6ES5 701-0LA11
Siemens 6ES5 701-0LA11 ER 701-0 expansion rack
The 6ES5 701-0LA11 is the ER 701-0 rack for an EU 0 expansion unit in a SIMATIC S5-115U system. This SIMATIC S5 rack has six I/O slots numbered 0–5 and a dedicated IM slot. The Siemens manual lists dimensions of 353 × 303 × 47 mm (W × H × D) and a weight of 4 kg.
The CR 700-0LA is an example of a central controller rack. The ER 701-0 uses a local, centralised connection and receives power through the IM. Power can come from the central controller or, in a supported layout, from an ER 701-2 or ER 701-3 expansion unit. The ER 701-1 is a separate model with nine I/O slots.
Choosing the interface, cable and I/O
The IM slot takes an IM 305 or IM 306. The IM 305 connects one expansion unit through a permanently attached cable and uses fixed slot addressing. Analogue I/O requires an IM 306. When replacing an interface module, record its complete order number and the installed addressing scheme.
For an IM 306 layout, choose a 705-series connecting cable that suits the physical installation. Siemens lists the short 705-0AF00 as well as the 705-0BB20 (1.25 m) and 705-0BC50 (2.5 m). In a centralised IM 306 layout, the maximum total cable length is 2.5 m.
Siemens lists block-type modules for digital input, digital output, combined digital I/O and analogue I/O. The 6ES5 430-7LA12 is an example of a block-type digital input module. Siemens excludes the 434-7 digital input family from this rack’s slot table. Hardware interrupt processing is unavailable on the ER 701-0.
- Before replacement, photograph the rack and IM labels. Record each module order number and front-connector position for slots 0–5.
- After safely isolating the power, check the backplane pins, IM socket and module guides for damage or corrosion.
- If all EU 0 cards become inaccessible together, follow the shared path. Start with the rack supplying power, then check the IM pair and connecting cable.
- If only one module is affected, check its backplane contact and front connector. Compare the I/O address you are monitoring in STEP 5 with the wiring diagram.
- If digital cards respond but analogue readings are missing, check the IM label first. With an IM 306 installed, compare the analogue module’s address and range settings with the original record.
- After replacement, keep actuator power circuits isolated while you monitor the inputs in STEP 5. Verify that each field signal changes at its recorded address.
When buying a used rack, confirm whether the offer includes the rack, IM and cable. To offer a rack for sale, send photos of its label and backplane to otomasyonavm@gmail.com.
PDFs and Siemens references
Siemens ST 50 catalogue, p. 3/63 (EN) · S5-115U manual, Figure 3-9 (EN) · S5-115U manual, technical data p. 15-7 (EN).