6ES5 101-8UA13 is the 20-input, 12-relay-output S5-101U central controller in the SIMATIC S5 family. The CPU, program memory and I/O are built into one housing. OtomasyonAVM lists it in the CPU 90U–115U parts directory. For background, see About Siemens S5 PLCs.
Power supply and terminals
The mains connection is rated for 220 or 240 V AC. The controller provides 24 V DC at up to 300 mA for field sensors. If the cabinet uses an external 24 V supply, check the wiring against Siemens Figure 10. Other supply hardware is listed under S5 power supplies.
The digital inputs are rated at 24 V DC and addressed I0.0–I2.3. The outputs are addressed Q0.0–Q1.3. Each pair of relay contacts shares a common terminal. Record these common terminals alongside the S5 I/O addresses on the cabinet wiring list.
Siemens lists contact ratings of 1.5 A at 250 V for AC-11 and 0.5 A at 30 V for DC-11. For contactor or valve coils, check the load against the applicable switching category.
S5-101U variants and expansion
The 8UB13 has 10 inputs and 6 relay outputs. The 8UA23 has 16 AC inputs and 8 triac outputs. The 8UA33 uses a 24 V DC supply and transistor outputs. Match the full order number to the cabinet diagram when choosing a replacement.
The 8UC11 relay expansion unit brings the hardware total to 40 inputs and 24 relay outputs. The 8UC31 is the transistor-output expansion unit in the same family. When checking the expansion hardware, record the EU/EG connecting cable and the supply for each unit.
STEP 5 and program memory
Internal RAM holds 1,024 STEP 5 statements. A backup battery retains RAM contents. An external EPROM or EEPROM submodule provides long-term program storage. Siemens explains that a fitted submodule can overwrite the internal program at power-up or when switching from STOP to RUN. Archive the existing STEP 5 program before commissioning a replacement.
The programmer connects through the PU/PG TTY port. Siemens lists the 6ES5 731-1BD20 cable for PG670 and PG675 programmers. If the installation uses SINEC L1, record the order numbers of the fitted communications hardware.
Buying a used unit
Ask for clear photos of the full order number and the input and output terminals. Check the mains and sensor fuse holders for heat damage. Confirm whether the backup battery and memory submodule are included.
Editor’s Note
The output LED follows the relay coil. Ask for a used-unit test record that also shows switching at each of the 12 relay contact terminals. Recording the Q address and shared common for each result makes it easier to match the channels in the cabinet.
To offer an S5-101U for sale, send a label photo, quantity, operating condition and asking price to otomasyonavm@gmail.com.
Related topics
6ES5 101-8UA11 · SIMATIC S5-90U · What is a PLC?
Siemens S5 PLC · Used Siemens equipment · All used automation equipment
References
Siemens SIMATIC S5-101U Operating Instructions (6ES5 998-0UC23, EWA 4NEB 810 2119-02c, English). Page 2-4 shows the 8UA13 terminal diagram. Pages 3-2 and 3-3 cover memory and expansion. Pages 5-1 through 5-3 give the technical ratings.