6ES5 498-1AA21
Siemens 6ES5 498-1AA21 SIMATIC S5 ±1 V Measuring Range Card, 4 Channels
The Siemens 6ES5 498-1AA21 is a four-channel voltage-divider range card for 460 and 465 analog input modules in SIMATIC S5 systems. With the host in 500 mV mode and gain set to ×1 where selectable, the card gives four field inputs a range of −1 V to +1 V. Siemens lists the card for the relevant 460 and 465 modules in its S5-135U/155U and S5-115U/115H manuals.
In the field, the card scales a bipolar voltage signal, such as the output of a signal amplifier, to the level expected by the host module’s A/D converter. Wire the signal to the corresponding M+ and M− terminals on the host’s front connector. One range card sets the span for all four inputs in its group.
Which 460 and 465 modules accept the card?
The 460-4UA11, 460-4UA12 and 460-4UA13 are eight-input host modules. Their two slots serve CH0–CH3 and CH4–CH7. The 465-4UA11, 465-4UA12 and 465-4UA13 use four groups in 16-channel voltage or current mode. The operating mode determines the input count and which groups are active.
The S5-115H manual covers the 460-7LA11, 460-7LA12, 465-7LA11 and 465-7LA12. The S5-115U manual also shows 498 range cards on the 460-7LA13 and 465-7LA13. The OtomasyonAVM S5-115 PDF archive links to the system manuals. Read the host module’s label before looking up its range table and front connector diagram.
The 463-4UA12 and 463-4UB12 also measure 1 V signals. On these 463 modules, sensor wiring and jumpers at the front connector set the range. Check the host label for 460, 465 or 463 before ordering a 498-1AA21 spare.
How do the 500 mV and 50 mV modes affect the input range?
The 498-1AA21 gives a ±1 V range in 500 mV mode. On modules with selectable gain, that range corresponds to ×1. Siemens lists a ±100 mV range in 50 mV mode with a greater measurement error. On the 460-4UA12 and 460-4UA13, ×4 gain gives ±250 mV in 500 mV mode and ±25 mV in 50 mV mode.
For example, Siemens specifies ±2048 counts over the rated bipolar input range of the 460-4UA11. For STEP 5 scaling, use the host manual’s layout for the measured value and status bits. Check the unused-input and wire-break settings against the diagram for the exact 460 or 465 order number.
Which signals use the other 498 range cards?
The 498-1AA11 covers millivolt and Pt100 applications. In 500 mV mode, the 498-1AA61 gives ±5 V and the 498-1AA31 gives ±10 V. Check the suffix to identify the voltage span selected for the group.
For current measurement, the 498-1AA41 covers ±20 mA. The 498-1AA51 is for two-wire 4–20 mA transmitters, and the 498-1AA71 is for four-wire 4–20 mA transmitters.
Editor’s note
Read both labels. Record the full 460 or 465 order number alongside 498-1AA21. The host order number determines which wiring diagram and switch table to use.
Mark the channel group. Before removal, photograph the card slot, retaining screw and 50/500 mV switch position. Record the gain setting where the host has a gain selector.
Check the front connector against the wiring diagram. Confirm that the signal goes to the correct M+/M− pair. For example, when a 465-7LA13 mixes Pt100 and voltage inputs, Siemens requires wire-break signalling to be disabled for the group fitted with a 1AA21.
Verify all four inputs. After replacement, use a suitable test source at zero and at a known voltage within the configured span. Check both the PLC reading and the scaled value on the display.
Start by identifying the affected channels. If all four drift together, check the shared range card and host settings. If only one input is off, start with that channel’s sensor, cable and M+/M− wiring.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog input modules and range cards · Siemens SIMATIC S5 PLC systems
OtomasyonAVM SIMATIC S5-115 PDF manual archive
Related topics
460-4UA13 eight-input analog module · 465-4UA12 16-input analog module · 498-1AA61 ±5 V range card
Browse SIMATIC S5
Siemens SIMATIC S5 · S5 analog modules
Siemens and other external references
Siemens SIMATIC S5 U Periphery manual, 460 and 465 range tables (English PDF)
Siemens S5-135U/155U system manual, 460-4UA13 range and gain table (English PDF)
Siemens S5-115H system manual, Table 7-6 range cards (English PDF)
Siemens S5-115U system manual, Table 10-4 range cards (English PDF)