6ES5 470-4UC13

Siemens 6ES5 470-4UC13 – 8-Channel 1–5 V / 4–20 mA Analog Output Module

Siemens 6ES5 470-4UC13 is an 8-channel analog output module for S5-135U/155U systems in the Siemens SIMATIC S5 family. Each channel provides 1–5 V voltage and 4–20 mA current outputs driven by the same digital command. Within the S5 analog module range, its output group is galvanically isolated from the system; the eight channels share a common MANA reference. It converts values from the SIMATIC S5 program into continuous process commands.

Typical loads include drive reference inputs and valve positioners with matching analog inputs. It can serve speed control, pressure control, level control and flow control applications, provided the receiving input accepts the selected 1–5 V or 4–20 mA range.

Output ranges and channel arrangement

When comparing 0–10 V and 4–20 mA interfaces, remember that this model’s nominal voltage range is 1–5 V, not 0–10 V. The voltage and current terminals of a channel follow the same command; they do not provide 16 independently controlled channels. Match the analog signal type to the receiving device’s analog input configuration.

In analog control applications, the module outputs the reference calculated by the PLC. For PID control with a PLC, process feedback is acquired through a separate input; the PID calculation is not performed by this output module. The specified delay from data transfer until the analog output exceeds 99% of its final value is 5 ms maximum.

Power, load limits and front connector

The digital section draws approximately 250 mA from the 5 V system bus. The analog section requires an external 24 V DC supply, 200–400 mA. Voltage loads must be at least 3.3 kΩ; total current-loop resistance, including wiring, must be 300 Ω or less. Group isolation does not mean that each channel is isolated from the other channels.

The S5 front connector uses 1: F+, 2: F−, 3: L+, 21: L− and 42: MANA. Channel 0 uses 4: QV0, 5: S+0, 6: S−0 and 7: QI0. Follow the Siemens terminal diagram for the remaining channels. When arranging grounding, distinguish the functions of L−, MANA and protective earth.

The voltage output’s S+ and S− sense leads monitor voltage at the load. For current-only operation, or when a voltage output is unused, fit the corresponding S+ → QV and S− → MANA jumpers. Unused current outputs may remain open. Where cable voltage drop matters, route the sense leads to the load according to the Siemens four-wire connection diagram.

STEP 5 addressing and scaling

The module occupies 16 address bytes, with one word per channel. Select a start address that is a multiple of 16; each channel’s word address is start address + 2 × channel number. With a start address of 160, channel 0 uses word address 160 and channel 7 uses 174. The PLC program must match the module’s physical address-switch setting.

Siemens specifies 12-bit two’s-complement representation with a nominal range of 0–1024 units: 0 produces 1 V / 4 mA, 512 produces 3 V / 12 mA, and 1024 produces 5 V / 20 mA. For direct peripheral-word writes with the lower four bits cleared, these points correspond to 0000h, 2000h and 4000h. Distinguish these raw words from the engineering scale used by a conversion function block.

Enable circuit and stopping behavior

With the F+/F− enable circuit active, an external 24 V signal is required. The enable jumper is fitted at the factory; removing it disables supervision through this input. Missing enable voltage can prevent the module from acknowledging bus access and cause a QVZ timeout. During PLC troubleshooting, check the address switches, enable jumper and supply together.

The 470 analog output module does not evaluate the BASP output-inhibit signal; it retains the last output value. Do not assume that a CPU stop automatically drives the outputs to zero. Output values can drift if the external 24 V supply remains energized while the PLC is powered down; assess stopping behavior together with the power and control arrangement.

Differences between similar order codes

6ES5 470-4UA13 provides ±10 V and 0–20 mA, while 6ES5 470-4UB13 provides ±10 V. The 4UC13 uses 1–5 V and 4–20 mA. Although 6ES5 470-4UC12 belongs to the same nominal signal family, replacement still requires checking the hardware version, wiring and existing program.

Editor’s note

Read the complete 4UC13 suffix first. A similar-looking 470 module with a ±10 V range is not automatically suitable for an existing 1–5 V receiver. Compare the nameplate and signal range together.

A zero command means 4 mA / 1 V on this model. A 4 mA reading at zero is expected. Check the 0%, 50% and 100% points against 4–12–20 mA and 1–3–5 V on each channel.

Test current outputs in a closed loop. Connect the ammeter in series and keep the combined receiver, wiring and meter resistance within 300 Ω. An open-circuit voltage reading does not verify current accuracy.

Keep the sense jumpers in current-only installations. Connecting a load to QI alone is insufficient; verify S+–QV and S−–MANA for that channel. Rule out missing jumpers before diagnosing a module fault.

Include a stopping test. Because BASP does not automatically reset these outputs, a used-module check should also cover CPU stop, F+/F− behavior and removal of the 24 V supply. Use a suitable test load that cannot move the machine.

OtomasyonAVM resources and PDFs

+ S5 analog modules and related module pages

+ S5 cable and front-connector pages

+ Shared S5 PDF archive – system manuals and technical documents

Related topics

+ 6ES5 470-4UA13 – ±10 V / 0–20 mA

+ 6ES5 470-4UB13 – ±10 V

+ 6ES5 470-4UC12 – 1–5 V / 4–20 mA

Browse SIMATIC S5

+ S5 analog modules

+ SIMATIC S5

+ Siemens S5 PLC

+ Siemens used models

Siemens and external references

+ Siemens S5-135U/155U System Manual – §9.7, pp. 9-106–9-121 (English)

+ Siemens S5 → S7-1500 migration guide – Table 7-7, signal-range comparison (English)