6ES5 482-8MA11

Siemens 6ES5 482-8MA11 – S5-100U 16-Input / 16-Output Module

Siemens 6ES5 482-8MA11 is a combined I/O module for the S5-100U, with 16 digital inputs at 24 V DC and 16 digital outputs at 24 V DC, in the SIMATIC S5 range. Within the S5 digital input/output module family, it collects sensor states and provides commands to field devices.

The outputs comprise eight 0.1 A channels and eight 0.5 A channels. Select each load according to its output group. Unlike a digital input-only or digital output-only module, this assembly requires checks in both signal directions.

Input signals and field power

The inputs read machine on/off states. When connecting sensors, inductive sensors or photoelectric sensors, check the output circuit, supply and common connections. Keep the difference between analogue and digital inputs in mind: these digital channels cannot be used to measure a 0–10 V or 4–20 mA process signal.

Measure the 24 V DC power supply under load and check for voltage drop in the L+ and M wiring. Distinguish the functions of the S5 power supply and field supply. If several inputs or outputs fail together, start with shared supply and return connections.

Output loads and front connector

Before connecting relay or valve coils, assess both steady current and pickup demand. Use a suitable intermediate driver where a load exceeds the channel rating, and check inductive-load suppression. If considering separate outputs, compare modules such as the 6ES5 441-8MA11 by channel count and load capacity; an output-only module does not provide the 482’s input function.

In the S5 cable and connector range, consult the 6ES5 490-8MB11 reference for screw-terminal wiring. When considering another front connector, such as the 6ES5 490-8MA11, compare the exact module number, termination method and contact arrangement. Photograph the input/output sides and wire numbers before removal.

Addressing and ET 200U operation

Siemens ET 200U tables explicitly list the 482-8MA11. It requires two input bytes and a separate two output bytes. For remote I/O, check the interface module and communications arrangement together. The configuration must match the ET 200U station and protocol in use.

Example: with input start I8 and output start Q16, the bits are I8.0–I9.7 and Q16.0–Q17.7. This is an ET 200U example with separately assigned start addresses, not a fixed local S5-100U slot address. Refer to the S5 PLC architecture and existing address list; during PLC troubleshooting, match each field signal to its program bit.

Revision and system compatibility

Do not treat 8MA11, 8MA12 and 8MA13 as one specification. Before replacing this module with a 6ES5 482-8MA12 or 6ES5 482-8MA13, compare output groups, wiring diagrams and CPU requirements. Record the exact processor number and version, including for a CPU 103; a shared family name alone does not establish replacement compatibility.

Editor’s Note

The two different output-current groups are easy to overlook. Before transferring the old wiring, write down which load uses each channel. Even a small coil’s pickup demand can affect the choice of output.

Do more than check the LEDs on a used module. Activate and read all 16 inputs individually, then test all 16 outputs with suitable loads within their ratings. An unloaded voltage reading does not establish correct operation under load.

If inputs work but outputs do not, leave program changes until you have checked the basics. Inspect field power, the M return and connector contacts. A working half of the module provides useful information for narrowing down the fault.

Deal with heat marks, loose screws, recessed contacts or damaged conductors at the front connector first. If the same channel fails again after changing the module, take another careful look at the wiring.

Before buying, obtain photographs of the 8MA11 label and front connector, plus a record of the channels tested. Online listings sometimes show another revision under this number. Confirm the actual item’s label and agree on everything included.

OtomasyonAVM resources and PDFs

+ S5 digital input/output modules and the SIMATIC S5 main directory: related modules and system pages.

+ OtomasyonAVM shared S5 PDF archive: check that the selected document covers the exact order number and system version.

Related topics

+ 482-8MA12 · 482-8MA13 · 441-8MA11 output module · 490-8MB11 screw connector. These are comparison references, not a list of direct replacements.

Browse SIMATIC S5

S5 input/output modules | S5 module directory | SIMATIC S5 | Siemens S5 PLC | Siemens second-hand main page

External references

+ Siemens ET 200U manual – English: EWA 4NEB 812 6087-02b, Edition 03; Tables 4-3 and 5-4, exact 482-8MA11 entry and address scope.

+ Siemens ET 200 Handheld manual – English: EWA 4NEB 812 6096-02b; printed pages 9-19 and 9-20, combined-module identifier and separate address length in each direction.

+ RS–Siemens cross-reference data sheet – March 1996: 021-108, page 2; 482-8MA11 channel/current groups and 490-8MB11 connector reference. Archived copy of an RS publication.