6ES7 138-4CB00-0AB0
Siemens 6ES7 138-4CB00-0AB0 – ET 200S PM-E Power Module
Siemens 6ES7 138-4CB00-0AB0 is a PM-E power module for ET 200S within the SIMATIC ET 200 family. It distributes and monitors the load supply for the associated group of electronic modules. Diagnostic and fuse functions support investigation of supply-related problems within the station.
What the PM-E module does
The PM-E transfers an externally supplied voltage to the relevant ET 200S module group. It does not convert 230 V AC into 24 V DC. The required voltage must come from a suitable external power supply or supply circuit.
A machine may, for example, require a separate supply group for selected outputs. The PM-E and its suitable terminal module form part of that distribution arrangement. The PLC program and the availability of load power are separate matters: the controller can remain operational while one load group has lost its supply.
AC and DC voltage ranges
Siemens lists this order number as PM-E DC24..48V/AC24..230V. Its DC application range is therefore identified as 24–48 V DC, and its AC range as 24–230 V AC. The abbreviated “UC 24–230 V” wording found in older product descriptions should not, by itself, be used to justify operation at 230 V DC.
The PM-E’s support for different supply types does not mean that every downstream electronic module can operate at every voltage. The requirements of the digital input modules and digital output modules in the group must match the applied supply.
How a potential group is formed
In ET 200S, the TM-P terminal module carrying the power module starts a new potential group. The relevant sensor and load supplies for downstream electronic modules are distributed through that group. A subsequent TM-P separates the P1/P2 power buses and starts another group.
This arrangement allows station supplies to be divided according to the application. Separating supply groups is not equivalent to implementing a safety shutdown. A standard PM-E does not become a PROFIsafe power module simply because it includes diagnostics and a fuse.
Terminal module and connection compatibility
The PM-E plugs into a suitable terminal module, which provides the field wiring and potential distribution. Record the existing TM-P order number alongside the power-module code.
Selection should account for the terminal connection method, AUX bus arrangement and suitability for the load voltage. Similar-looking connection components do not necessarily provide the same electrical distribution. Also check whether the terminal module is included in the proposed supply.
Diagnostics and fuse function
Assess load-supply availability and fuse condition together. If several I/O modules in one group show problems simultaneously, checking the common supply path can be more useful than treating every electronic module as a separate failure.
If a fuse has opened, investigate short circuits, excessive load or wiring faults before replacing it. Select the replacement fuse type and rating from the applicable product documentation. The word “backup” appearing in some older English listings should not be interpreted as a battery-backup or UPS function.
Replacing CB00 with CB11
Siemens provides a specific replacement note in the manual for 6ES7 138-4CB11-0AB0: AC applications require an updated hardware configuration with the “Voltage type” parameter set to “AC”. CB11 defaults to DC, allowing direct replacement in DC applications with respect to this parameter.
For an AC-powered station, fitting the replacement while retaining the old configuration is therefore insufficient. Check the new order number, actual load voltage and project parameters together. Physical compatibility does not establish configuration compatibility.
Load calculation and system communication
Calculate the combined demand of the group’s electronic modules, sensors and output loads. The capacity of the DIN rail power supply does not replace the need to check the current permitted through the terminal and power module. Do not apply CB10 or CB11 current-rating tables to CB00 without confirming their applicability.
The PM-E is not a network interface. The station’s PROFIBUS or PROFINET connection is provided by its interface module. Working communication does not establish that every load group has power.
Maintenance and spare-parts preparation
Before replacement, record the PM-E and TM-P labels, supply type, downstream modules and existing project settings. Review messages on an HMI panel or SCADA system alongside PLC diagnostics and the actual field-supply condition.
The description “ET 200S power module” is not enough to select a replacement. Match the complete 6ES7 138-4CB00-0AB0 order number, AC/DC supply arrangement and terminal configuration.
Manuals and related topics
For station architecture and supply groups, consult the ET 200S documents available through our Siemens ET 200 manuals and PDF documentation page. When moving to CB11, also review the explicit CB00 replacement note in the new module’s manual.
Related topics: About Siemens ET 200 | PROFIBUS FAQ
Editor’s note: The load supply’s AC or DC type is a key selection detail for this model. When replacing CB00 with another order number, check the hardware configuration as well as terminal compatibility.
Navigation: Siemens products | Siemens S7 PLC | SIMATIC S7 | ET 200 products