Vacon VFD Fault code 3

   Active faults menu for Vacon ac drive
   The Active faults menu can be entered from the Main menu by pushing the Menu button right when the location indication M4 is visible on the first line of the keypad display.
   When a fault brings the frequency converter to a stop, the location indication F1, the fault code, a short description of the fault and the fault type symbol will appear on the display.
addition, the indication FAULT or ALARM is displayed and, in case of a FAULT, the red led on the keypad starts to blink. If several faults occur simultaneously, the list of active faults can be browsed with the Browser buttons.
   The memory of active faults can store the maximum of 10 faults in the order of appearance. The display can be cleared with the Reset button and the read-out will return to the same state it was before the fault trip. The fault remains active until it is cleared with the Reset button or with a reset signal from the I/O terminal or fieldbus.
Note! Remove external Start signal before resetting the fault to prevent unintentional restart of the drive.

A (Alarm)
This type of fault is a sign of an unusual operating condition. It does not cause the drive to stop, nor does it require any special actions.
The 'A fault' remains in the display for about 30 seconds.
F (Fault)
An 'F fault' is a kind of fault that makes the drive stop.
Actions need to be taken in order to restart the drive.
AR (Fault Autoreset)
If an 'AR fault' occurs the drive will also stop immediately. The fault is reset automatically and the drive tries to restart the motor. Finally, if the restart is not successful, a fault trip (FT, see below) occurs.
FT (Fault Trip)
If the drive is unable to restart the motor after an AR fault an FT fault occurs. The effect of the 'FT fault' is basically the same as that of the F fault: the drive is stopped.

The fault codes,
Their causes and correcting actions are presented in the table below. The shadowed faults are A faults only. The items written in white on black background present faults for which you can program different responses in the application. See parameter group Protections.

Note: When contacting distributor or factory because of a fault condition, always write down all texts and codes on the keypad display.

50 Analogue input
Iin < 4mA (sel.signal range 4 to 20 mA)
Current at the analogue input is < 4mA.
− control cable is broken or loose
− signal source has failed
Check the current loop circuitry.
------------------
51 External fault
Digital input fault. Remove fault situation on external device.
------------------
52 Keypad communication fault
The connection between the control keypad (or NCDrive) and the frequency converter is broken.
Check keypad connection and possible keypad cable.
------------------
53 Fieldbus fault
The data connection between the fieldbus
Master and the fieldbus board is broken
Check installation.
If installation is correct Contact the our technical personal..
------------------
54 Slot fault Defective option board or slot Check board and slot.
Contact the our technical personal..
------------------
56 PT100 board temp. fault
Temperature limit values set for the
PT100 board parameters have been exceeded
Find the cause of temperature rise
------------------
57 Identification Identification run has failed.
Run command was removed before completion of identification run.
Motor is not connected to frequency converter.
There is load on motor shaft.
------------------
58 Brake
Actual status of the brake is different from the control signal.
Check mechanical brake state and connections.
------------------
59 Follower communication
System modBus is broken between Master and Follower
Check option board parameters.
Check optical fibre cable.
------------------
60 Cooling
Coolant circulation on liquid-cooled drive has failed.
Check reason for the failure on external system.
------------------
61 Speed error
Motor speed is unequal to reference Check encoder connection.
PMS motor has exceeded the pull out torque.
------------------
62 Run disable Run enable signal is low Check reason for Run enable signal.
------------------
63 Emergency stop
Command for emergency stop received from digital input or fieldbus
New run command is accepted after reset.
------------------
64 Input switch open
Drive input switch is open Check the main power switch of the drive.
------------------
65 PT100 board 2 temp fault
Temperature limit values set for the PT100 board parameters have been exceeded.
More inputs are selected than actually connected.
PT100 cable is broken.
Find the cause of temperature rise.
------------------
74 Follower fault
When using normal Master Follower function this fault code is given if one or more follower drives trip to fault.


++ Fault time data record
When a fault occurs the information described above in 7.3.4 is displayed. By pushing the Menu button right here you will enter the
Fault time data record menu indicated by T.1-T.13. In this menu, some selected important data valid at the time of the fault are recorded. This feature is intended to help the user or the service person to determine the cause of fault.
The data available are:
T.1 Counted operation days
(Fault 43: Additional code)
T.2 Counted operation hours
(Fault 43: Counted operation days) hh:mm:ss
T.3 Output frequency
(Fault 43: Counted operation hours)
T.4 Motor current A
T.5 Motor voltage V
T.6 Motor power %
T.7 Motor torque %
T.8 DC voltage V
T.9 Unit temperature °C
T.10 Run status
T.11 Direction
T.12 Warnings
T.13 0-speed