6ES7 124-1FA00-0AB0
Siemens 6ES7 124-1FA00-0AB0 – SIMATIC SC 1 AO U
The 6ES7 124-1FA00-0AB0 is a single-channel analog voltage output module in the SIMATIC SC / Smart Connect family. It is used in ET 200L-SC and compatible IM-SC arrangements within the Siemens ET 200 range. It converts a digital command from the main PLC into a −10 to +10 V or 1–5 V signal for equipment with a suitable analog input, such as a drive or valve controller.
Voltage and current outputs
This module generates an analog command; it does not acquire sensor measurements like an analog input module. It is also not a 4–20 mA output module. The SC family's 6ES7 124-1GA00-0AB0 is a separate current-output model. Match the selected output range to the receiving device's signal requirements.
Resolution is 12 bits for ±10 V and 11 bits for 1–5 V. The maximum conversion time is 5 ms; this is not the complete response time including PLC scanning and communication. In analog signal control, resolution must also be distinguished from accuracy: the specified basic error limit is ±0.6% at 25 °C, and the operational error limit is ±0.9% over the full temperature range.
Terminal block and space requirements
The module plugs into a TB 16SC terminal block and occupies two of its eight SC slots. One output does not mean a single-slot module. Dimensions are 20 × 64 × 51 mm, in width, height and depth order. Field wires connect to the terminal block rather than directly to the electronics module.
Check SC bus connections and available slots when assessing the station's connection arrangement and accessories. The ET 200 family overview helps distinguish fixed ET 200L blocks from systems with SC expansion; the ET 200 name alone does not establish compatibility.
QV and S terminals: two-wire and four-wire circuits
The module connections are 1: QV+, 3: QV−, 2: S+, 4: S−. QV carries the output voltage, while S senses the voltage at the load. In the manual's TB 16SC position A example, these correspond to A1, A3, A2 and A4, respectively. Check the actual terminal letter against the installed module position.
In a four-wire circuit, S+ and S− connect directly to the load terminals, allowing compensation for voltage drops along the output leads. For a two-wire circuit, bridge QV+ to S+ and QV− to S− at the terminal block; cable resistance is then not compensated. S+ and S− must not be left unconnected.
Supply and load requirements
The electronics requires 24 V DC, drawing up to 50 mA from L+, with a maximum power loss of 1 W. The 50 mA figure describes supply consumption. Keep this distinction when calculating the power supply and power distribution requirements.
Load resistance must be at least 1 kΩ within the rated output range, and capacitive load must not exceed 1 µF. The specified shielded-cable limit is 200 m; consider cable properties together with the receiver's input characteristics. The output is short-circuit protected, but the approximately 30 mA short-circuit figure is not a continuous operating load rating.
Parameters and PLC values
Check both the output range and the SIMATIC S7/S5 data format in the project. The default voltage range is ±10 V. In S7 representation, nominal values are −27648 → −10 V, 0 → 0 V and 27648 → +10 V. With 1–5 V selected, 0 represents 1 V and 27648 represents 5 V. Do not transfer these raw values directly to a project using S5 representation.
This submodule has no individual PROFIBUS address or PROFINET port; communication is handled by the station's interface. The data sheet lists no module-specific diagnostics, alarms or configurable substitute values. Fault checks should compare the project command, selected range, supply and voltage measured at the load.
Editor's Note: Start by checking S+ and S−. Connecting only the QV terminals while leaving the sense connections open is incorrect. Next, verify the configured range: a zero PLC value does not mean 0 V when 1–5 V is selected. When selecting a spare, keep the 1FA00 voltage model distinct from the 1GA00 current model.
Manuals and related topics
For wiring diagrams, visit Siemens ET 200 manuals and PDF documents. References: Siemens 6ES7124-1FA00-0AB0 Data Sheet, 15 August 2019; ET 200L / ET 200L-SC / IM-SC manual, EWA 4NEB 780 6009-02c, particularly sections 11.17, 11.23 and 12.9.
ET 200 special output modules · HMI and operator panels · SCADA systems. Also check the scaling between the displayed percentage or engineering units and the PLC's raw output value.
Navigation: Siemens automation · SIMATIC S7 · Siemens ET 200 · OtomasyonAVM home