6ES5 420-4UA14

Siemens 6ES5 420-4UA14 — 32-Channel 24 V DC Non-Isolated Digital Input Module

Siemens 6ES5 420-4UA14 is a 32-channel, 24 V DC non-isolated digital input module for SIMATIC S5 systems. This compact U-type input module transfers field status signals to the S5 controller in suitable S5-135U/155U central or expansion arrangements. Its input reference must be assessed together with the system reference.

Typical sources include industrial sensors, inductive sensors, photoelectric sensors and limit switches. The manufacturer’s contact diagram applies positive 24 V to an input. For electronic sensors, check the output circuit, 0 V return and off-state leakage current.

Input voltage, current and switching rate

The specified logic-0 range is −33…+5 V and the logic-1 range is +13…+33 V. Do not use the region between +5 V and +13 V as a defined logic level. Rated input current is 8.5 mA, with a typical input resistance of 2.8 kΩ. Include this input load when assessing the field power supply and cable voltage drop.

Maximum input frequency is 100 Hz. The typical delay is 3 ms, with a specified range of 1.4–5 ms. The simultaneous-input loading factor is 100%. Include PLC scan timing when determining whether the program will detect short pulses.

System supply for the 4UA14 revision

The 4UA14 takes 5 V from the system bus at a typical current of 30 mA. Rated operating power dissipation is 7 W. When assessing the S5 power supply, distinguish the bus load from the external 24 V sensor circuit.

Front connector and common reference

The 42-pin front connection uses pin 1 for the F+ enable input and pin 42 for common L−. Pins 2 and 3 are not connected internally. Check the actual diagram when inspecting cables and connectors. Verify the system reference and field return together with the rack arrangement.

Input terminals run through 4–11, 13–20, 25–32 and 34–41. Fitting the X20 jumper activates external enable control; this is the factory setting, so the F+ voltage must be provided. The manufacturer’s diagram connects the field supply L− to the reference potential (PE). Preserve the grounding and common-reference arrangement specified in the machine’s electrical design.

In an expansion arrangement, inspect the connection chain through the S5 interface modules and expansion modules as well. Module dimensions are 20 × 255 × 195 mm, with an approximate weight of 0.4 kg. Check mechanical fit and electrical compatibility together.

Addressing and troubleshooting

The 32 inputs use four input bytes in the PLC project. For a starting address of 64, the example area is IB64–IB67, with bits I64.0–I67.7. This is not a factory address. Match the PLC input addresses to the module’s address switch and existing program.

Compare the voltage from the relay contact or sensor output, the green channel indicator and the program bit in that order. In a Siemens S5 system, loss of enable can cause a QVZ access timeout. Check the address, F+ circuit and front connector together when investigating this condition.

Differences from nearby order numbers

6ES5 420-4UA13 has a typical bus current of 80 mA, compared with 30 mA for this 4UA14 revision. Assess 6ES5 420-4UA12 as a separate revision. 6ES5 430-4UA14 has isolated inputs. Compare the full order number, reference arrangement and enable circuit before choosing a replacement.

Editor’s note

Start with the common reference. These inputs are non-isolated, so finding 24 V at a sensor output is only part of the check. Measure against the correct L− reference and inspect the common return for loose or broken connections.

Trace the front plug against this module’s diagram. L− is on pin 42; pins 2 and 3 are not connected internally. Check each terminal before reusing old wiring, including any bridges added during previous repairs.

Investigate QVZ before ordering a replacement. Check the F+ voltage, X20 jumper position and address switch. An incompletely seated front connector can produce an access fault even when the module itself is healthy.

Test every channel on a used board. With a suitable current-limited test arrangement, apply 0/24 V to each input in turn. Record both the green indicator and the PLC bit for every channel; a few working inputs do not establish the condition of the whole module.

Include the wiring in intermittent-fault checks. Sensor leakage, cable voltage drop and the common return can all cause trouble. Record field measurements before replacing the board, and put machine outputs into a safe state before making test connections.

OtomasyonAVM resources and PDFs

+ About Siemens S5 PLC — systems and module structure

+ S5 digital input modules — model pages

+ Our general SIMATIC S5 PDF archive — existing manual and file index.

Related topics

S5 digital output modules · S5 analog modules · Relay and contact operation

Browse SIMATIC S5

S5 digital input modules · SIMATIC S5 · Siemens S5 PLC · Used Siemens equipment