Toshiba VF-A5 Fault codes 1

Hi everyone,

OC 1, OC 1P: Overcurrent during acceleration (DC section)
- The acceleration time ACCACC is too short.
- The V/f selection is incorrect.
- Start was attempted on a rotating motor after a momentary power failure.
- Is a special (low impedance) motor being used?

    Solutions:
- Increase the acceleration time ACCACC.
- Check the V/f pattern setting.
- Use auto-restart or regeneration power ride-through control.
- Try inserting an AC reactor on the output.
- Try increasing the carrier frequency.

OC 2, OC 2P: Overcurrent during deceleration (DC section)
- The deceleration time dECdEC is too short.

    Solutions:

- Increase the deceleration time dECdEC.

OC 3, OC 3P: Overcurrent during constant speed run (DC section)
- The load changed suddenly.
- The load is faulty.

    Solutions:
- Reduce the load fluctuations.
- Check the load equipment.

Note: Additional Causes for OC 1P, OC 2P, and OC 3P
- A main circuit power transistor is faulty.
- The overheating protection has functioned (5.5~30kW).
- The control power supply undervoltage protection has functioned (5.5~30kW).

    Solutions:
- Refer to OCROCR.
- Refer to OHOH.
- Refer to UPUP, POFFPOFF, NOFFNOFF.

OCL: Overcurrent (overcurrent on load-side during start-up)
- The output main circuit wiring or motor insulation is faulty.
- The motor impedance is too small.

    Solutions:
- Check the condition of the wiring and insulation.
- Change the setting of the output short circuit detection selection OLLSOLLS.

OCA 1: U-phase armature short circuit
- The main circuit U-phase power transistor is faulty.

    Solutions:
- Check the main circuit U-phase power transistor.

OCA 2: V-phase armature short circuit
- The main circuit V-phase power transistor is faulty.

    Solutions:
- Check the main circuit V-phase power transistor.
- The transistor element must be replaced.

OCA 3: W-phase armature short circuit
- The main circuit W-phase power transistor is faulty.

    Solutions:
- Check the main circuit W-phase power transistor.
- The transistor element must be replaced.

OP 1: Overvoltage during acceleration
- The input voltage fluctuated abnormally.
+ The power source capacity is 500kVA or more.
+ Power-factor improvement capacitors went on-line/off-line.
+ A device using thyristors is connected to the same power line.
- Start was attempted on a rotating motor after a momentary power failure, etc.

    Solutions:
- Try inserting an input AC reactor.
- Use auto-restart or regeneration power ride-through control.

OP 2: Overvoltage during deceleration
- The acceleration time dECdEC is too short. (The amount of regenerated power is too large.)
- The DBR resistance value PBrPBr is too large.
- The dynamic braking function PBrPBr is OFF.
- OP stall OPSSOPSS is OFF.
- The input voltage fluctuated abnormally.
+ The power source capacity is 500kVA or more.

    Solutions:
- Increase the deceleration time dECdEC.
- Install a dynamic braking resistor.
- Decrease the dynamic braking resistance value PBrPBr.
- Select the dynamic braking function PBrPBr.
- Select OP stall OPSSOPSS.
- Try inserting an input AC reactor.

OP 3: Overvoltage during constant speed run
- The input voltage fluctuated abnormally.
+ The power source capacity is 500kVA or more.
+ Power-factor improvement capacitors went on-line/off-line.
+ A device using thyristors is connected to the same power line.
- The motor is rotating at a frequency higher than the inverter output frequency due to a force on the load and is in a regenerative state.
+ There are multiple mechanically-coupled motors.
+ The load undergoes piston-type cyclic movement.

    Solutions:
- Try inserting an input AC reactor.
- Change the load so that a regenerative state is not entered.
- Install a dynamic braking resistor.

OLIn: Inverter overload

- Sudden motor acceleration was attempted.
- The DC injection current (time) is set too high (long).
- Start was attempted on a rotating motor after momentary power failure, etc.
- The load is too large.

    Solutions:
- Increase the acceleration time ACCACC.
- Decrease the DC injection current dCIdCI and DC injection time dCIdCI.
- Use auto-restart or regeneration power ride-through control.
- Increase the inverter rating.

+ Toshiba VF-A5 User Manual  >>

+ VF-A5 Fault codes 1 >>

+ VF-A5 Fault codes 2 >>

+ VF-A5 Fault codes 3 >>


+ Toshiba 2 Main page -

+ Used VFD Models

+ VFD Main page -

-

"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us."  08.03.2013    