6ES7 138-7EA01-0AA0

Siemens 6ES7138-7EA01-0AA0 ET 200iSP 24 V DC Power Supply

6ES7138-7EA01-0AA0 is a PS DC24V power supply module for SIMATIC ET 200iSP stations. Part of the Siemens industrial automation range, it powers the station's power bus, interface module and backplane bus. It converts an external 24 V DC supply into the galvanically isolated, intrinsically safe voltages required by ET 200iSP.

Within the Siemens ET 200 distributed I/O family, ET 200iSP supports hazardous-area applications. When selecting this power supply for process and industrial automation applications, assess the terminal base, product version, station load and Ex installation conditions together.

Supply requirements and capacity assessment

The nominal input is 24 V DC, with a specified maximum input current of 4 A from L+. In PLC-based control systems, select the external supply, cables and protective devices according to Siemens wiring requirements. Recalculate total consumption when adding modules; an available slot alone does not establish sufficient power capacity.

Five checks before selection or replacement

1. Terminal base and product version: Bases 6ES7193-7DA10-0AA0 / 6ES7193-7DB10-0AA0 accept all product versions of PS DC24V. UC bases 6ES7193-7DA20-0AA0 / 6ES7193-7DB20-0AA0 require power supply product version 7 or later. When reviewing ET 200 system architecture and module compatibility, record the version on the label alongside the complete order number.

2. Single or redundant supply: Two power supplies can form a redundant arrangement using suitable TM-PS-A and TM-PS-B bases. When assessing supply redundancy in SIMATIC S7 control systems, check the IM version and the project's redundancy settings. Plan the station load so that either power supply can carry it alone if the other becomes unavailable.

3. Cabinet temperature and installation: The data sheet specifies a typical power loss of 20 W. Include this heat dissipation in cabinet thermal calculations for Siemens PLC and I/O products. Check permissible output current, ambient temperature and mounting orientation against the documentation for the installed product version; earlier and later versions can have different temperature limits.

4. Diagnostics and maintenance records: Power supply diagnostic information can be read through IM 152. Review station faults displayed on HMI operator panels together with the interface module's diagnostic record. Distinguish supply interruptions, communication problems and individual I/O channel faults. Record the event time and affected modules to help locate the cause.

5. Ex enclosure and removal conditions: Siemens product information requires an Ex e enclosure for Zone 1 and a suitable enclosure meeting the applicable Ex requirements with at least IP54 protection for Zone 2. In potentially explosive atmospheres, wait at least 2 minutes after unlocking the power supply before withdrawing it. Apply this waiting period together with all other manufacturer installation and operating conditions. Qualified personnel must perform enclosure and connection work.

PDF manuals and technical documents

Visit the Siemens ET 200 PDF manuals page. In the ET 200iSP manual, 11/2022, A5E00247483-AK, Section 11.1 covers the power supply, 10.2 terminal compatibility and 4.12 supply redundancy. Also consult the model-specific A5E41370612-AC product information. Share photographs of the label and terminal base through Siemens product technical enquiries.

Editor's note: The 4 A figure describes maximum input current; 20 W describes typical power loss. Neither figure specifies output capacity. For capacity calculations, compare connected module consumption with the power supply's output limits for its product version and operating temperature.