6ES5 385-8MB11

Siemens 6ES5 385-8MB11 – SIMATIC S5 385B High-Speed Counter Module

The Siemens 6ES5 385-8MB11 (385B) is a single-channel high-speed counter and position decoder. It accepts up to 500 kHz with 5 V differential RS-422 or 25 kHz with 24 V signals. In C mode it counts up from 0 to 65,535. In PD mode it tracks position in both directions from −32,768 to +32,767.

15-pin Sub-D and field connections

Position decoding uses A and B phases plus the R reference pulse. The 5 V differential pairs on the front connector are A/A− on 7/6, B/B− on 9/10 and R/R− on 11/12. For 24 V signals, A/B/R use pins 13/14/15 respectively. Counter mode uses only the A count signal. Check the encoder output and S5 cable pinout against Figure 15-8.

The bus unit has separate 24 V enable and reference inputs. Outputs Q0 and Q1 correspond to the two setpoints entered in STEP 5. When troubleshooting, check the signal type of a second-hand encoder and inspect the coupling if the machine uses a rotary encoder.

S5 and distributed I/O compatibility

The Siemens data sheet lists the S5-90U, S5-95U, S5-100U, ET 100U and ET 200U. On an S5-100U with a CPU 100, CPU 102 or CPU 103, verify the slot and peripheral address against the system manual. In an ET 200U station with an IM 318-B, the 385B is addressed as a two-channel analog module using four bytes. See section 9.6 of the ET 200U manual for DP Siemens and DP Standard identifiers.

Check the part number on the 8MA11 screw-terminal, 8MA21 crimp or 8MA22 EMC bus unit. Siemens specifies coding key 6 for the 385B. On multi-tier S5 installations, record any IM 315 or IM 316 connection along with the module address.

385A and other S5 modules

The 6ES5 385-8MA11 (385A) is a two-channel 500 Hz counter. The IP 240 1AA12 and IP 240 1AA21 are separate counting and position measurement modules. The IP 263 handles fast/slow positioning and the IP 265 handles high-speed subcontrol. To sell a 385B module, send photos of its label, front connector and switches to otomasyonavm@gmail.com.

Editor's note

Before removal, photograph the 8MB11 label and the C/PD and 5 V/24 V switch settings. Record the 1×, 2× or 4× resolution setting in PD mode.

Isolate the 24 V supply at the bus unit before connecting or removing the front plug. Verify the 5 V RS-422 and 24 V pins separately against the wiring diagram.

If pulses are missed, check the encoder output, signal frequency and shield connection to the metal connector shell. Open-collector sensors are incompatible with this input.

If the count runs in reverse in PD mode, check the A/B phase sequence, R pulse and external reference input.

During a controlled test, read the current count and diagnostic byte in the PLC. Then verify that Q0 and Q1 switch at the stored setpoints.

PDFs and Siemens documentation

+ Siemens 6ES5 385-8MB11 data sheet (EN)

+ Siemens S5-100U manual (EN) – Section 15.6, wiring and operating modes

+ Siemens S5-90U/95U manual (EN) – Section 16.6, 385B

+ Siemens ET 100U manual (EN) – Section 7.5, 385B

+ Siemens ET 200U manual (EN) – Section 9.6, 385B and addressing

+ Siemens S5 PDF archive

Related topics

+ S5 positioning modules

+ S5 interface modules

+ About Siemens S5 PLCs

Navigation

+ S5 special modules

+ SIMATIC S5 modules

+ Siemens S5 PLCs

+ Second-hand Siemens automation