What Is a Type N Thermocouple?

A Type N thermocouple is a base-metal thermocouple that uses a nickel-chromium-silicon alloy commonly known as Nicrosil for the positive thermoelement and a nickel-silicon-magnesium alloy commonly known as Nisil for the negative thermoelement. It was developed to provide improved long-term thermoelectric stability in demanding high-temperature applications.

In simple terms: Type N works on the same basic thermoelectric principle as Type K, but it uses different alloys. It therefore has its own temperature–EMF reference characteristic and must be configured as Type N in the PLC, transmitter or temperature controller.

Type N should not be described simply as a “more expensive Type K.” Nicrosil and Nisil were developed specifically to improve resistance to some of the oxidation-related drift and short-term thermoelectric instability that can occur in conventional nickel-based thermocouples at elevated temperatures.

What materials are used in a Type N thermocouple?

The nominal Type N thermoelement system is:

Positive (+): Nickel-Chromium-Silicon alloy — Nicrosil
Negative (-): Nickel-Silicon-Magnesium alloy — Nisil

Type N belongs to the base-metal thermocouple family together with Types J, K, T and E. It is fundamentally different from platinum-based noble-metal thermocouples such as Types R, S and B.

Why was Type N developed?

One of the main reasons for developing Type N was to improve on certain long-term stability limitations found in the very widely used Type K thermocouple.

Type K is an extremely successful and economical industrial sensor, but prolonged exposure to high temperatures can cause oxidation, local compositional changes and thermoelectric inhomogeneity in its conductors.

Nickel-alloy thermocouples can also exhibit temporary EMF changes in certain intermediate-temperature regions because of structural and magnetic changes in the alloys.

The Nicrosil/Nisil system was developed specifically to reduce these effects and provide improved high-temperature thermoelectric stability.

Why can Type N be more stable than Type K?

The chromium, silicon and magnesium contents of the Nicrosil and Nisil alloys were selected partly to improve their oxidation behaviour at elevated temperatures.

Under suitable conditions, more protective oxide structures can form on the conductors. This helps reduce selective depletion of alloying elements and can preserve thermoelectric homogeneity better than conventional Type K materials during long-term exposure.

The objective was not simply to create a thermocouple with a higher maximum temperature. A major goal was to improve repeatability and long-term EMF stability after prolonged high-temperature operation.

Type N is not drift-free. Like every real base-metal thermocouple, it can still change chemically and physically after long exposure to severe temperatures.

What is the Type N reference temperature range?

The ITS-90 reference function for Type N is defined over approximately -270 °C to +1300 °C.

An important distinction must be made:

-270 to 1300 °C is the standardized reference-function range, not the guaranteed continuous operating range of every physical Type N probe.

The practical service range of a real sensor also depends on:

thermoelement diameter · sheath alloy · mineral insulation · process atmosphere · probe construction · duration of high-temperature exposure.

The difference between standardized reference data and real probe limits is discussed further in IEC 60584-1 Thermocouple EMF Reference Functions and Tolerances.

How does a Type N thermocouple work?

Type N operates through the same Seebeck effect used by other thermocouples.

Nicrosil and Nisil have different thermoelectric properties. When the thermocouple circuit is exposed to a temperature distribution, a small electromotive force is generated.

The EMF is only a few millivolts and does not change linearly with temperature. A fixed millivolts-per-degree factor therefore cannot accurately represent the complete Type N range.

Type N temperature–EMF reference function

The forward relationship can be represented conceptually as:

E = f(t90)

A measuring instrument performs the inverse conversion:

t90 = g(E)

The reference values are based on the ITS-90 temperature scale. The relationship between thermocouple tables, polynomial functions and ITS-90 is explained in Thermocouple Reference Tables, Polynomials and ITS-90.

Does Type N produce the same signal as Type K?

No. Type N and Type K do not produce the same EMF at the same temperature.

The overall Type N output is somewhat lower than Type K over much of the range, and the shape of its temperature–EMF curve is also different.

If an existing Type K probe is replaced with Type N, the measuring instrument must also be reconfigured for Type N.

Can Type N directly replace Type K?

Not as an electrical drop-in replacement.

Types K and N use:

different thermoelement alloys
different temperature–EMF reference functions
different extension/compensating wiring
different instrument input settings

The two probes may be manufactured with identical mechanical dimensions, but they cannot be treated as the same sensor by the measuring electronics.

Type N versus Type K

Type K uses nickel-chromium and nickel-aluminium based thermoelements.

Type N uses nickel-chromium-silicon and nickel-silicon-magnesium based thermoelements.

Both are nickel-based base-metal thermocouples capable of industrial high-temperature measurement.

