6ES5 700-8MA22

Siemens 6ES5 700-8MA22 SIMATIC S5 crimp bus unit

The 6ES5 700-8MA22 is an enhanced-EMC bus unit that connects two plug-in I/O modules to the SIMATIC S5 serial backplane. Siemens documents the unit for expansion in the S5-90U, S5-95U and S5-100U families, including the CPU 103. The S5-90U connects to external I/O through the IM 90. Parts lists also cover ET 100U and ET 200U. For those stations, match the full bus-unit order number and hardware revision to the installed ET 100U interface or ET 200U interface.

Specifications and mounting

Two module positions, 10 terminals per slot, 0.5–1.5 mm² stranded conductors and 35 mm DIN rail mounting. The bus unit measures 91.5 × 135 × 39 mm (W × H × D) and weighs approximately 250 g. It draws a typical 1 mA from the CPU’s internal +9 V bus. Use the wiring diagram of the installed card for the field terminals. Pin assignments and mechanical coding can differ between digital input, digital output, analog I/O and combined digital I/O modules.

A ribbon cable connects each bus unit to its neighbor. The 8MA11 SIGUT and enhanced-EMC 8FA11 use screw terminals. The 8MA21 is an earlier crimp version. For a CPU 103 position that uses a hardware interrupt, refer to the 8MB21 crimp interrupt bus unit or 8MB11 screw-terminal interrupt bus unit configuration. ST 50 lists the 8MA22 as a standard bus unit.

For S5-95F, ST 50 lists the 8MA22 in both the safety-related and non-safety-related component tables. Follow the existing project and Siemens-approved configuration for a safety chain. The IM 316 F and standard IM 316 are distinct interfaces.

Where to start troubleshooting

If every card beyond one point drops out, inspect the bus unit that contains the first missing slot and its ribbon cable and plug connection to the unit on its left. If an entire tier is affected, check the S5 interface modules and the installed tier link, such as the IM 315. If only one field signal is missing, start with that channel’s crimp contact.

Editor’s note
1. Isolate the PLC and field power supplies. Verify that power is off, then photograph both module labels and the terminal numbers.
2. If the downstream chain drops out, inspect the ribbon plug at the first missing bus unit and the socket on its left. Check that the plug is seated and the ribbon is free of sharp folds and crushing.
3. If one channel drops out, inspect its crimp contact’s retaining spring. Tug the wire gently after insertion. If it pulls back, use the 6ES5 497-8MA11 extractor and fit the correct replacement contact.
4. If a card will not seat, compare the white rotary coding element with the number on the card. Do not force the card or cut off its coding key.
5. For a used unit, ask for close-ups of the 8MA22 label, both terminal blocks, the ribbon plug and the rail latch. Check the side hooks that keep adjacent bus units aligned.
6. During controlled recommissioning, verify both slots and the next card in the chain separately. This helps distinguish a single terminal fault from a break in the bus link.

Siemens manuals

S5-100U, specifications p. 14-11 (EN) · S5-90U/95U, specifications p. 15-7 (EN) · ST 50, ordering data p. 2/75 (EN)

SIMATIC S5 PDF archive

Related topics

Used Siemens equipment · S5 racks and bus units · SIMATIC S5 · Siemens S5 PLC · Used Siemens main page