The Siemens 6ES5 101-8UA23 is a compact SIMATIC S5-101U central controller with 16 AC inputs and 8 triac outputs. The CPU, program memory and I/O share one housing. See the Siemens S5 PLC guide for the family and the used PLC CPU section for second-hand controllers.
Supply and terminal layout
Figure 12 of the Siemens manual specifies a 220 V AC or 240 V AC mains connection. The input groups, output groups and mains supply must use the same phase. Check the unit label and Figure 12 for the terminal layout. The 101-8UA13 is a relay-output version, while the 101-8UA33 uses a 24 V DC supply and transistor outputs.
AC inputs and triac outputs
The digital inputs use addresses I0.0–I1.7. Their nominal rating is 220 V AC. They form two groups of eight, each with its own common terminal. The digital outputs use addresses Q0.0–Q0.7 and form two groups of four.
At 264 V AC, Siemens rates the triac outputs at 50 mA–1 A for resistive loads, 50 mA–0.5 A for inductive loads and 60 W maximum for lamp loads. Off-state leakage is 5 mA maximum. For applications that require relay outputs, see the load ratings and terminal drawing for the 101-8UB13 relay version.
Programming and memory
The internal RAM holds 1,024 statements. A backup battery retains the RAM contents during power loss. A plug-in EPROM or EEPROM module can store the program. The controller can copy the installed S5 memory module into RAM at power-up or on switching to RUN. To reduce the risk of memory data loss, read and back up the existing program before changing modules.
The controller uses a TTY interface for PLC programming. Siemens lists the 6ES5 731-1BD20 cable for PG670 and PG675. When selecting Siemens PLC cables, check both the programmer model and the interface type.
Expansion and used equipment checks
Figure 15 shows the terminal layout for the 6ES5 101-8UC21 triac expansion unit. A short ribbon cable connects the central controller to the expansion unit. Check the interfaces and connecting cables against the manual. The 8UC11 relay and 8UC31 transistor expansion units have separate wiring drawings.
When buying used equipment, inspect the terminals, fuse holder and PG socket as well as the electronic boards. Ask for a photo of the full order number and a test record showing the RUN/STOP indicators and the triac outputs switching a suitable AC load.
Editor’s note
When reviewing an output test, allow for the manual’s 50 mA minimum load and up to 5 mA of off-state leakage. Ask for a record that shows both the output LED and the AC load switching on and off.
If you have this PLC for sale, send photos of the unit and its label to otomasyonavm@gmail.com.
Siemens S5 PDF archive
The relevant 101U manual pages are listed below. See the shared Siemens S5 PDF archive for other documents.
Related topics
6ES5 101-8UA11 · 6ES5 101-8UA12 · S5 digital I/O modules
References
Siemens S5-101U, Figure 12, 8UA23 terminal layout · Siemens 8UA23 I/O ratings, p. 5-3 · Siemens CPU and memory data, p. 5-2 · Siemens programmer connection cable, p. 6-1