Type N was specifically developed to provide improved long-term high-temperature stability, oxidation behaviour and repeatability through certain thermal cycles.

Type K remains far more common and is an excellent solution for a very large number of industrial processes. Type N should therefore not automatically replace every Type K installation.

Why is the intermediate-temperature region important?

Some conventional nickel thermocouple alloys can show temporary EMF shifts in an intermediate temperature region because of changes in short-range atomic ordering and magnetic structure.

These changes can influence repeatability after heating and cooling cycles.

The Nicrosil/Nisil alloy system was developed to reduce this behaviour, making Type N interesting not only for maximum temperature but also for applications where repeatability and long-term drift matter.

Why can Type N resist high-temperature oxidation better?

The alloy chemistry of Nicrosil and Nisil was designed to provide improved oxidation resistance compared with conventional Type K materials.

Under suitable oxidizing conditions, protective surface oxides can help reduce excessive local depletion of important alloying elements.

Maintaining a more uniform alloy composition helps preserve thermoelectric homogeneity and can reduce long-term EMF drift.

This does not mean that Type N cannot oxidize or age. Severe temperatures and long service periods can still alter its properties.

What atmospheres are suitable for Type N?

Type N is especially well known for high-temperature performance in suitable oxidizing environments, but no thermocouple alloy is universally compatible with every atmosphere.

Special attention may be required in:

sulfur-containing atmospheres
strong reducing environments
vacuum
metal vapours
processes chemically aggressive to the thermoelements or sheath

The thermocouple wires may be protected inside a metal sheath, but the process atmosphere and sheath alloy still need to be selected together.

Can Type N be made as a mineral-insulated thermocouple?

Yes. Type N is commonly available in mineral-insulated metal-sheathed constructions.

Nicrosil and Nisil conductors can be embedded in compacted mineral insulation inside a metal sheath, producing small-diameter probes with good mechanical strength and vibration resistance.

The general requirements for this sensor construction are discussed in IEC 61515 Mineral-Insulated Metal-Sheathed Thermocouples.

Can Type N be grounded, ungrounded or exposed?

Yes. The Type N designation identifies the thermoelement system, not the mechanical construction of the measuring junction.

A Type N probe can be manufactured with a:

grounded junction
ungrounded junction
exposed junction

The differences in thermal response and electrical isolation are explained in Grounded, Ungrounded and Exposed-Junction Thermocouple Differences.

Does Type N require cold-junction compensation?

Yes. Type N is a standard thermoelectric measurement system and its reference-junction temperature must be taken into account.

Its reference functions assume a reference junction at 0 °C.

A PLC, transmitter or controller operating at another terminal temperature must therefore apply cold-junction compensation (CJC).

Why is the correct Type N extension cable important?

A Type N thermocouple should not simply be extended using Type K thermocouple cable.

The connection between sensor and instrument should use wiring with the appropriate Type N thermoelectric characteristics, such as NX extension cable or a suitable Type N compensating cable.

Cable classes and tolerances are addressed in IEC 60584-3 Thermocouple Extension and Compensating Cables.

Using the wrong cable can create additional thermoelectric junction errors even when both the sensor and PLC are functioning correctly.

Can Type N be connected directly to a PLC?

Yes, provided the PLC thermocouple module supports Type N.

The PLC thermocouple input should be configured for Type N.

The module then:

measures the Type N EMF
measures terminal temperature
applies CJC
uses the Type N reference function for linearization
provides the resulting temperature to the PLC program

If a physical Type N thermocouple is connected while the input is configured for Type K, the calculated temperature will be incorrect.

Can Type N be converted to 4–20 mA?

Yes. A compatible temperature transmitter or sensor converter can measure a Type N thermocouple locally.

The transmitter applies Type N linearization and CJC, then converts the calculated temperature into a standard process signal such as 4–20 mA.

This can be useful when the thermocouple is far from the control cabinet or where electrical noise makes long low-level thermocouple runs undesirable.

Can Type N be used on machines with VFDs?

Yes. However, Type N is not inherently immune to electromagnetic interference.

A thermocouple cable routed close to VFD motor wiring, servo cables or other switching power circuits can pick up noise because the Type N signal is only a few millivolts.

Signal and power wiring should be separated appropriately, shielding and grounding should be designed correctly, and a local transmitter can be considered where necessary.

Type N versus Type E

Type E uses nickel-chromium against a copper-nickel alloy, while Type N uses the Nicrosil/Nisil alloy system.

Type E is well known for relatively high thermoelectric sensitivity. Type N was developed primarily for improved high-temperature stability and oxidation behaviour.

The better choice therefore depends on the process temperature and the measurement priorities.

