6ES7 138-4DB00-0AB0

Siemens main menu › Siemens S7 family › ET 200 › Function modules

6ES7 138-4DB00-0AB0 — Siemens ET 200S 1SSI Absolute Encoder Interface Module

6ES7 138-4DB00-0AB0 is a 1SSI absolute encoder interface module for the Siemens ET 200S family. It transfers SSI encoder position data to the PLC. Among the ET 200 function modules, its catalogue designation is 1 SSI 25 bit / 1 MHz, with a width of 15 mm.

Application

Use it to read position from an SSI absolute encoder. Its connection method differs from ET 200 counter modules that process incremental A/B pulses. The additional digital input serves functions such as capturing a position on a trigger; it is not a replacement for standard digital input modules.

Key technical data

Encoders: 1. SSI telegram lengths: 13, 21 or 25 bits. Coding: Binary or Gray. Supply: 24 V DC; permitted range 20.4–28.8 V DC. Electronics module dimensions: 15 × 81 × 52 mm. Digital inputs: 1. A comparison-value function is provided.

Five checks before selection or replacement

1. Encoder telegram: Compare the encoder label and data sheet with the configured bit length. The specified 13, 21 and 25-bit options do not mean that every length from 13 to 25 bits is supported by this revision. Match the coding selection as well.

2. Interface and product release: When selecting ET 200 communication interfaces, check more than the order number. The Siemens manual for IM151-1 High Feature 6ES7151-1BA02-0AB0 lists 6ES7138-4DB00-0AB0 up to and including product version 3 as incompatible. Do not extend this restriction to every 1SSI revision.

3. Terminal base and cabling: Record the ET 200S terminal base order number. Check clock and data pairs against the wiring diagram; shielding and pair arrangement also matter for encoder connection components. Assess cable length together with the selected SSI clock frequency.

4. Supply compatibility: Check the ET 200S power supply modules and encoder voltage requirements. Verify reference and supply connections within the station power distribution. An SSI interface does not by itself specify the encoder’s supply voltage.

5. Interpreting the PLC value: In positioning applications, distinguish the raw encoder value from the machine’s engineering units. Record scaling, zero offset, direction and comparison settings before replacement. Then check readings at several known mechanical positions.

Replacement with 4DB03

Siemens manual A5E00124867-07 identifies 6ES7138-4DB03-0AB0 as a compatible replacement for 4DB00. This does not mean that every additional feature of the newer revision exists in 4DB00. Use the existing hardware configuration and parameters as the basis for replacement.

Editor’s note

A plausible position reading does not prove that every setting is correct. An incorrect bit length or coding selection may produce believable values at some positions and jumps elsewhere. When selecting a spare, request a label photograph showing both the complete order number and the product release.

PDF documentation and references

Use the Siemens ET 200 PDF and user manual page. Read the 4DB00 data sheet, A5E01075975-02, page 8 for the interface restriction, and ET 200S Technological Functions, A5E00124867-07, section 4.1 for replacement information. The latter document’s 1SSI chapter describes 4DB03.

Related topics

Terminal bases • Connection modules • Digital inputs • Digital outputs • Power distribution • Additional modules