6ES5 701-0LA11

Siemens 6ES5 701-0LA11 ER 701-0 expansion rack

The 6ES5 701-0LA11 is the ER 701-0 rack for an EU 0 expansion unit in a SIMATIC S5-115U system. This SIMATIC S5 rack has six I/O slots numbered 0–5 and a dedicated IM slot. The Siemens manual lists dimensions of 353 × 303 × 47 mm (W × H × D) and a weight of 4 kg.

The CR 700-0LA is an example of a central controller rack. The ER 701-0 uses a local, centralised connection and receives power through the IM. Power can come from the central controller or, in a supported layout, from an ER 701-2 or ER 701-3 expansion unit. The ER 701-1 is a separate model with nine I/O slots.

Choosing the interface, cable and I/O

The IM slot takes an IM 305 or IM 306. The IM 305 connects one expansion unit through a permanently attached cable and uses fixed slot addressing. Analogue I/O requires an IM 306. When replacing an interface module, record its complete order number and the installed addressing scheme.

For an IM 306 layout, choose a 705-series connecting cable that suits the physical installation. Siemens lists the short 705-0AF00 as well as the 705-0BB20 (1.25 m) and 705-0BC50 (2.5 m). In a centralised IM 306 layout, the maximum total cable length is 2.5 m.

Siemens lists block-type modules for digital input, digital output, combined digital I/O and analogue I/O. The 6ES5 430-7LA12 is an example of a block-type digital input module. Siemens excludes the 434-7 digital input family from this rack’s slot table. Hardware interrupt processing is unavailable on the ER 701-0.

Editor’s note
  1. Before replacement, photograph the rack and IM labels. Record each module order number and front-connector position for slots 0–5.
  2. After safely isolating the power, check the backplane pins, IM socket and module guides for damage or corrosion.
  3. If all EU 0 cards become inaccessible together, follow the shared path. Start with the rack supplying power, then check the IM pair and connecting cable.
  4. If only one module is affected, check its backplane contact and front connector. Compare the I/O address you are monitoring in STEP 5 with the wiring diagram.
  5. If digital cards respond but analogue readings are missing, check the IM label first. With an IM 306 installed, compare the analogue module’s address and range settings with the original record.
  6. After replacement, keep actuator power circuits isolated while you monitor the inputs in STEP 5. Verify that each field signal changes at its recorded address.

When buying a used rack, confirm whether the offer includes the rack, IM and cable. To offer a rack for sale, send photos of its label and backplane to otomasyonavm@gmail.com.

PDFs and Siemens references

Siemens ST 50 catalogue, p. 3/63 (EN) · S5-115U manual, Figure 3-9 (EN) · S5-115U manual, technical data p. 15-7 (EN).

Siemens S5 PDF archive