Type N versus Type T

Type T uses copper and copper-nickel thermoelements and is especially important in low-temperature measurement.

Type N is nickel based and is primarily associated with higher-temperature industrial applications.

Their reference functions and extension wiring are completely different.

Type N versus Pt100

Type N measures temperature through thermoelectric EMF, while a Pt100 measures the temperature-dependent resistance of a platinum element.

Pt100 can offer excellent stability and accuracy in many low- and moderate-temperature applications. Type N extends into much higher-temperature base-metal thermocouple service.

For the broader comparison, see Thermocouple vs Pt100.

What does Type N thermocouple tolerance mean?

A real Type N thermocouple can deviate slightly from its standardized reference function. The permitted deviation is described by the applicable thermocouple tolerance.

Tolerance does not define the accuracy of the complete measurement system.

PLC input performance, CJC, extension cable, calibration, installation and sensor drift can all contribute additional error or uncertainty.

For current IEC terminology, see Thermocouple Standards.

Does a Type N thermocouple need calibration?

Individual calibration is not mandatory for every ordinary industrial Type N installation.

However, sensor-specific calibration can be important in critical heat treatment, laboratory work, aerospace testing and applications requiring lower measurement uncertainty.

Calibration determines how the actual physical sensor differs from the standardized Type N reference function.

Why does high-temperature recalibration require care?

Base-metal thermocouples can change chemically and physically during high-temperature service.

A high-temperature recalibration cycle can itself expose the thermocouple to additional thermal ageing, oxidation and diffusion.

The act of recalibrating a heavily used high-temperature sensor is therefore not always completely non-invasive. The sensor can continue to change during the calibration process.

What contributes to Type N measurement uncertainty?

Important contributors can include:

sensor calibration or tolerance
high-temperature drift
thermoelectric inhomogeneity
extension wiring
cold-junction compensation
measurement electronics
electromagnetic interference
immersion depth
process temperature gradients

For critical measurements, the complete system should be evaluated using a full thermocouple measurement uncertainty approach.

Where are Type N thermocouples used?

With a suitable probe construction, Type N can be used in:

high-temperature furnaces
heat-treatment processes
turbine and engine testing
aerospace equipment
energy systems
semiconductor process equipment
applications where long-term temperature stability is important

The process atmosphere and sheath construction remain part of the sensor selection and should not be ignored.

What should be specified when selecting a Type N thermocouple?

A useful Type N specification should include at least:

Normal and maximum process temperature
Process atmosphere
Probe diameter and insertion length
Sheath material
Grounded or ungrounded junction
Cable type and length
Type N support in the PLC or controller
Required tolerance and calibration level
Expected continuous service duration

Advantages of Type N thermocouples

In the correct application, Type N can provide:

Improved high-temperature thermoelectric stability compared with conventional Type K materials
Improved oxidation resistance
Reduced short-term EMF changes in certain intermediate-temperature regions
Suitability for high-temperature base-metal thermocouple service
Availability in mineral-insulated and other rugged industrial probe constructions

Limitations of Type N thermocouples

Important limitations include:

It may be less widely stocked than Type K.
It is not electrically interchangeable with Type K.
Correct Type N wiring and instrument configuration are required.
It is not completely free from high-temperature drift.
Process atmosphere, especially sulfur-containing environments, requires careful evaluation.
Like other thermocouples, it requires correct CJC and low-level measurement electronics.

Conclusion

Type N is a Nicrosil/Nisil base-metal thermocouple developed to provide improved thermoelectric stability in demanding high-temperature measurement.

Its ITS-90 reference function covers approximately -270 °C to +1300 °C, but this mathematical range should not be confused with the guaranteed continuous service range of every physical Type N probe.

The main advantage of Type N over Type K is not simply a higher temperature limit. Its distinguishing feature is the improved oxidation, long-term drift and thermoelectric stability behaviour of the Nicrosil/Nisil alloy system.

Reliable Type N measurement still requires correct Type N extension wiring, proper cold-junction compensation, the correct PLC or transmitter configuration, a suitable sheath and a probe construction compatible with the actual process atmosphere.

Related thermocouple types and temperature measurement topics

+ Types of Thermocouples (T/C)

+ Type K Thermocouples · What Is a Type E Thermocouple?

+ What Is a Type T Thermocouple? · What Is a Type S Thermocouple?

+ What Is a Thermocouple (T/C)? · Seebeck Effect

+ Thermocouple Cold-Junction Compensation

+ Thermocouple Standards · IEC 60584-1

+ IEC 60584-3 Extension and Compensating Cables · IEC 61515 MI Thermocouples

+ Pt100 Sensors · Thermocouple vs Pt100

+ Temperature Sensor Converters · Temperature Controllers · PLC Systems