6ES5 470-7LB13
Siemens 6ES5 470-7LB13 SIMATIC S5 470 Analog Output Module
The Siemens 6ES5 470-7LB13 is a galvanically isolated SIMATIC S5 analog output module with eight ±10 V DC outputs. The Siemens data sheet lists S5-115U and S5-115F, and the ST 50 catalog also lists S5-115H. The module occupies one slot in the S5-115 system, converts digital CPU commands to bipolar voltages and uses an external 24 V DC supply.
Typical loads include a drive with a bipolar analog input or a proportional valve amplifier that accepts a ±10 V reference signal. A bidirectional drive can interpret positive and negative voltages as commands for opposite directions, depending on its input configuration. The 6ES5 470-7LC13 is a separate model with +1–5 V and +4–20 mA ranges.
Fixed output range and common reference
The ±10 V range is fixed in hardware. Use the 7LB13 wiring arrangement when replacing a module from a system that also uses variants such as the 470-7LA12, which provides current outputs. ST 50 specifies a minimum resistive load of 3.3 kΩ for voltage outputs, a 1 ms conversion time and an external supply range of 20–30 V DC, including ripple.
All eight channels share the MANA analog reference. The galvanic isolation separates the output circuit from the S5 bus. For multiple receivers, check their analog returns and grounding arrangement against the panel schematic.
Front connector and load wiring
The 46-pin 490 front connector is available as the 6ES5 490-7LB21 screw-terminal version or the 6ES5 490-7LA11 crimp version with contacts. The 6ES5 490-7LA21 comes without crimp contacts. The 24-pin 490-7LB11 is a different connector.
Run separate field conductors from QV and S+ to the positive load terminal and from MANA and S− to the negative terminal. The sense leads measure voltage at the load. Siemens specifies compensation for a voltage drop of up to 3 V per lead with this arrangement.
On every unused channel, jumper QV to S+ and S− to MANA at the front connector. Use the 470-7LB wiring diagram to distinguish the wired channels from the jumper positions.
STEP 5 addressing and output words
The slot in the S5 rack determines the module base address. There is no address setting on the module. On an S5-115U with a CPU 944 or CPU 945, check the peripheral output addresses in the STEP 5 project. Each channel uses two bytes. Word addresses advance in two-byte steps. With a base address of 128, channel 0 uses PW 128 and channel 7 uses PW 142.
The nominal scale is −1024 → −10 V, 0 → 0 V and +1024 → +10 V. With the unused low four bits set to zero, the Siemens output words are KH C000, KH 0000 and KH 4000, respectively.
Editor’s note
Record the full 6ES5 470-7LB13 order number, rack and slot. When assessing a 7LB11 or 7LB12 spare, compare the hardware and wiring for both full order numbers.
If all eight outputs are missing, check the module’s external 24 V DC supply first. The field supply can be absent while the PS 951 rack power supply is running.
If only one channel is off target, compare the voltage at QV and MANA with the reading at the receiver. Then check that channel’s S+ and S− terminals for loose connections or broken conductors.
Photograph the wired terminals and unused-channel jumpers before removing the connector. Check the jumper positions against the wiring diagram on the replacement.
With the machine in a safe test state, check −10 V, 0 V and +10 V at the receiver. Compare the polarity and scale of the drive’s analog command input with the PLC command.
OtomasyonAVM resources and PDFs
SIMATIC S5 analog modules · SIMATIC S5 racks
SIMATIC S5-115 PDF archive · SIMATIC S5-115H system manual – analog output wiring (PDF)
Related topics
6ES5 470-7LB12 – ±10 V output · 6ES5 470-7LA12 – voltage and current output · 6ES5 470-7LC13 – +1–5 V and +4–20 mA output
S5 navigation
Siemens S5 PLC › S5-90U–115U CPU family › S5 analog modules
Siemens and other external references
Siemens 6ES5 470-7LB13 data sheet – full order number and ±10 V output
Siemens ST 50 catalog – 470 specifications and ordering data, pp. 3/49–3/50
Siemens S5-115U system manual – 470-7LB load wiring, Figure 10-28
Siemens S5-115U system manual – analog output word format, §10.8.2