Siemens 6ES5 755-3AA11 is a 50 Ω termination set for SINEC H1 / Industrial Ethernet triaxial bus networks associated with the SIMATIC S5 generation. The manufacturer lists two terminating resistors, two rubber caps and one fixing bracket. Matching the Ethernet bus impedance reduces signal reflections at the cable ends.

The accessory belongs to the physical cable arrangement of legacy coaxial H1 networks used in S5 communication systems. During industrial communication troubleshooting, inspect the bus ends and fittings alongside diagnostics for a processor such as the CP 535-3LB11. A small termination fault can affect communication at several stations.

50 Ω termination at both segment ends

Siemens specifies one 50 Ω terminator at each end of every bus segment. Missing or incorrect termination can cause reflections and signal levels that a transceiver interprets as collisions. In terms of Ethernet operation, this calls for examination of the physical cable path.

A persistent collision indication is a reason to inspect both end terminations and their connections. When assessing Ethernet problems, treat the indication as evidence for investigation rather than a complete diagnosis. Check the terminator, cable and connection points separately.

Original set contents and used parts

The original 6ES5 755-3AA11 set contains 2 terminators, 2 rubber caps and 1 fixing bracket. When buying used S5 accessories or PLC accessories, confirm the actual quantity and any missing parts from photographs. A set order number does not establish that a used package is complete.

N-type connection and installation position

At a segment end, the terminator screws onto the transceiver connection or connects to the cable through a suitable N-type coaxial coupling. The 6ES5 755-4AA11 N-type connector set serves cable preparation; it has a different function from the termination set.

When inspecting S5 cable connections and PLC communication cables, examine the centre contact, threads and retention together. A used connector needs reliable electrical contact as well as a mechanical fit. Forcing a damaged thread does not restore a dependable connection.

Rubber caps and grounding

The rubber caps provide electrical insulation. In a triaxial cable, the outer conductor of the inner coaxial line and the outermost screen have different connection arrangements. Siemens requires insulation to prevent unintended multiple grounding of the coaxial outer conductor. Keep this distinction when reviewing grounding and the Ethernet cable construction.

Keep exposed terminator metal away from cabinet sheet metal and mounting hardware. Preserve the caps, insulation and fixing arrangement shown by the manufacturer. Do not create an arbitrary grounding path for the outermost screen through the terminator body.

Network speed and segment length

The manual describes classic SINEC H1 triaxial networks operating at 10 Mbit/s, with up to 500 m of bus cable per segment. Assess Ethernet speeds and cable lengths for the actual physical medium. These network limits do not mean that the terminator independently increases speed or range.

A practical maintenance sequence

During PLC communication troubleshooting, identify the two actual segment ends before checking terminations, couplings and cable damage. Record the work before returning the Siemens S5 system to service, then repeat communication checks between the same stations after the change.

Editor’s Note

When buying used Siemens equipment, ask for an item-by-item photograph. This original order code covers two terminators; establish whether the offer contains one or both. Check the caps and bracket before the installation day.

Measure resistance with the part disconnected from the cable. A reading around 50 Ω is a useful initial check, but it does not establish high-frequency performance. A continuity buzzer alone is not a meaningful acceptance test.

Treat the rubber cap as insulation, not decoration. Correct a missing, hardened or cracked cap before installation. Contact between the metal body and cabinet sheet metal can introduce a grounding problem while you are investigating another fault.

Do not remove a terminator experimentally from a running network. Mark both ends during a planned maintenance stop before changing parts. Compare S5 PLC communication before and after under the same conditions so the effect of the work is clear.

Matching threads do not establish the correct resistance or function. Check identification, the 50 Ω value, connector type and cap condition together. A few minutes spent on this small component can save a much longer search across the whole network.

OtomasyonAVM resources and PDFs

Browse S5 communication modules, S5 cable connections and the 755-4AA11 N-type connector set for related hardware.

Shared PDF archive for S5 systems — This page uses Siemens triaxial-network manuals in English and German. The manufacturer links below identify the exact set contents and termination drawings.

Related topics

+ 6ES5 755-4AA11 N-type connector set

+ 6ES5 535-3LB11 CP 535

+ Grounding and connections

+ Ethernet questions and explanations

Browse SIMATIC S5

+ S5 accessories

+ S5 communication modules

+ SIMATIC S5

+ Siemens second-hand equipment

Siemens and external references

+ SIMATIC NET — Manual for Triaxial Networks, Release 04, §2.3.3, English

+ AR 463-220/4 — Figure 35, exact 6ES5 755-3AA11 set contents, English

+ SIMATIC NET — Handbuch für Triaxialnetze, Ausgabe 04, Figure 35, Deutsch