6ES5 788-8MK11
Siemens 6ES5 788-8MK11 — S5-90U Digital Input Simulator
Siemens 6ES5 788-8MK11 is a digital input simulator for the S5-90U PLC in the SIMATIC S5 family. It provides eight maintained switches and two momentary pushbuttons for manually setting ten input states during bench testing and program checks.
It helps examine how the program responds to a sensor, limit switch or control pushbutton without waiting for the corresponding machine event. For example, a position signal can remain active while a brief start command is applied. The actual field device and its wiring still require their own checks.
Input assignments
The eight maintained switches correspond to I32.0–I32.7; the momentary pushbuttons correspond to I33.0 and I33.1. German STEP 5 notation uses E instead of I. The system manual identifies 33.0 as the interrupt input and 33.1 as the counter input; their use depends on the PLC program and required configuration.
When checking S5 digital inputs, establish the address mapping first. Operate a switch, observe the associated input LED and monitor the same bit in the software. Following the PLC input and output signal path in this order helps distinguish an address mistake from a hardware problem.
Connection to the front terminals
With the PLC supply disconnected, insert the simulator into the S5-90U input terminals and secure its contacts with the terminal screws. Check the S5 connections and S5 supply arrangement before restoring power. Do not force bent contacts into the terminals.
The manufacturer’s S5-90U connection drawing identifies the inputs as 24 V DC. Follow the system diagram when checking the power supply and terminal assignments. A moving switch alone does not establish that the PLC CPU is executing the program correctly.
Monitoring the program in STEP 5
During PLC programming, the CPU executes the program while this accessory supplies manually selected input conditions. Siemens demonstrates the simulator with the STEP 5 Block status and Status variable functions. Use the programming software to follow the physical input into the program.
For a ladder diagram or instruction list test, write down the expected response to each input combination before operating the switches. Although PLC programming languages present the logic differently, the test still compares an applied condition with an expected result. Back up an existing machine program before changing it.
During PLC debugging, an input that changes without the expected result calls for a check of the logic conditions and address selection. A digital output LED changing state and a field load operating are separate observations. A bench simulation does not complete the load test.
Difference from the 788-8MA11
The 788-8MK11 connects to the S5-90U front inputs. The 6ES5 788-8MA11 is a different simulator module, installed in a bus unit for eight input or eight output signals. When selecting S5 accessories, compare the complete order number and the connection method.
The system manual specifies S5-90U for direct installation of this simulator. The S5-90/95 label in the STEP 5 training diagram does not establish direct mechanical compatibility with another CPU. Check the terminal arrangement of the actual controller.
Editor’s Note
When buying a used PLC accessory, start with the contacts underneath. Ask for a close photograph of the terminal contact area; a clean top view will not reveal bent pins, oxidation or loose parts.
Test each maintained switch individually. Only its corresponding input should change. If two inputs move together, inspect for touching contacts. Keep the relay and control circuit separated from its loads while assessing the test arrangement.
Check both momentary pushbuttons separately. Each should operate when pressed and return when released. A sticking button can mislead the test. Manually operating the counter input does not verify high-frequency performance.
If an input does not respond, do not condemn the CPU immediately. Disconnect power, check the terminal screw and simulator contact, then compare the same address at the LED and in the software. Isolating the fault step by step avoids unnecessary replacements.
Record which switches remain on at the end of the test. Disconnect power before removal, restore the field wiring to its diagram and recheck the input states before operating the machine. A successful bench test does not establish that every machine condition has been verified.
OtomasyonAVM resources and PDFs
Browse the S5-90U family and S5 accessory pages for related hardware.
S5-90U PDF files and system manuals — Our archive page for installation, addressing and test documentation. The Siemens system and STEP 5 manuals used here are in English; the relevant manufacturer PDFs are linked below.
Related topics
+ S5 digital input/output modules
+ 6ES5 788-8MA11 simulator module
Browse SIMATIC S5
+ Siemens second-hand equipment
Siemens and external references
+ S5-90U/S5-95U System Manual — EWA 4NEB 812 6115-02b, §16.3.1–16.3.2, English
+ STEP 5 Version 6.6 — C79000-G8576-C820-01, §2.5.2–2.5.3, English