6ES5 526-3LF11

Siemens 6ES5 526-3LF11 CP 526-2 Color Operator Display Board

Siemens 6ES5 526-3LF11 is a CP 526-2 basic board for color operator displays in SIMATIC S5 installations configured under S5-DOS. This version of the S5 communications processor requires external forced-air cooling. The CP 526 color interface has four BNC video outputs and a 15-pin, 20 mA TTY connection for a process keyboard or programming device.

The operator display shows process values and messages from the PLC. The operator can call up screens and enter setpoints where the application permits it. COM GRAPH can display readings from analog modules, the state of digital inputs and the status of digital outputs in separate fields.

Identifying the color board

The 6ES5 526-3LF01 is the monochrome CP 526-2 basic board. The 6ES5 526-3LG11 is the naturally cooled color version. The 6ES5 526-3LA11 is also a color CP 526 designed for forced-air cooling. When sourcing a spare, verify the 3LF11 suffix, the monitor interface and the rack cooling arrangement.

Monitor and process keyboard connections

The Siemens CP 526 family manual identifies the color outputs as R, G or G/S, B and S. RGB is 0.7 V into 75 Ω and the separate sync output is 1.0 V into 75 Ω. Jumper X17 routes sync to its own line or the green channel. Match the S5 cables and connectors to the monitor wiring diagram. The BNC outputs are non-isolated, so follow the manual’s shielding and grounding arrangement.

The front 15-pin TTY socket serves the process keyboard during operation and the PG during programming. The family manual specifies 50–9,600 bit/s for the serial interface. When matching the existing serial interface, verify the TTY current loop, cable pinout and connected device settings.

Rack slots, addressing and application memory

The Siemens family manual lists rack configurations for S5-115U, S5-135U, S5-150U and S5-155U. The permitted slot depends on the S5 rack. The CR 700-2, for example, requires an adapter casing. The family manual lists 2.2 A on the 5 V rail and up to 40 mA on the 24 V rail for the basic board. Allow roughly 200 mA extra on the 24 V rail in the rack power supply budget when a process keyboard is fitted.

The page number set at X7 must match SSNR in the STEP 5 handling blocks. Configure the display application in COM GRAPH and store it on the CP’s RAM or EPROM memory submodule. If the application uses trends, bar graphs or enlarged values, check the expansion board as well. Siemens lists the 6ES5 526-3LA21 and 6ES5 526-3LA22 as separate expansion boards.

Editor’s note

Ask for a photo of the 3LF11 label and all four BNC sockets. Verify color video and keyboard input separately during the bench test.

Back up the COM GRAPH project before removing the board. The Siemens manual states that removing the board or RAM submodule clears the application held in RAM.

Isolate the rack and verify it is de-energized. Record the original X7, X10, X14 and X17 jumper settings before removal.

If the picture rolls or stays blank, check the monitor’s resolution and sync input first. X10 and X14 must be set for the same resolution.

If the display is active but process values are stale, check the RUN selector and the X7–SSNR match. In STOP, display functions can remain active while PLC data exchange is suspended.

OtomasyonAVM resources and PDFs

+ About the Siemens SIMATIC S5 PLC

+ SIMATIC S5 manuals and PDF archive

Related topics

+ 6ES5 526-3LF01 monochrome CP 526-2 · 6ES5 526-3LG11 naturally cooled color CP 526 · 6ES5 526-3LA22 expansion board

Browse the range

+ S5 communications modules · SIMATIC S5 · Used Siemens automation equipment

Siemens and external references

+ Siemens COROS CP 526 family manual (PDF) · §3.10.4.1, color video outputs

+ 6ES5 526-3LF11 exact part number listing