6ES5 943-7UA22

Siemens 6ES5 943-7UA22 – S5-115U CPU 943, 16 KB RAM, Two TTY Connections

Siemens 6ES5 943-7UA22 is the CPU 943 central processing unit for S5-115U in the SIMATIC S5 family. It provides 16 KB of internal RAM and two TTY serial connections. Within an S5 system, it executes STEP 5 programs and works with the installed I/O modules and suitable PG/OP connections.

The Siemens technical table for this exact reference specifies typically 0.65 A from the internal 5 V supply. Assess additional module and connected-device loads separately when checking the S5-115U power supply and rack connections. Record voltage measurements separately from program-execution and communication tests.

Internal RAM and removable memory

The CPU 943 specification lists 8192 instructions of internal memory; the comparison table gives 16 × 1024 bytes of RAM. Assess the installed memory submodule separately by type and capacity. Internal RAM and total capacity available with an external module are different specifications.

For memory options such as 6ES5 375-0LA21 and 6ES5 375-0LA41, check the complete reference, capacity and applicable CPU scope. Distinguish EPROM, EEPROM and RAM. Compare an older submodule’s contents with the current machine backup before replacement.

Using the two serial connections

Record cables and connected devices separately for SI1 and SI2. On an installation using an older programmer such as the PG 615, or an operator panel, establish each connection’s role from the machine arrangement. Connector shape alone does not establish electrical suitability.

The Siemens manual explains that some PG/OP requests can block one another when SI1 and SI2 are used concurrently. For “AS-Funktion gesperrt: laufende Funktion”, inspect the operation running on the other connection as well. Include active operations in the interface and connection checks before continuing to change cables.

Hardware and software requirements for SI2

Table 4.2 permits compression, overall reset and writing blocks to the PLC through SI2 from CPU 943-7UA22 hardware version 5 and system-software version Z06. Check revision information alongside the complete order number.

Being able to read a program through a connection does not establish that every write or erase function is available there. Identify the PG function required for the work and back up the existing program and data blocks before intervention.

Distinguishing other CPU 943 references

Do not automatically treat 6ES5 943-7UA11, 6ES5 943-7UA21, 6ES5 943-7UB11 or 6ES5 943-7UB21 as interchangeable with 7UA22. Establish memory, connection count and system-software scope for each complete reference.

Likewise, do not transfer specifications for CPU 944, version 7UA22 directly to CPU 943. Similar appearance or two connections does not make every instruction-processing or communication capability identical.

Peripheral checks and commissioning

Check digital-input, digital-output and analog-module addresses against the existing project. Match programmed addresses to installed hardware and use diagnostic records to distinguish CPU, memory, supply and peripheral-connection faults.

After replacement, verify PG access, the operator panel, the second connection in use and the machine’s normal operating sequence in addition to the RUN indication.

Editor’s Note

Obtain clear photographs of the 943-7UA22 reference and revision information. With used Siemens CPUs, a “943, two ports” description does not identify the actual version being supplied.

Successful reading through one connection is only a partial check. Verify the revision-dependent SI2 functions specifically; reading a program and loading one are different tests.

When a panel and programmer are connected simultaneously, allow for one operation blocking another. A busy connection need not indicate a failed board. Record the active operation and the port used.

Back up the program and data blocks before removing a memory submodule. An old EPROM may not contain the machine’s current program. Check that replacement will not restore an outdated application.

In Siemens S5 maintenance, use the correct rack, a sound supply and suitable connections for meaningful testing. Ask which functions were checked on each serial connection, and distinguish completed tests from assumptions.

OtomasyonAVM resources and PDFs

Start with the 6ES5 943-7UA22 product page, S5 memory cards and the SIMATIC S5 overview. Use the OtomasyonAVM S5 PDF archive to locate relevant documentation. The German S5-115U A-CPU manual includes the exact 7UA22 reference. Printed page 2-16 compares memory, 4-5–4-6 describe SI2 functions and revision requirements, and 15-15 gives technical specifications. The PDF itself is in German.

Related topics

+ 943-7UA11 · 943-7UA21 · 943-7UB11 · 943-7UB21 · 944-7UA22

Browse SIMATIC S5

+ SIMATIC S5 · Siemens S5 PLC · S5 racks · Used Siemens overview

Siemens and external references

Siemens S5-115U A-CPU Handbuch — GWA 4NEB 811 6000-01b, German