6ES5 400-0AA11

Siemens 6ES5 400-0AA11 S5-010W Digital Input and Timer Module

Siemens 6ES5 400-0AA11 is a module for the S5-010W with 40 inputs rated at 24 V DC and four analog timers in the SIMATIC S5 family. When selecting this S5 supporting module, check the complete order number, existing housing arrangement and address-coding jumpers together.

Alongside its digital input function, timing is adjusted on the board. Do not select a different 400 suffix, such as the 6ES5 400-7AA13, from the shared number alone. Preserve the S5-010W connection arrangement and timer configuration specific to the 0AA11.

Input connection and module location

Signal wiring uses a 48-way front connector; four inputs can serve as interrupt inputs. Match the pin arrangement and common references when inspecting cables and connectors. Measure the supply against the reference used by the board rather than relying on wire colours.

Record the S5 carrier arrangement and CPU position. In the S5-010W, the CPU and input/timer modules have assigned locations. Check the relevant layout documentation before moving the board or transferring it to a different housing.

Adjusting the four analog timers

The timing ranges are 10–100 ms, 100 ms–1 s, 1–10 s and 10–100 s. A range selector provides coarse adjustment and a potentiometer provides fine adjustment. Record the selected range and measured duration before making changes.

Repeat the measurement at the same setting to check consistency. For short durations, consider the measurement method and PLC program cycle together. A potentiometer turning normally does not establish smooth, repeatable adjustment throughout its range.

Coding jumpers and an address-group example

The manual’s first coding group shows timers at 00.1–00.4, interrupt inputs at 01.0–01.3 and the remaining inputs at 01.4–05.7. Other jumper arrangements change these addresses. During PLC programming checks, compare the application with the actual jumper settings.

Do not assume these addresses are a fixed default. Preserve a backup of the program memory and the address list. Distinguish hexadecimal from decimal notation in older documents: hexadecimal 0D, for example, equals decimal 13. Investigate address overlaps before replacing hardware.

Timer logic in STEP 5

S5-010 timers are started with output operations and scanned with input operations. When reviewing PLC programming languages, Ladder or function block diagrams, distinguish the timer’s start condition, running state and elapsed state.

The documented AI/OI scan returns “1” while the timer is running. Logic that detects completion must also account for whether the timer was started. Read the existing program before equating this board’s timing signal with timer operations from another S5 family.

Bench testing and fault isolation

Record input and output tests separately. Where the S5-010W arrangement includes a 6ES5 410-0AA12 or 6ES5 410-0AA41, check the output board’s load and wiring conditions in its own documentation. Test arrangements for combined I/O products must not be transferred directly to this board.

Record the programming interface and communications equipment used for online inspection. Follow the physical board signal through to the CPU address and program response. This helps separate wiring, addressing and program faults.

For an older Siemens S5 system, test the inputs individually and evaluate each timer separately during used-unit acceptance. State the complete code, jumper configuration, included connector parts and actual results in the quotation. Identify interrupt functions or timing ranges that have not been tested.

Editor’s note

Ask for a clear photograph of the 400-0AA11 label. The timer controls and front connection equipment should be visible as well. A missing connector can leave a sound board waiting on the workshop bench.

If timing is inconsistent, inspect the range selector, potentiometer and recorded original setting before changing the program. Note sudden jumps in adjustment or a different duration when returning to the same position.

Checking a few inputs is insufficient for a useful acceptance test. Inspect channels sharing a common reference and isolate the suspect field cable. An incorrect reference connection can make several inputs appear faulty together.

Photograph the original address and interrupt jumper settings before removal. A damaged link during cleaning or copied settings from another board can change behaviour even when the program is sound. Establish the required configuration before altering jumpers.

The manual describes testing timers with the TEST switch while the CPU is in STOP. Use a controlled bench arrangement and return the switch to its normal position afterwards. Record the board’s timing test separately from the machine program’s response.

OtomasyonAVM resources and PDFs

+ 6ES5 400-0AA11 product and information page and Siemens S5 models.

+ OtomasyonAVM shared SIMATIC S5 PDF archive. Dedicated S5-010W documents for this model are linked in the external references below.

Related topics

+ S5-010W 410-0AA12 output board, 410-0AA41 output board and S5 connection accessories.

+ PLC programming, S5 memory modules and about Siemens S5 PLC.

Browse SIMATIC S5

S5 supporting modules  |  S5 digital inputs  |  Siemens S5 models  |  Siemens second-hand homepage

Siemens and external references

+ Siemens S5-010W Operating Instructions, English. GWA 4NEB 807 1021-02; module description, timing adjustments, jumpers and front-connector assignments.

+ Siemens S5-010W and K Programming Instructions, English. GWA 4NEB 807 1071-02; addressing in Section 1.2 and timer/interrupt operations in Section 4.1. Distinguish the sections applicable to W and K systems.