6ES7 193-7CA00-0AA0
6ES7 193-7CA00-0AA0 — ET 200iSP TM-EM/EM 60S Terminal Module
6ES7 193-7CA00-0AA0 is the TM-EM/EM 60S terminal module for ET 200iSP in the Siemens SIMATIC product range. It provides the base for two electronic modules and the connection points for field wiring. It has blue screw terminals; the fitted electronic modules perform the measurement or control functions.
Within the Siemens ET 200 distributed I/O range, this part belongs specifically to ET 200iSP. It must not be confused with ET 200S or ET 200SP bases. Two module slots do not mean two signal channels: channel count and signal type depend on the electronic modules selected.
Technical design and application
Order number: 6ES7193-7CA00-0AA0. Type: TM-EM/EM 60S. Capacity: 2 electronic modules. Connection: screw terminals. Terminal colour: blue. Dimensions: 60 × 190 × 52 mm (width × height × depth).
The base connects compatible electronic modules to field wiring. When selecting Siemens PLCs and accessories, check the complete order numbers of both electronic modules as well as the terminal base. Communication with a SIMATIC S7 control system takes place through the station's interface module; this base is not a communication interface in its own right.
How the similar order numbers differ
6ES7193-7CA10-0AA0 is the TM-EM/EM 60C version with spring terminals. 6ES7193-7CA20-0AA0 has black terminals for identifying non-intrinsically safe signals in non-hazardous areas. 6ES7193-7CB00-0AA0 is the TM-RM/RM base for relay modules. These parts must not be treated as direct equivalents; in particular, do not select 7CA00 for a 2 DO relay module.
Five selection and maintenance checks
1. System family: Confirm that the existing station is ET 200iSP. The ET 200 system overview helps distinguish terminal bases, electronic modules and interface modules.
2. Electronic modules: Match the modules intended for both slots against the Siemens compatibility table. Physical dimensions alone are not sufficient to establish suitability.
3. Terminal assignments: Read terminal functions from the wiring diagram for the electronic module being fitted. Follow its installation instructions for conductor size, stripping length and screw tightening torque.
4. Hazardous-area application: Blue terminals alone do not establish installation compliance. Area classification, equipment markings, enclosure requirements and intrinsically safe circuit conditions must be assessed together. For an industrial automation installation, selecting the base completes only part of that assessment.
5. Mechanical condition: Inspect screws, terminal housings, module latches and contacts joining adjacent bases, particularly on used or spare parts. Do not disregard cracked housings or damaged contacts.
Interpreting a fault
If a channel fails, assess the field wiring, electronic module and terminal base separately. Review diagnostics from the PLC and control equipment. An alarm on an HMI operator panel or SCADA monitoring system does not by itself prove that the base has failed. Follow the site's isolation and hazardous-area maintenance procedures before intervention.
Editor's note: The key question is which two electronic modules will be fitted. “ET 200 base” is not a sufficient ordering description. Check the complete part number, terminal type and intended location together; the blue and black terminal versions differ in intended application, not merely appearance.
Manuals and PDF documentation
Visit the Siemens ET 200 manuals and PDF links page for system documentation. For this product, use the ET 200iSP terminal-module section together with the module compatibility table and the wiring diagram for the electronic module being installed.