6ES5 498-1AA41
Siemens 6ES5 498-1AA41 SIMATIC S5 Measuring Range Module, 4 Channels, ±20 mA
The Siemens 6ES5 498-1AA41 is a four-channel ±20 mA shunt module for compatible 460 and 465 analog input modules in SIMATIC S5 systems. It converts a current signal into a voltage the host input module can measure in S5-135U/155U and compatible S5-115U/H/F installations. The 460-4UA12 and 460-4UA13 also support a ±5 mA range with the appropriate gain setting.
A level transmitter with a 0–20 mA output, for example, uses the positive half of the ±20 mA range. For a 4–20 mA loop, check the power supply and scaling separately. Siemens lists the 498-1AA51 for two-wire transmitters and the 498-1AA71 for four-wire transmitters in that range.
Which host modules accept it, and how many channels does it cover?
The S5-135U/155U manual lists the 460-4UA13, 465-4UA12 and 465-4UA13 with this module. Each 498 card sets the range for one group of four inputs. An eight-input 460 has two groups. A 465 configured for 16 current or voltage inputs has four.
The U Periphery manual also covers earlier revisions such as the 460-4UA11, 460-4UA12 and 465-4UA11. The Siemens ST 50 catalog pairs it with the 460-7LA13 for S5-115U/H/F and the 465-7LA13 for S5-115U/H.
Range setting, wiring and STEP 5 scaling
For ±20 mA, the host module uses its 500 mV/mA mode. On the 460-4UA12 and 460-4UA13, ×1 gain gives ±20 mA and ×4 gain gives ±5 mA in this mode. Check the switch table on the host module. Siemens specifies a 25 Ω input resistance for the ±20 mA configuration on the 460-4UA13 and 465-4UA12.
The current signal connects to the channel’s M+ and M− terminals on the host module’s front connector. Use the pinout for the exact host order number. The 497-4UA12 crimp connector and 497-4UB31 screw-terminal connector are separately ordered parts. The PLC address is set on the host input module. In the Siemens S5-115H example, the AI 460 converts 0–20 mA to 0–2048 measurement units, which the STEP 5 program scales to engineering units.
Which signals do the other range cards handle?
The 498-1AA11 serves low-voltage and Pt100 applications. Voltage options include the 498-1AA21 for ±1 V, 498-1AA61 for ±5 V and 498-1AA31 for ±10 V. On a module with mixed signal types, check the range card fitted to each four-channel group.
The 466-3LA11 analog input module has its own hardware range settings. The 470-4UA12 analog output module sends a signal to a field device. When identifying a spare, check the signal direction first, then read the complete host module order number.
Editor’s note
Before ordering, photograph the 498-1AA41 label and the complete order number on the 460 or 465 host module.
Before removal, record the four-channel group and the host switch positions. Pay particular attention to the ×1 or ×4 gain setting.
If the reading moves in the wrong direction, check M+ and M− polarity first. Then compare the transmitter’s actual output with the PLC channel reading.
If a channel stays at zero, check transmitter power and loop continuity. With this shunt card, use a loop measurement to verify a suspected broken wire.
After replacement, test at two known current levels. Check both the PLC reading and the engineering value on the operator display.
OtomasyonAVM resources and PDFs
See the Siemens SIMATIC S5 PLC overview and the S5 analog module catalog.
See the OtomasyonAVM S5-115 PDF archive and the SIMATIC S5-115H system manual, page 7-32, 0–20 mA wiring example using the 498-1AA41.
Related topics
Compare the 460-7LA12 analog input module and the range cards for two-wire 4–20 mA and four-wire 4–20 mA loops.
Browse the S5 range
Siemens SIMATIC S5 › S5 analog modules
To sell a Siemens S5 module, email the full order number, quantity, working condition, label photo and asking price to otomasyonavm@gmail.com.
External Siemens references
+ SIMATIC S5-135U/155U system manual, Chapter 9 and 460/465 range cards
+ Siemens U Periphery manual, range tables for 460 and 465 revisions
+ Siemens ST 50 catalog, page 3/47, S5-115 analog input modules and 498 ordering data