6ES5 390-5AA22

Siemens 6ES5 390-5AA22 SIMATIC S5 390 timer and counter module

The 6ES5 390-5AA22 is the 390-5 digital timer and counter module in the SIMATIC S5 special module family. It handles timing and down-counting in the S5-130A and S5-130K. The user program can start a timer, decrement a counter and check when the count reaches zero.

The Siemens ST 53 catalog lists 56 presettable timers and 8 count-up stopwatches. The timer bases are 0.01 / 0.1 / 1 s and the overall preset range is 0.01–999 s. The 16 down counters accept presets from 1 to 999. The catalog specifies a maximum counting frequency of 50 Hz. During fault diagnosis, trace the triggering digital input and the resulting digital output separately through the PLC program.

391 operator panel and presets

The enclosed 6ES5 391-5AA13 is the operator panel for the 390-5. It lets you select a timer or counter address, enter a preset and read the actual value. It can also display programmed fault messages as numbers. Siemens specifies a maximum panel connection length of 1.5 m. Match the S5 cable and connectors to the existing installation. Check the full panel order number when buying a spare. Similar-numbered panels such as the OP 393-II belong to a separate product family.

Rack and slot compatibility

The ST 53 installation tables specify slot 4 in the ZG 130A and slot 49 in the ZG 130K. Check the central unit label and slot number on the S5 rack. The catalog lists the PS 950-3AA51 as one rack power supply for the 130A. Siemens specifies that the 392-5 analog timer and the 390-5 cannot be used in the same system.

If the cabinet has several S5 expansion units, identify the central rack on the drawing. Parts such as the EG 182-3A and IM 300 EU help identify the expansion side. When checking interface modules, verify the terminating plug against the drawing if the installation uses an IM 310.

Other S5 timing and counting modules

Use the full order number to identify each module. Consult the model-specific wiring and addressing tables for the 380 timer, 385A, 385B, IP 240 and IP 242.

Editor’s note

1. Record the settings before removal. Back up the STEP 5 program. Record the addresses and presets shown on the 391 panel and the time bases used in the project. After qualified personnel isolate power, mark the slot number and panel cable.

2. Check the time base if the duration is off by a factor of 10 or 100. Compare the 0.01 / 0.1 / 1 s selection with the panel preset. A preset of 100 at 0.1 s, for example, gives 10 seconds. Compare that value with the duration measured under safe test conditions.

3. Start with a single trigger if the counter does not decrement. Use a known preset and verify that one controlled trigger to the program's count command reduces the value by one. Then check the signal the program expects when the count reaches zero.

4. Check the connection first if the panel shows no value. Have the 391-5AA13 order number, cable and sockets checked. If the connection is sound, verify timer or counter mode, the selected address and the actual-value display.

5. When buying used, ask about the board, panel and cable separately. Request photos of the 5AA22 label, rack connector and panel socket. Ask for a test record showing one timer completing its interval and one down counter reaching zero.

To offer a 390-5AA22 for sale, send the full order number, quantity, condition, label photo and asking price. Include details of the 391 panel and cable if available. Contact otomasyonavm@gmail.com.

Siemens PDF documentation

+ Siemens ST 53 order number and system compatibility, p. 9/2 (DE)

+ 390-5 specifications and 391 panel connection, p. 8/3 (DE)

+ ZG 130A slot and 391 panel, p. 2/7 (DE)

+ ZG 130K slot and 391 panel, p. 3/12 (DE)

+ OtomasyonAVM S5 PDF archive

Related topics

+ Siemens S5 PLC overview

+ SIMATIC S5 interface modules

Second-hand Siemens navigation

+ SIMATIC S5 special modules

+ SIMATIC S5

+ Second-hand Siemens