6ES5 700-8MA21

Siemens 6ES5 700-8MA21 two-slot crimp bus unit

The 6ES5 700-8MA21 is a SIMATIC S5 bus unit with crimp snap-in contacts for two I/O modules. It belongs to the S5 mounting hardware range. Field wires terminate at the base, and a flat ribbon cable links adjacent units.

Slots, terminals and dimensions

The base has two I/O slots and 10 terminals per slot for 0.5–1.5 mm² stranded wire. It measures 91.5 × 135 × 39 mm (W × H × D), weighs about 250 g, and clips onto a 35 mm mounting rail.

System coverage

Siemens lists the exact 8MA21 code in the ET 100U and ET 200U manuals and in the older S5-100U CPU 100/102 manual. For S5-90U and S5-95U, see Figure C-8 in the joint system manual. For S5-95F, see Appendix A of its manual. Use the S5 CPU range to identify the controller fitted.

On an ET station, use the interface module nameplate to select the correct manual. The IM 318-8MA12 is an ET 100U interface, and the IM 318-8MB12 is an ET 200U example.

8MA11, 8MA22 and interrupt versions

The 8MA11 uses SIGUT screw terminals. The 8MA22 is the crimp version with enhanced EMC protection. The 8FA11 combines enhanced EMC protection with screw terminals. The 8MB11 and 8MB21 are separate S5-100U interrupt bus units. Match the nameplate, terminal block and wire ends when choosing a spare.

Wiring and troubleshooting

Terminal assignments depend on the fitted digital input, digital output, mixed I/O or analog module. Record its wiring diagram and terminal numbers before disturbing the existing S5 cables and connectors.

If several bases are affected, also check the S5 power supply and the station interface. The ET 100U manual lists the PS 930 and PS 931 as separate power supply options.

Editor’s note

1. Record the wiring first. Safely isolate power. Photograph both module order numbers, the mechanical coding settings and the wire positions at the terminals.

2. Follow the symptom. For one intermittent channel, check the crimp contact latch at that terminal. If adjacent bases drop offline together, inspect the ribbon cable between the last working base and the first affected one.

3. Release the contact with the proper tool. Use the 6ES5 497-8MA11 extractor to depress the retaining tang. Replace a bent or loose contact.

4. Check that the new contact locks. Crimp a 6XX3 070 contact with the proper tool. Once the tang engages, tug gently on the wire to check retention.

5. Read the coding number on the module. Set the base to match the number on the module front. If the module binds, recheck the coding and the seating.

6. Verify both slots in a safe test state. Compare the I/O addresses with the wiring drawings. Even after a single-channel fault, check both slots and the next base in the chain.

Manuals and PDF archive

See ET 100U page 2-9 for specifications and pages 3-30 and 3-31 for contact insertion and extraction. ET 200U page 8-13 lists the same order number. Siemens S5 PDF archive.