6GK1 901-0FB00-0AA0
Siemens 6GK1901-0FB00-0AA0 PROFIBUS POF Simplex Connector and Polishing Set
6GK1901-0FB00-0AA0 is a termination package containing 100 Simplex connectors and 5 polishing sets for PROFIBUS plastic fiber-optic cables. Siemens identifies it as PB Simplex Plug POF. Within the range of Siemens industrial automation products, it provides cable-end components for compatible optical interfaces.
When preparing fiber connections for industrial automation applications, check both the cable construction and the device socket. This package is intended for POF, or plastic optical fiber. Do not select it for PCF or glass fiber based on appearance alone; those cable types can require different connectors and termination equipment.
Application within ET 200 systems
Siemens lists this order number among the accessories for the ET 200S IM151-1 FO STANDARD interface module. It is therefore relevant when selecting Siemens ET 200 products for stations using optical PROFIBUS DP connections. As ET 200 interfaces use different connection technologies, review the ET 200 system architecture alongside the exact interface module installed.
In SIMATIC S7 control systems, the communication interface determines the connector requirement more directly than the CPU family. The 6ES7195-1BE00-0XA0 connector adapter used for the IM151-1 FO connection is a separate order item. Do not assume that adapters are included with this 100-connector package.
Technical details and five selection checks
1. Cable compatibility: This is a Simplex crimp connector for plastic-clad POF cable. When selecting accessories for Siemens PLC products, check the cable and port documentation; the description “fiber optic” alone does not establish compatibility.
2. Connector quantity: One Simplex connector terminates one fiber end. A two-fiber connection uses two connectors at the device end, one for transmission and one for reception. Consequently, 100 connectors do not represent 100 completed duplex cables.
3. Communication rate: The Siemens data sheet specifies 9.6 kbit/s to 12 Mbit/s for PROFIBUS. Actual network speed and permitted distance depend on the connected devices and cable; this passive accessory does not independently increase either value.
4. Mechanical design: The connector has a plastic housing, a 180° cable outlet and IP20 protection. Route the cable without tensile loading and observe the cable manufacturer's minimum bend radius.
5. End preparation: Follow the relevant assembly instructions for cutting, stripping, crimping and polishing. Before commissioning PLC-based control applications, useful checks include clean fiber ends, correctly seated adapters and the transmitter-to-receiver connection direction.
Practical maintenance checks
When investigating a station communication alarm displayed on HMI operator panels, also check the interface module's power supply and diagnostic indicators. Inspect the fiber ends, connection direction and adapter seating before assuming that replacing a connector will resolve the fault.
Use the relevant system documentation available through the Siemens ET 200 PDF manuals page. The optical PROFIBUS DP wiring section of the ET 200S operating instructions and the IM151-1 FO STANDARD device manual are particularly relevant. For component matching, provide the interface module code, cable markings and existing adapter details through Siemens product technical enquiries.
Editor's note: Start with the cable type, then confirm the device's optical port and any adapter requirement. Distinguishing POF from PCF early and counting Simplex connectors per fiber end helps prevent incorrect or incomplete maintenance orders.
Related topics and Siemens navigation
Product families
Siemens main menu |
Siemens PLC products |
SIMATIC S7
ET 200 resources
ET 200 products |
ET 200 system overview |
ET 200 PDF manuals
Control and assistance
HMI operator panels |
SCADA systems |
Siemens product enquiries