Teco VFD fault codes 4
TECO VFD Fault Codes 4
This page covers additional TECO VFD parameter, PID, pump/HVAC, start-protection and control-board fault codes. Parameter numbers are included where they are available in the source documentation.
Current and Automatic Reset Messages
CLB – Overcurrent Protection Level B
Description: The inverter current has reached protection level B.
Possible causes:
- Inverter current is too high.
- Mechanical load is too heavy.
Check:
- Check the mechanical load.
- Check the inverter output current.
- Check the machine duty cycle.
Retry – Automatic Reset in Progress
Description: This is a status message rather than a fault. The automatic reset function is active and the message is displayed until the reset period has finished.
The source associates this function with parameter 07-01. The message normally clears when the automatic reset period expires.
External Fault Inputs
EF1 / EF2 / EF3 – External Faults
Description: An external fault signal has been received through terminals S1, S2 or S3.
Input settings:
EF1: 03-00 = 25
EF2: 03-01 = 25
EF3: 03-02 = 25
The source states that inverter external-fault selection parameter 08-24 = 2 is used for this condition.
Check:
- Check the external device connected to the input.
- Check the multifunction input assignment.
- Check the S1–S3 wiring.
Parameter Setting Errors
SE01 – Parameter Range Error
Description: A parameter has been set outside the permitted range, usually because its valid range depends on another parameter.
Examples given in the source:
- 02-00 > 02-01
- 00-12 < 00-13
- When 00-07 = 1, 00-05 and 00-06 may conflict.
- 20-16 ≤ 20-15
Check: Review the related parameters together and correct any value that falls outside the permitted range.
SE02 – Digital Input Terminal Error
Description: There is a conflict in the multifunction digital-input assignments.
Possible causes:
- Two or more inputs from 03-00 to 03-07 are assigned to the same function, except for functions where duplication is permitted.
- UP / DOWN commands are not assigned as a valid pair.
- UP / DOWN functions 08 / 09 conflict with ACC / DEC function 11.
- Speed Search 1 (19) and Speed Search 2 (34) are assigned at the same time.
Check: Review the multifunction input assignments at 03-00 through 03-07.
SE03 – V/f Curve Error
Description: The V/f frequency points are not set in the correct order.
Source relationship:
01-02 > 01-12 > 01-06 > 01-08
Fmax > Fbase > Fmid1 > Fmin
For the second V/f curve, the source gives:
201-16 > 01-24 > 01-20 > 01-22
Check: Review and correct the V/f frequency parameters.
SE05 – PID Selection Error
Description: PID reference or feedback-source settings conflict with each other.
Check:
- Make sure 10-00 and 10-01 are not both assigned to AI1 or AI2 in an invalid combination.
- Check parameters 10-33, 10-34 and 23-05.
HPErr – Model / Capacity Selection Error
Description: The inverter capacity setting does not match the rated voltage class.
Check: Check inverter capacity / model parameter 13-00.
SE09 – PI Setting Error
Description: The pulse-input selection conflicts with the PID source settings.
Check:
- Pulse-input selection: 03-30
- PID source settings: 10-00 / 10-01
PID Feedback and Start Protection
FB – PID Feedback Loss
Description: The PID feedback signal has remained below the level set in 10-12 for longer than the time set in 10-13.
Check:
- Check the feedback wiring.
- Measure the feedback sensor signal.
- Replace the sensor if necessary.
USP – Unattended Start Protection
Description: The drive detected an active RUN command at power-up while Unattended Start Protection was enabled. The inverter will not accept the start command until the condition is cleared.
Check:
- Remove the RUN command.
- Reset the inverter through the appropriate multifunction input where configured.
- The RESET key on the keypad can also be used where applicable.
- Check the USP input and power-up command sequence.
Pump and HVAC Faults
LFPB – Low Flow Fault
Description: HVAC flow feedback is below the configured minimum-flow limit.
Check:
- Check that the feedback sensor is connected correctly.
- Check the feedback signal.
- Compare the actual value with the configured minimum-flow limit.
HFPB – High Flow Fault
Description: HVAC flow feedback has exceeded the configured maximum-flow limit.
Check:
- Check the feedback sensor and signal.
- Check sensor calibration.
- Compare the actual feedback value with the maximum-flow limit.
LPBFT – Low Pressure Fault
Description: Pump pressure feedback is below the configured minimum-pressure limit, or the feedback signal is missing.
Check:
- Check the pressure sensor connection.
- Check the pressure-feedback signal.
- Compare the actual pressure with the minimum-pressure setting.
OPBFT – High Pressure Fault
Description: Pump pressure feedback has exceeded the configured maximum-pressure limit.
Check:
- Check the pressure-feedback signal.
- Check the pressure sensor and calibration.
- Compare the measured pressure with the configured maximum-pressure limit.
LSCFT – Low Suction Fault
Description: The pump application has detected inadequate suction.
Possible causes:
- Insufficient water in the supply tank.
- Unstable or restricted suction flow.
- PID difference has exceeded its configured level.
- Output current has fallen below the configured level.
Check:
- Check that the tank contains enough water.
- Check the suction pipe and water supply.
- Check the PID difference.
- Check inverter output current.
Fire and Pump Control Functions
FIRE – Fire Override Mode
Description: Fire Override mode is active. This is a status indication rather than a normal inverter fault.
SE10 – PUMP / HVAC Setting Error
Description: There is an invalid relationship between the pump or HVAC parameters.
Check:
- Pump parameters: 23-02 / 23-03
- HVAC parameters: 23-46 / 23-47
COPUP – Pump Communication Loss
Description: Communication has been lost between drives in a multi-pump or cascade-control system.
Check:
- Check the cascade communication wiring.
- Check communication settings.
- Check that all drives are connected correctly.
Other Parameter and Start Messages
ParEr – Parameter Setting Error
Description: A parameter setting is not valid for the current configuration.
Check: Review the relevant parameter in the instruction manual and check whether the function has been disabled by another setting.
StP1 – Direct Start Warning
Description: The inverter cannot start directly because a RUN input at S1–S6 is already active while 07-04 = 1.
Check:
- Check the RUN input.
- Remove the digital RUN command.
- After delay time 07-05 has expired, apply the RUN command again.
Control Board and Memory Errors
AdCer – ADC Voltage Error
Description: An abnormal voltage level has been detected on the control board.
Possible causes:
- Abnormal input voltage.
- Excessive electrical noise.
- Control-board fault.
Check:
- Check the incoming voltage.
- Check the control-board voltage levels.
- Check for electrical noise or interference.
EPErr – EEPROM Archiving Error
Description: A problem has occurred while reading or writing parameter data in the EEPROM, often during the drive start-up check.
Check:
- Power-cycle the inverter.
- If the warning returns, inspect the EEPROM and control-board circuitry.
- Control-board replacement may be required if the error remains.
bdErr – Control Board Error
Description: The installed control board does not match the inverter program or hardware configuration.
Check: Verify that the control board is correct for the inverter model. Replace it with the correct board if necessary.
TECO VFD Fault Code Pages
+ TECO VFD Fault Codes – Main Page
Related TECO Pages