Toshiba VF-S15 Fault Codes 4
Hi everyone,
When
a problem occurs, diagnose according to the table below. If parts
replacement is necessary or the problem cannot be resolved with the
solutions listed in the table, contact your Toshiba distributor.
Error Code: EF 2
Problem: Ground fault
Possible Causes:
+ Parameter P−6P−6 is set and a high-speed motor is connected.
+ There is a ground fault in the output cable or motor.
+ Excessive current in dynamic braking resistor.
Solutions:
+ Check cables and motor for ground faults.
+ Increase deceleration time DECDEC.
+ Set supply voltage correction F302F302 to 0.
Error Code: SOut
Problem: Step-out (for PM motor driver only)
Possible Causes:
+ Motor shaft is locked.
+ An output phase is open.
+ A pulse load has been applied.
+ DC braking function.
Solutions:
+ Unlock the motor shaft.
+ Check the connection cables between the inverter and motor.
+ Extend acceleration/deceleration time.
+ Disable the step-out function when using servo lock.
Error Code: ELP YP
Problem: Inverter type error
Possible Causes:
+ There may be a fault failure.
Solutions:
+ Contact your Toshiba distributor.
Error Code: E-13
Problem: Over-speed error
Possible Causes:
+ Input voltage fluctuates abnormally.
+ Over-speed error due to over-voltage limit operation.
Solutions:
+ Install an optional dynamic braking resistor (optional).
Error Code: E-18
Problem: Analog input cutoff detection error
Possible Causes:
+ Input signal from V1 to C2 is below F633F633 setting or less.
Solutions:
+ Check input signal level and wiring.
Error Code: E-19
Problem: CPU communication error
Possible Causes:
+ A communication error occurs between control CPUs.
Solutions:
+ Check the control PCB and re-establish communication.
Error Code: OLF
Problem: Over torque increase error
Possible Causes:
+ Automatic torque increase parameter F402F402 setting is too high.
+ Motor impedance is low.
Solutions:
+ Set a lower automatic torque increase parameter value or disable it.
Error Code: Erc7
Problem: CPU error 2
Possible Causes:
+ Control CPU is faulty.
Solutions:
+ Contact your Toshiba distributor.
Error Code: Erc8
Problem: Optional unit error 2
Possible Causes:
+ An optional device is faulty.
Solutions:
+ Contact your Toshiba distributor.
Error Code: Erc9
Problem: Internal circuit error
Possible Causes:
+ Internal circuit is faulty.
Solutions:
+ Contact your Toshiba distributor.
Error Code: E-31
Problem: Main power On/Off heavy cycling
Possible Causes:
+ Main power On/Off is frequently performed during operation.
+ If caused by other reasons, there may be a startup error.
Solutions:
+ Reduce the frequency of main power On/Off during operation.
Error Code: E-32
Problem: PTC error
Possible Causes:
+ PTC thermal protection is activated.
Solutions:
+ Check the PTC in the motor.
Error Code: E-37
Problem: Servo lock error
Possible Causes:
+ Motor shaft did not lock during servo lock operation.
Solutions:
+ Reduce load during servo lock operation.
Note: For all unresolved issues, it is recommended to contact your Toshiba distributor for further assistance.
------
>> VF-S15 User manual
>> VF-S15 Faul codes
>> Toshiba Homepage
---------
"* The user manuals, commissioning suggestions, error codes, and solution recommendations provided on this page are not binding. The information and documents above are open to and even in need of improvement. As the Otomasyon Mall Community, we gladly welcome your suggestions and contributions. If you have field experience and insights on ease of use, please do not hesitate to share them with us." 12.08.2014