6ES5 095-8MA03

Siemens 6ES5 095-8MA03 — SIMATIC S5-95U Compact PLC

6ES5 095-8MA03 is the S5-95U basic unit. It runs the STEP 5 program and processes machine signals through its onboard I/O. The Siemens S5 PLC guide covers the family, and the S5 CPU catalogue lists other models.

Power, memory and onboard I/O

The nominal supply is 24 V DC, with a permitted range of 20–30 V DC. Siemens lists the PS 931 (6ES5 931-8MD11) among the external S5 power supplies for this unit. The 16 KB of internal RAM is shared between program instructions and data blocks. Check the EPROM or EEPROM type and full order number when selecting an S5 memory module for program backup.

The controller has 16 digital inputs and 16 digital outputs. Both groups use addresses 32.0–33.7. External stations may have separate digital input and digital output cards or combined I/O modules. When tracing a fault, check whether the program address refers to an onboard channel or an external module.

The eight analog inputs have a 0–10 V range. The single analog output operates at 0–10 V or 0–20 mA depending on the connection. The unit also has four interrupt inputs and two counter inputs. Siemens specifies 5 kHz for counter A and 2 kHz for counter B when no PG, OP or SINEC L1 is connected. If the cabinet uses external S5 analog modules, verify the signal range against the individual module code.

Connections and compatibility

The digital channels use a 40-pin front connector. Siemens lists the 6ES5 490-8MA12 crimp connector and the 6ES5 490-8MB11 screw-terminal connector. Check the interfaces at both ends when choosing an S5 programming cable for the PG port. The 734-1BD20-CL is an example with RS-232 on the PC side.

With expansion hardware and compatible S5-100U I/O, the external limits are 448 digital and 32 analog channels, counting inputs and outputs together. Record the order numbers and addresses of installed S5 modules before replacing hardware.

The S5-90U is a separate series in the SIMATIC S5 family. If you are considering an 8MA04 or 8MA05, compare the existing STEP 5 program, hardware revision and connections. Identify the communications hardware separately if the cabinet uses SINEC L2 or L2-DP. Siemens lists 95U units fitted with these interfaces under separate order numbers.

Used-unit checks

Ask for a label photo showing 6ES5 095-8MA03 and the hardware revision. Check RUN/STOP operation, program readout through the PG port and digital I/O operation under load. Inspect the battery compartment and confirm whether the front connector is included. To sell a unit, send the label photo, quantity, working condition and asking price to otomasyonavm@gmail.com.

Editor’s Note. Check whether the machine uses the analog output in voltage or current mode. During a bench test, measure the output at two different commands with a suitable load. This checks whether the output responds while the RUN light is on. Back up DB1 along with the STEP 5 program before swapping the unit.

Related topics

Shared Siemens S5 PDF archive · Used SIMATIC S5 · Siemens second-hand main page · All second-hand automation

References

Siemens S5-95U operating instructions (PDF, German) — EWA 4NEB 812 6068-01d. See pp. v, F-1 and H-1 for the model and revision, pp. 1-2–1-4 for connections, and pp. A-2–A-4 for specifications.