Vacon VFD Fault code 2

   Active faults menu for Vacon ac drive
   The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display.
   When a fault brings the frequency converter to a stop, the location indication F1, the fault code, a short description of the fault and the fault type symbol will appear on the display.
addition, the indication FAULT or ALARM is displayed and, in case of a FAULT, the red led on the keypad starts to blink. If several faults occur simultaneously, the list of active faults can be browsed with the Browser buttons.
   The memory of active faults can store the maximum of 10 faults in the order of appearance. The display can be cleared with the Reset button and the read-out will return to the same state it was before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset signal from the I/O terminal or fieldbus.
Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the drive.

A (Alarm)
This type of fault is a sign of an unusual operating condition. It does not cause the drive to stop, nor does it require any special actions.
The 'A fault' remains in the display for about 30 seconds.
F (Fault)
An 'F fault' is a kind of fault that makes the drive stop.
Actions need to be taken in order to restart the drive.
AR (Fault Autoreset)
If an 'AR fault' occurs the drive will also stop immediately. The fault is reset automatically and the drive tries to restart the motor. Finally, if the restart is not successful, a fault trip (FT, see below) occurs.
FT (Fault Trip)
If the drive is unable to restart the motor after an AR fault an FT fault occurs. The effect of the 'FT fault' is basically the same as that of the F fault: the drive is stopped.

The fault codes,
Their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The items written in white on black background present faults for which you can program different responses in the application. See parameter group Protections.

Note: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display.

------------------
29 Thermistor fault
The thermistor input of option board has detected increase of the motor temperature
Check motor cooling and loading
Check thermistor connection
(If thermistor input of the option board is not in use it has to be short circuited)
------------------
30 Safe disable
The input on OPTAF board has opened Cancel Safe (STO) Disable if this can be done safely.
------------------
31 IGBT temperature (hardware)
IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current
Check loading.
Check motor size.
Make identification run.
------------------
32 Fan cooling
Cooling fan of the frequency converter does not start, when ON command is given
Contact the our technical personal..
------------------
34 CAN bus communication
Sent message not acknowledged. Ensure that there is another device on the bus with the same Can bus configuration.
------------------
35 Application Problem in application software
Contact the our technical personal.. If you are application programmer check the application program.
------------------
36 Control unit NXS
Control Unit can not control NXP Power Unit and vice versa
Change control unit
------------------
37 Device changed (same type)
Option board or control unit changed.
Same type of board or same power rating of drive.
Reset. Device is ready for use.
Old parameter settings will be used.
------------------
38 Device added (same type)
Option board or drive added. Reset. Device is ready for use.
Old board settings will be used.
------------------
39 Device removed Option board removed. Reset. Device no longer available.
------------------
40 Device unknown
Unknown option board or drive.
Subcode in T.14:
S1 = Unknown device
S2 = Power1not same type as Power2
Contact the our technical personal..
------------------
41 IGBT temperature
IGBT Inverter Bridge overtemperature protection has detected too high a short term overload current
Check loading.
Check motor size.
Make identification run.
------------------
42 Brake resistor
Problems with brake resistor. Set the deceleration time longer.
Use external brake resistor.
------------------
43 Encoder fault
Problem detected in encoder signals.
Subcode in T.14:
1 = Encoder 1 channel A is missing
2 = Encoder 1 channel B is missing
3 = Both encoder 1 channels are missing
4 = Encoder reversed
5 = Encoder board missing
Check encoder channel connections.
Check the encoder board.
Check encoder frequency in open loop.
------------------
44 Device changed (different type)
Option board or power unit changed.
New device of different type or different power rating.
Reset
Set the option board parameters again if option board was changed.
Set converter parameters again if power unit was changed.
------------------
45 Device added (different type)
Option board of different type added. Reset
Set the option board parameters again.
------------------
49 Division by zero in application
Division by zero has occurred in application program.
Contact your distributor if the fault reoccurs while the converter is in run state. If you are application programmer check the application program.


++ Fault time data record
When a fault occurs the information described above in 7.3.4 is displayed. By pushing the Menu button right here you will enter the
Fault time data record menu indicated by T.1-T.13. In this menu, some selected important data valid at the time of the fault are recorded. This feature is intended to help the user or the service person to determine the cause of fault.
The data available are:
T.1 Counted operation days
(Fault 43: Additional code)
T.2 Counted operation hours
(Fault 43: Counted operation days) hh:mm:ss
T.3 Output frequency
(Fault 43: Counted operation hours)
T.4 Motor current A
T.5 Motor voltage V
T.6 Motor power %
T.7 Motor torque %
T.8 DC voltage V
T.9 Unit temperature °C
T.10 Run status
T.11 Direction
T.12 Warnings
T.13 0-speed