6ES7 122-1BB00-0AA0

Siemens 6ES7 122-1BB00-0AA0 – SIMATIC SC 2 DO 24 V DC / 0.5 A

The 6ES7 122-1BB00-0AA0 is a two-channel digital output module in the SIMATIC SC / Smart Connect family. It is used in ET 200L-SC and compatible IM-SC arrangements within the Siemens ET 200 range. Its 24 V DC transistor outputs are rated at 0.5 A per channel. It transfers on/off commands from the main PLC to suitable relays, solenoid valves or other DC loads.

Two-output SC electronic submodule

This product belongs to the ET 200 digital output range; it does not read sensor signals like a digital input module. It is neither a standalone PLC nor an S7-1200 SM 1222 card. The ordering description “8 pieces per packaging unit” refers to the manufacturer's pack quantity, not eight outputs on one module. Check the actual quantity offered in the product listing separately.

TB 16SC terminal block and installation

The electronics plugs into a TB 16SC terminal block and occupies one of its eight SC slots. Dimensions are 10 × 64 × 51 mm in width, height and depth order, with an approximate weight of 15 g. The manual lists the screw-terminal 6ES7 120-0AH01-0AA0 and spring-terminal 6ES7 120-0BH01-0AA0 TB 16SC versions.

Check the station connections, SC bus arrangement and accessories together. Terminal blocks and electronic modules from different ET 200 subfamilies are not automatically interchangeable. For this DC module, the terminal block's coding slide must be in the upper DC position.

Output terminals and load supply

The manual assigns 1: Q channel 0, 3: M; 2: Q channel 1, 4: M. In the position A example, the first load connects across A1–A3, and the second across A2–A4. Terminal letters change with the installed slot; follow the markings for the actual module position.

L+ and M are supplied through the terminal block's relevant 1L+/1M and 2L+/2M supply groups. When checking the 24 V DC power supply and power distribution, verify polarity before energizing: Siemens warns that reversing these supply connections can activate connected actuators.

Channel current and temperature limits

For horizontal installation, the combined current of both outputs is limited to 1 A up to 40 °C and 0.8 A up to 60 °C. At 60 °C, both channels therefore cannot simultaneously carry 0.5 A. Assess the module total and enclosure temperature as well as each channel's current.

Consumption from L+, excluding load current, is a maximum of 3 mA; typical module power loss is 0.4 W. The active output voltage is at least L+ − 0.5 V, while off-state residual current can reach 0.3 mA. With low-current electronic loads, do not assume that an inactive output carries absolutely no current.

Load type and switching frequency

Maximum switching frequency is 100 Hz for resistive loads. For DC-13 inductive loads, the limits are 2 Hz at 0.3 A and 0.5 Hz at 0.5 A. Lamp-load limits are 2.5 W and 1 Hz. The resistive-load frequency must therefore not be applied directly to a solenoid coil.

With a resistive load, maximum output delays are 200 µs when switching on and 1.3 ms when switching off. Connecting L+ through a mechanical contact can also produce a brief output pulse: the manual specifies 8–20 µs, depending on load current. Consider this characteristic when the receiving equipment responds to very short pulses.

Status LEDs and troubleshooting

Each channel has a green status LED indicating the system output state; it does not independently prove that the load is powered. The module has no dedicated alarms or diagnostic functions. Outputs have electronic short-circuit protection, but switching back on at full load after a short circuit is not guaranteed. After correcting the fault, consult the manual's recovery conditions.

This submodule has no individual PROFIBUS address or PROFINET port; communication is handled by the station's interface. Compare the PLC command, load supply and voltage measured at the load when investigating an output fault.

Editor's Note: Keep two distinctions in mind: an eight-piece pack does not mean eight channels, and a 0.5 A channel rating does not permit a 1 A module total at every temperature. When selecting a spare, check the complete order number, terminal block and actual load current together.

Manuals and related topics

For wiring diagrams, visit Siemens ET 200 manuals and PDF documents. References: Siemens 6ES7122-1BB00-0AA0 Data Sheet, 2017; ET 200L / ET 200L-SC / IM-SC manual, EWA 4NEB 780 6009-02c, particularly sections 3.5, 7.4 and 10.2.