thermocouple used extensively in general industrial machinery.

Type R is a platinum-rhodium/platinum noble-metal thermocouple used in more specialized high-temperature and calibration applications.

The higher cost of Type R does not automatically make it the better sensor for an ordinary moderate-temperature process. The sensor should match the actual application.

Type R versus Pt100

Type R measures temperature through thermoelectric EMF, while a Pt100 measures temperature through the resistance change of a platinum sensing element.

Pt100 sensors can offer excellent stability and accuracy through many low- and moderate-temperature applications. Type R extends into much higher-temperature measurement.

See Thermocouple vs Pt100 for the broader comparison.

Can Type R be connected directly to a PLC?

Yes, provided the PLC thermocouple input supports Type R.

When Type R is selected in the PLC thermocouple module, the module measures the low-level EMF, measures its terminal temperature, applies CJC and calculates temperature using the Type R reference function.

A standard 0–10 V analog input is not suitable for direct Type R measurement. The thermocouple signal is much smaller and requires dedicated low-level measurement and linearization.

Can Type R be connected to a temperature controller?

A temperature controller that explicitly supports Type R can accept the thermocouple directly.

The input must be configured as Type R. Selecting Type S or Type B applies the wrong temperature–EMF curve and produces an incorrect result.

Can Type R be converted to 4–20 mA?

Yes. A compatible temperature transmitter can measure the Type R thermocouple locally and convert the result into a standard process signal.

The transmitter performs Type R linearization and cold-junction compensation and can provide an output such as 4–20 mA.

This can be useful when the furnace and control panel are separated by a long cable distance.

Can compensating cable be used with Type R?

Yes. Running platinum and platinum-rhodium wire over long distances can be unnecessarily expensive.

Suitable compensating cable can therefore be used over defined ambient-temperature ranges in Type R measurement systems.

The compensating conductors are not the same noble-metal alloys as the actual thermocouple. They are selected to provide an appropriate thermoelectric approximation over their specified operating range.

Cable classes and tolerances are covered under IEC 60584-3 Thermocouple Extension and Compensating Cables.

What does Type R thermocouple tolerance mean?

A real Type R thermocouple can differ slightly from the ideal standardized reference function. The permitted difference is described by the applicable thermocouple tolerance.

Tolerance is not the same as calibration. Tolerance defines an allowable manufacturing deviation, while calibration determines the actual deviation of one individual sensor.

For current IEC terminology and tolerance interpretation, see Thermocouple Standards.

Why is individual calibration useful for Type R?

For high-temperature precision measurement, the nominal Type R reference function may not be enough by itself.

Individual calibration determines how a specific physical thermocouple differs from the standardized Type R reference relationship at selected temperatures.

Sensor-specific corrections can then be used together with the associated measurement uncertainty.

What contributes to Type R measurement uncertainty?

A precision Type R system can include uncertainty contributions from:

calibration · sensor drift · contamination · thermoelectric inhomogeneity · compensating cable · CJC · measuring instrument · furnace uniformity · immersion depth · temperature gradients.

The complete measurement chain should therefore be evaluated rather than quoting thermocouple tolerance alone.

The full method is discussed in Measurement Uncertainty in a Thermocouple System.

What should be specified when selecting a Type R thermocouple?

A useful Type R specification should include at least:

Normal process temperature
Maximum temperature
Continuous or intermittent exposure
Process atmosphere
Thermoelement diameter
Ceramic insulation type
Protection-tube material
Probe length and immersion depth
Type R support in the controller or PLC
Calibration requirement and target uncertainty

Above roughly 1000 °C, simply specifying “Type R” is not enough. Atmosphere and protection-material compatibility can become critical to sensor life and stability.

Advantages of Type R thermocouples

In a suitable application, Type R can offer:

high-temperature measurement capability
a well-characterized international reference function
useful high-temperature stability from noble-metal thermoelements
suitability for calibration and reference applications

Limitations of Type R thermocouples

Important limitations include:

high raw-material cost
lower thermoelectric sensitivity than many base-metal thermocouples
susceptibility to high-temperature contamination
need for appropriate ceramic insulation and protection
requirement for cold-junction compensation
possible long-term high-temperature drift

Conclusion

Type R is a Pt-13%Rh / Pt noble-metal thermocouple used primarily for high-temperature and precision temperature measurement.

Its ITS-90 reference function covers approximately -50 °C to +1768 °C, but this mathematical range should not be confused with the guaranteed continuous service range of every physical Type R sensor.

Real performance depends strongly on platinum and rhodium purity, process atmosphere, contamination, ceramic protection, thermoelectric homogeneity and calibration.

Type R and Type S may look similar, but they are not the same thermocouple. Type R must be measured as Type R, with suitable wiring, correct CJC and protection materials appropriate to the process.

Related thermocouple types and temperature measurement topics

+ Types of Thermocouples (T/C)

+ What Is a Type S Thermocouple? · What Is a Type B Thermocouple?

+ What Is a Type T Thermocouple? · Type K Thermocouples

+ What Is a Thermocouple (T/C)? · Seebeck Effect

+ Thermocouple Cold-Junction Compensation

+ Thermocouple Standards · IEC 60584-1

+ IEC 60584-3 Extension and Compensating Cables

+ Pt100 Sensors · Thermocouple vs Pt100

+ Temperature Sensor Converters · Temperature Controllers · PLC Systems