6ES5 374-0AA11
Siemens 6ES5 374-0AA11 SIMATIC S5 IP 252 DR/SR Memory Submodule
The Siemens 6ES5 374-0AA11 is a 374-series memory submodule for the X3 receptacle on the IP 252 closed-loop control module in SIMATIC S5 systems. Its 2 × 32 KB EPROM holds the DR drive controller and SR standard controller structures. A separate 8 KB EEPROM retains the settings for the configured control loops.
In a drive application, the IP 252 uses the DR structure to process motor speed feedback and send a current setpoint to the converter. The SR structure supports closed-loop and PID control for tasks such as holding a process variable at its setpoint. The IP 252 handles the field signals through eight analog inputs and eight analog outputs at X6, with a nominal signal range of ±10 V.
Which IP 252 and rack does it fit?
Siemens documents the 6ES5 252-3AA11 with the 6ES5 374-0AA11 in an S5-115U installation. The example uses a CR 700-2 rack, a CPU 942-7UA11 and a PS 951-7LD11 power supply. The same DC motor application includes a 430-7LA11 digital input module and a 451-7LA11 digital output module.
The IP 252 manual specifies an adapter casing for the S5-115U and covers installation in the S5-135U with an R processor and the S5-150U. For an IP 252 6ES5 252-3AA13, check the module revision and the order number of the installed submodule before choosing a spare.
How do the similar 374 order numbers differ?
The 6ES5 374-0AB11 provides the extended DRS/SR structures, including drive controller self-tuning. The 6ES5 374-0BA11 is a separate special version for the IP 252. The 6ES5 374-2KG21 is a long-format Flash EPROM card for the CPU 928. When selecting a replacement, check the 0AA11 suffix on the submodule and the DR/SR selection in COM REG.
Where are COM REG settings stored?
To configure the controller in COM REG, connect the PG to the IP 252’s X5 interface with the appropriate S5 programming cable. Sampling times, controller structures, channel assignments and tuning constants first go into IP 252 RAM. The IP 252 then automatically saves changes to retentive settings in the 0AA11’s EEPROM.
After a memory replacement, the IP 252 loads the EEPROM settings into working RAM under the startup conditions described in the manual. Before returning the machine to service, compare the controller structure, sampling time and analog channel assignments with the saved COM REG configuration.
Editor’s note
When buying a spare, check photos of both the IP 252 label and the 0AA11 suffix on the memory submodule.
Record the configured loops and parameters in COM REG before removal. In particular, document which channels carry the feedback input and the control output.
Bring the machine to a safe stop and isolate the S5 rack supply. Check the orientation before seating the submodule in the 48-pin X3 receptacle.
If the IP 252 stays in STOP at startup, check that the submodule is seated in X3, that its identifier is valid and that the RUN/STOP selector is set as intended. Siemens lists missing or incorrectly identified memory as a cause of STOP.
After changing parameters, allow time for the EEPROM update. Read the settings back and record them in the service log before switching off.
OtomasyonAVM resources and PDFs
+ IP 252 6ES5 252-3AA11 · IP 252 6ES5 252-3AA13 · Siemens SIMATIC S5 PLC overview
+ SIMATIC S5 manuals and PDF archive
Related topics
+ 6ES5 374-0AB11 DRS/SR memory · 6ES5 374-0BA11 special IP 252 memory · PID control with a PLC
Browse SIMATIC S5
+ SIMATIC S5 memory submodules · SIMATIC S5 · Used Siemens automation equipment
Siemens and external references
+ Siemens 6ES5 374-0AA11 data sheet, EPROM and EEPROM capacities (DE, PDF)
+ SIMATIC S5 IP 252 and COM REG Manual, S5-115U application example (PDF) · Section 4.1, DR/SR and DRS/SR controller structures · Sections 4.5–4.6, retentive settings and startup behavior