6ES7 142-1BD40-0XB0
Siemens Main Menu | SIMATIC S7 | Siemens ET 200 | PDF Manuals
6ES7 142-1BD40-0XB0 - Siemens SIMATIC DP ET 200X EM 142 Digital Output Module
Series: SIMATIC DP ET 200X
Product type: EM 142 expansion module; 4 digital outputs, 24 V DC / 2 A
Order number: 6ES7142-1BD40-0XB0
6ES7 142-1BD40-0XB0 is a four-channel EM 142 digital-output expansion module for ET 200X stations in the Siemens ET 200 distributed I/O family. Each channel is rated for a 24 V DC, 2 A output and can operate field loads such as solenoid valves, DC contactors and indicator lamps under a SIMATIC S7 automation system.
ET 200X expansion module: not a standalone station
This product is an ET 200X expansion module, not a basic module. Communication, station addressing and the main supply arrangement are provided through the attached basic module. It cannot directly replace mechanically different ET 200S, ET 200pro or ET 200eco products elsewhere in the Siemens ET 200 system architecture, even if their channel descriptions look similar.
The manufacturer manual lists specific hardware revisions for BM 141 DI, BM 141 ECOFAST, BM 141 ECOFAST DIAG, BM 142 DO, BM 143-DESINA FO/RS485 and BM 147/CPU basic modules. Older units such as 6ES7141-1BF01-0XB0 and 6ES7142-1BD11-0XB0 have minimum product-version requirements. Do not accept a generic “ET 200X compatible” description without reading the label and hardware revision.
Key technical specifications
Digital outputs: 4.
Rated load voltage: 24 V DC, 2L+.
Rated output current: 2 A per channel; permissible range 6 mA-2.4 A.
Total output current: 6 A maximum up to 20 °C and 4 A maximum up to 55 °C.
Short-circuit protection: electronic; typical response threshold 3.5 A.
Lamp load: 10 W maximum per channel.
Load resistance: 12 Ω-4 kΩ.
Switching frequency: 100 Hz with resistive, 0.5 Hz with inductive and 1 Hz with lamp loads.
Cable length: 30 m maximum, unshielded.
Power loss: typically 2.5 W.
Degree of protection: IP65/IP66/IP67 when correctly assembled and capped; the product data sheet specifies IP66/67.
Dimensions: 87 × 110 × 55 mm; electronic-module body width 60 mm.
Weight: approximately 250 g.
A 2 A channel rating does not mean that all four channels can supply a total of 8 A simultaneously. Module total is limited to 6 A or 4 A depending on temperature. When comparing ET 200 digital output modules, check simultaneous load and ambient temperature as well as the per-channel figure.
What the four M12 sockets actually carry
On M12 sockets X1-X4, pin 3 is load-supply ground 2M and pin 5 is protective earth PE. The signal arrangement is X1 pin 4 = Q0; X1 pin 2 or X2 pin 4 = Q1; X3 pin 4 = Q2; X3 pin 2 or X4 pin 4 = Q3. The alternate physical points for Q1 and Q3 do not create two extra output channels.
Use Q1 through either X1 or X2, and Q3 through either X3 or X4. Do not connect loads to both alternative sockets of the same channel. This matters when selecting ET 200 connection modules and connectors or moving an existing cable set. Every unused M12 port requires the correct screw cap before the stated IP protection can be assumed.
Diagnostics and CPU STOP behavior
The module can report wire break, short circuit to M and short circuit to L+ channel by channel. These diagnostics and the diagnostic interrupt are parameterizable, however, and are disabled by default. Wire-break detection is triggered below approximately 6 mA only when the corresponding channel is enabled. Green LEDs show output state and the red SF LED indicates a group fault.
For CPU STOP, each channel can be configured to output a substitute value, hold the last value or switch to a de-energized state. The default is no current or voltage. Holding the last value can leave a moving or heating load energized, so it should not be selected without an explicit process and maintenance risk review.
Six field checks for selection and commissioning
1. Derate total current for temperature. The module total is 6 A at 20 °C but only 4 A at 55 °C. Four simultaneous 2 A loads exceed the specified limit. Include coil inrush, simultaneity and the real field temperature in the calculation.
2. Verify 2L+ and 2M load power independently. Working electronics and bus communication do not prove that load power is healthy. Check voltage drop, protection, conductor size and station total current together with the ET 200 power supply arrangement and ET 200 power distribution architecture.
3. Do not parallel outputs to increase current. Parallel wiring for performance increase is not permitted. Redundant load control using outputs in the same group is possible, but its protection and control logic must be engineered separately.
4. Match the basic module and project record. EM 142 is not a PROFIBUS device by itself. Station address, GSD/HW Config selection and network diagnostics belong to the basic module. Check the exact basic-module order number against the ET 200 PROFIBUS interface and network architecture.
5. Do not treat an LED as proof of movement. A green output LED shows the PLC command, not that a contactor has pulled in or a valve has moved. Return an auxiliary contact, pressure switch or limit sensor through the ET 200 field connection arrangement for critical loads.
6. Do not use a standard output as a safety output. 6ES7142-1BD40-0XB0 is not an F-DQ or PROFIsafe module. Emergency-stop and guard-door functions require appropriate ET 200 safety modules and a correctly engineered safe energy-isolation architecture.
Used-unit inspection
Read the 0XB0 suffix and hardware revision from the label; do not substitute a 0XA0 version on appearance alone. Inspect all four M12 threads, seals, side backplane contacts, housing latch and protective caps. Test every channel under 2L+ load, then enable and verify wire-break, short-to-M, short-to-L+ and SF diagnostics in the project. Missing caps and connectors can be completed from the ET 200 supplementary modules and accessories. Send clear photographs of the label, basic module and sockets through the Otomasyon AVM Siemens contact page for a more reliable compatibility check.
Editor’s note
Two details are easy to misread on this model. First, 4 × 2 A does not mean an unrestricted 8 A module total; the total falls to 4 A at the high-temperature limit. Second, four M12 sockets are not four completely independent signal arrangements. Q1 and Q3 are presented at alternative sockets and the same channel must not be used through both points. On a used unit, missing caps and damaged seals are not cosmetic defects; they directly compromise field protection.
PDF manuals and documentation
Consult ET 200X Distributed I/O Device, Edition 02/2003, EWA 4NEB 780601602-06 and the exact 6ES7142-1BD40-0XB0 data sheet on the Siemens ET 200 PDF manuals page. Manual section 7.14 covers socket pinout, parameters, CPU STOP behavior and electrical data; section 5.4 covers channel diagnostics. This page is selection guidance; use the device label, basic-module hardware revision, installed project and manufacturer manual as the final authority for wiring and commissioning.
Related topics and Siemens navigation
Digital output modules | Connection modules | Power supply modules
Power distribution modules | PROFIBUS and PROFINET | ET 200 system architecture