6ES5 265-8MA01

Siemens 6ES5 265-8MA01 IP 265 High-Speed Subcontrol Module

The 6ES5 265-8MA01 is the IP 265 high-speed subcontrol module for SIMATIC S5. Within the S5 function-module range, it runs its own program for fast counting, signal processing and time-critical outputs. The CPU exchanges commands, parameters and results through the S5 I/O bus.

Inputs, outputs and load supply

The 9-pin Sub-D INPUT connector provides eight 24 V DC inputs. Siemens specifies up to 10 kHz for these digital inputs. The 15-pin INTERFACE connector has three 5 V RS-422 differential inputs rated up to 58 kHz, with high and low pulses of at least 8.6 µs. The same connector can link a second IP 265. Expansion and differential input operation are separate modes. Match the connector and signal type when choosing a cable.

The 9-pin Sub-D OUTPUT connector provides eight 24 V DC outputs. These digital outputs use a separate 20–30 V DC load supply. At 60 °C, Siemens specifies 0.5 A per output and 2 A total. Identify the CPU bus 9 V logic feed and the separate load supply on the drawing. Use the full order number to select the wiring diagram, as with other input/output modules.

CPU compatibility and program loading

Siemens documents S5-90U, S5-95U and S5-100U with CPU 100 from 100-8MA02, CPU 102 from 102-8MA02 or CPU 103. Check slots 0–5 on S5-90U and 0–7 on S5-95U and S5-100U when mounting on the bus unit. For ET 200U, the manual specifies IM 318-B version 2 or later, Slow mode and loading from the memory submodule. Read the station interface version from its label.

Custom applications are built with COM 265. The 6ES5 840-4SH01 standard counter EPROM provides two separate 16-bit counters or one cascaded 32-bit counter. The 385-8MA11 and 385-8MB11 are dedicated counter modules. The IP 263 and IP 266 handle positioning, the IP 264 handles electronic cams and the IP 267 controls stepper motors. Match the existing program and wiring to the IP 265 when replacing the module.

Editor’s note

Check load power first if RUN is unavailable. Siemens requires 24 V DC load power at L+ and M before the IP 265 can enter RUN.

Identify the sensor signal before tracing a count fault. Check the wiring drawing for 24 V single-ended signals at INPUT and 5 V differential pairs at the appropriate INTERFACE pins.

Confirm the function of the 15-pin socket. Check whether the COM 265 project uses differential inputs or expansion to a second IP 265. Match the cable to that setting.

Record the program and memory before removal. Save the EPROM/EEPROM label details and the COM 265 project backup. Remove the memory submodule with CPU power off.

Include STOP behavior in the maintenance plan. The IP 265 can keep running during CPU STOP depending on configuration. Expansion outputs can retain their state when the IP 265 stops. Follow the plant isolation procedure before removal.

Ask which memory was used in a used-unit test. Request the CPU and memory details, confirmation that the module entered RUN, and the test results for the INPUT/OUTPUT connectors and an I/O channel.

To offer an IP 265 for sale, send photos of the label, front connectors and any memory submodule, together with the test status, to otomasyonavm@gmail.com.

PDF and wiring diagrams

+ IP 265 manual (English PDF) · Connectors in chapter 2, diagnostics in Appendix A, limits in Appendix B.

+ IP 265 standard counter manual (English PDF)

+ Shared S5 PDF archive