6ES5 095-8FA01
Siemens 6ES5 095-8FA01 — SIMATIC S5-95F Subunit
6ES5 095-8FA01 is one subunit of the redundant SIMATIC S5-95F control system. A basic S5-95F system consists of subunits A and B connected by a fiber-optic link. See the Siemens S5 PLC guide for the family overview and the S5 CPU catalogue for other models.
Matching subunits and technical specifications
Siemens requires both S5-95F subunits to have the same order number and hardware revision. The SIMATIC S5 catalogue lists 8FA02 and 8FB01 as separate 95F models. The 8MA03 belongs to the S5-95U series.
The nominal supply is 24 V DC. Siemens lists 16 KB of user memory, with typically 8 KB used for the program. When identifying the cabinet’s S5 power supplies, check the 8FA01 isolation requirements and supply arrangement against the electrical drawings.
The two-subunit basic system provides 16 failsafe digital inputs, eight failsafe digital outputs, four interrupt inputs and two counter inputs. It also has eight standard digital outputs, four per subunit. When tracing a field fault, use the cabinet drawings to identify the functions of the digital inputs, digital outputs and connected contactors.
Connections, programming and expansion
Digital field wiring uses a 40-pin front connector. For standard analog functions, the S5-95F manual lists external S5-100U analog modules. For servicing, identify the PG cable and installed EPROM memory modules. STEP 5 handles the program, and COM 95F handles the system parameters supported by the 8FA01.
When inspecting expansion hardware, record the order numbers of the installed S5 modules separately for A and B. Siemens specifies paired modules such as the 6ES5 431-8FA11 for safety-related input tasks. List standard combined I/O modules separately in the cabinet inventory.
Verify the full order number of any installed communications hardware. Siemens’ CP 541 manual lists the 8FA01 from revision 03 for safety-related data transmission. The CPU 942F in the same table belongs to the S5-115F system.
Used-unit checks
Ask for label photos of both units and check the front connectors, fiber-optic ends and EPROM modules. Confirm whether the offer covers one subunit or an A/B pair. Check the commissioning records for the PLC outputs and connected safety relays. To sell a unit, send the label photo, quantity, working condition and asking price to otomasyonavm@gmail.com.
Editor’s Note. On the 8FA01, Siemens documents that the power-down sequence can cause a false I/O fault indication when the controller and load have separate supplies. If the fault coincides with a power interruption, compare the service log and supply drawings before ordering a module. After replacement, verify the A/B pair, program and parameters together and perform the system acceptance test.
Related topics
Shared Siemens S5 PDF archive · Used SIMATIC S5 · Siemens second-hand main page · All second-hand automation
References
Siemens 6ES5095-8FA01 datasheet · S5-95F system manual — EWA 4NEB 812 6210-02a, Table 1-3 and sections 4.2, 4.7 and 5.5.
Siemens S5-95F subunit matching requirements — EWA 4NEB 812 6220-02, p. xix · COM 95F manual — EWA 4NEB 812 6221-02a, p. vii and Chapter 5 · CP 541 manual — EWA 4NEB 812 6188-02, Table 5-1.