6ES5 498-1AA51
Siemens 6ES5 498-1AA51 SIMATIC S5 4–20 mA Two-Wire Measuring Range Submodule
The Siemens 6ES5 498-1AA51 is a 498 measuring range submodule for two-wire 4–20 mA transmitters on SIMATIC S5 analog input cards. On supported cards such as the S5-115U 460-7LA12 and the U-periphery 460-4UA12, one submodule sets the range for four input channels. The submodule uses a 31.25 Ω shunt.
A two-wire pressure, level or temperature transmitter shares one loop for power and the 4–20 mA measurement signal. In the 1AA51 wiring arrangement, the analog input card supplies loop power from L+ through the submodule. The host analog input card converts the signal to a digital value.
How does the two-wire 1AA51 differ from the four-wire 1AA71?
The 6ES5 498-1AA71 covers the same 4–20 mA range and is listed for four-wire transmitters with their own power supply. Check the transmitter’s power and signal terminals against the installed wiring diagram. When switching between current and voltage signals, consult the range tables for the 1AA31 ±10 V, 1AA61 ±5 V and 1AA41 current range cards.
Match the S5 connection cables and front connector terminals to the diagram for the host input card. Siemens states that using the 1AA51 removes galvanic isolation between the analog inputs and L+. Check the 24 V supply and reference potentials against the wiring diagram.
Which analog input cards list this submodule?
The S5-115U manual shows the 1AA51 for the 460-7LA12 and 465-7LA13. The section on the 460-7LA13 also states that it provides the functions of the 460-7LA12. Use the full host order number to check the channel-group settings, front connector terminals and submodule positions.
The U Periphery manual lists the 1AA51 in the technical tables for the 460-4UA11, 460-4UA12, 465-4UA11 and 465-4UA12. A Siemens supplement states that 4UA13 modules such as the 460-4UA13 and 465-4UA13 have the same functions and specifications as the corresponding 4UA12 models. In an S5-135U rack, verify compatibility against the fitted input card’s order number.
How do you scale the measurement and detect an open loop?
For the 460-4UA12, Siemens gives 4 mA → 512 and 20 mA → 2560 measurement units. Subtract 512 to map the span to 0–2048. Before using these values in the STEP 5 project, check how the program extracts the measured value from the host card’s input word.
The 1AA51 shunt prevents the built-in analog input wire-break indication from signalling in this range. Siemens shows how software can evaluate current below 3 mA from the measured-value bits. Keep this fault condition separate from the normal 4 mA lower endpoint.
Editor’s note
Read the transmitter label first. A two-wire transmitter uses the same loop for power and signal. Check the device wiring diagram as well as the terminal count.
Record the channel group before replacement. Photograph the host card order number, channel numbers and the slot occupied by the 1AA51.
Use the correct calibrator mode. If the card supplies loop power, use the calibrator mode intended to simulate a two-wire transmitter.
Check the scaling at three points. Apply 4, 12 and 20 mA. Compare the S5 PLC measurement value with the engineering units shown on the display.
Record the fault test separately. Verify that low current raises the software alarm and that the process value remains valid at the normal 4 mA endpoint.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog modules · Siemens S5 hardware and STEP 5 guide
OtomasyonAVM S5 system manuals and PDF archive
Related topics
498-1AA71 four-wire 4–20 mA · 460-7LA12 analog input · 460-4UA12 analog input · 465-7LA13 analog input
S5 navigation
Siemens S5 PLC · SIMATIC S5 · S5 analog modules
External references
Siemens S5-115U system manual, range cards and L+ note, Table 10-1 (English PDF)
Siemens U Periphery manual, 460-4UA12 technical data (English PDF)